Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS203 M AC-C13/0.03 is a 13 A 3-pole Type AC 30 mA RCBO with C-curve overcurrent protection and 10 kA breaking capacity for commercial and industrial three-phase electrical circuits.
£213.54
The ABB DS203 M AC-C13/0.03, order code 2CSR273001R1134, is a high-performance 3-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.
This DS200 M series RCBO uses Type AC residual-current protection together with a C tripping characteristic. It provides protection against indirect contact and, with its 30 mA rated residual operating current, additional protection against direct contact. The C-curve characteristic is suited to circuits with moderate starting or inrush currents, including many commercial and industrial loads.
With a rated current of 13 A, 400 V AC rated voltage, 30 mA residual-current sensitivity and 10 kA breaking capacity, the DS203 M AC-C13/0.03 provides robust combined protection for three-pole circuits. Its DIN rail construction makes it suitable for professional distribution boards and control panels where dependable three-phase circuit protection is required.
An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS203 M AC-C13/0.03 protects all three poles of the connected circuit against excessive current while also detecting sinusoidal alternating earth leakage currents, providing coordinated protection for three-phase commercial and industrial distribution systems.
The DS203 M AC-C13/0.03 combines a 13 A C-curve overcurrent characteristic with 30 mA Type AC residual-current protection and a 10 kA breaking capacity. This combination makes it suitable for three-phase circuits with moderate inrush currents where combined overcurrent, short-circuit and Type AC earth fault protection is required.
| Product group | DS200 / DSH200 RCBO |
|---|---|
| Series | DS200 M |
| ABB order code | 2CSR273001R1134 |
| EAN | 8012542852704 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3 |
| Protected poles | 3 |
| Rated current | 13 A |
| Tripping characteristic | C curve |
| Rated residual current (IΔn) | 30 mA |
| Residual current type | Type AC |
| Operating characteristic | Instantaneous |
| Rated voltage | 400 V AC |
| Breaking capacity | 10 kA |
| Standards | IEC/EN 60947-2; IEC/EN 61009-1 |
| Terminal type | Screw terminals |
| Application | Commercial and industrial electrical installations |
| Mounting | DIN rail |
| Width | approx. 87 mm |
| Height | approx. 93 mm |
| Depth | approx. 69 mm |
| Weight | approx. 0.61 kg |
The ABB DS203 M AC-C13/0.03 is a 3-pole RCBO used to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial installations.
The RCBO has a rated current of 13 A and uses a C-curve tripping characteristic.
The DS203 M AC-C13/0.03 has a rated residual operating current of 30 mA and uses Type AC residual-current protection.
The DS203 M AC-C13/0.03 has a 10 kA breaking capacity, providing robust short-circuit protection for suitable commercial and industrial three-phase installations.
Type AC means the RCBO is designed to detect sinusoidal alternating residual currents, providing residual-current protection for applications where this type of earth leakage current is expected.
ABB DS200 M RCBOs combine residual-current and overcurrent protection in factory-assembled devices designed for reliable electrical distribution, with the DS203 M range providing three-pole protection for commercial and industrial three-phase applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.