2CSR273001R1134 ABB DS203 M AC-C13/0.03 RCBO 3P 13 A 30 mA 10 kA

2CSR273001R1134 ABB DS203 M AC-C13/0.03 RCBO 3P 13 A 30 mA 10 kA

ABB DS203 M AC-C13/0.03 is a 13 A 3-pole Type AC 30 mA RCBO with C-curve overcurrent protection and 10 kA breaking capacity for commercial and industrial three-phase electrical circuits.

SKU: 2CSR273001R1134Alt SKU: DS203MACC130.03MPN: 2CSR273001R1134
Price
List Price £328.52 ex VAT
Your Price (ex VAT) Save 35%
£213.54 35% OFF
You save £114.98 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £213.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£213.54

Why Choose the ABB DS203 M AC-C13/0.03 RCBO?

The ABB DS203 M AC-C13/0.03, order code 2CSR273001R1134, is a high-performance 3-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.

This DS200 M series RCBO uses Type AC residual-current protection together with a C tripping characteristic. It provides protection against indirect contact and, with its 30 mA rated residual operating current, additional protection against direct contact. The C-curve characteristic is suited to circuits with moderate starting or inrush currents, including many commercial and industrial loads.

With a rated current of 13 A, 400 V AC rated voltage, 30 mA residual-current sensitivity and 10 kA breaking capacity, the DS203 M AC-C13/0.03 provides robust combined protection for three-pole circuits. Its DIN rail construction makes it suitable for professional distribution boards and control panels where dependable three-phase circuit protection is required.

Key Advantages

  • Combined residual current, overload and short-circuit protection in one device.
  • 13 A rated current with C-curve overcurrent tripping characteristic.
  • 30 mA residual current sensitivity provides additional protection against direct contact.
  • Type AC protection for sinusoidal alternating residual currents.
  • 3-pole configuration with three protected poles.
  • 10 kA breaking capacity for demanding commercial and industrial applications.
  • Factory-assembled RCBO construction combines residual-current and overcurrent protection in a single device.
  • DIN rail mounting enables straightforward integration into modular three-phase distribution systems.

Key Features

  • ABB DS200 M RCBO series.
  • 13 A rated current.
  • C tripping characteristic.
  • 30 mA rated residual current (IΔn).
  • Type AC residual-current protection.
  • 3-pole configuration.
  • 3 protected poles.
  • 400 V AC rated voltage.
  • 10 kA breaking capacity.
  • Instantaneous operating characteristic.
  • Protection against overload and short-circuit currents.
  • Protection against sinusoidal alternating earth fault currents.
  • Protection against indirect contact and additional protection against direct contact.
  • Designed for commercial and industrial three-phase electrical applications.

Reliable 10 kA Three-Phase Circuit Protection

An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS203 M AC-C13/0.03 protects all three poles of the connected circuit against excessive current while also detecting sinusoidal alternating earth leakage currents, providing coordinated protection for three-phase commercial and industrial distribution systems.

The DS203 M AC-C13/0.03 combines a 13 A C-curve overcurrent characteristic with 30 mA Type AC residual-current protection and a 10 kA breaking capacity. This combination makes it suitable for three-phase circuits with moderate inrush currents where combined overcurrent, short-circuit and Type AC earth fault protection is required.

Typical Applications

  • Commercial three-phase electrical distribution systems.
  • Industrial distribution boards and control panels.
  • Circuits requiring combined 13 A overcurrent and 30 mA residual-current protection.
  • Three-phase resistive and inductive loads suited to a C-curve characteristic.
  • Three-pole circuits requiring Type AC residual-current protection.
  • Installations requiring a 10 kA breaking capacity.

Technical Specifications

Product group DS200 / DSH200 RCBO
Series DS200 M
ABB order code 2CSR273001R1134
EAN 8012542852704
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 3
Protected poles 3
Rated current 13 A
Tripping characteristic C curve
Rated residual current (IΔn) 30 mA
Residual current type Type AC
Operating characteristic Instantaneous
Rated voltage 400 V AC
Breaking capacity 10 kA
Standards IEC/EN 60947-2; IEC/EN 61009-1
Terminal type Screw terminals
Application Commercial and industrial electrical installations
Mounting DIN rail
Width approx. 87 mm
Height approx. 93 mm
Depth approx. 69 mm
Weight approx. 0.61 kg

Frequently Asked Questions

What is the ABB DS203 M AC-C13/0.03 used for?

The ABB DS203 M AC-C13/0.03 is a 3-pole RCBO used to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial installations.

What is the current rating of the DS203 M AC-C13/0.03?

The RCBO has a rated current of 13 A and uses a C-curve tripping characteristic.

What residual current sensitivity does this RCBO have?

The DS203 M AC-C13/0.03 has a rated residual operating current of 30 mA and uses Type AC residual-current protection.

What is the breaking capacity of the ABB DS203 M AC-C13/0.03?

The DS203 M AC-C13/0.03 has a 10 kA breaking capacity, providing robust short-circuit protection for suitable commercial and industrial three-phase installations.

What does Type AC mean on the ABB DS203 M AC-C13/0.03?

Type AC means the RCBO is designed to detect sinusoidal alternating residual currents, providing residual-current protection for applications where this type of earth leakage current is expected.