Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202 M A-C63/0.03 is a 63 A 2-pole Type A 30 mA RCBO with C-curve overcurrent protection and 10 kA short-circuit breaking capacity for commercial and industrial electrical circuits.
£235.76
The ABB DS202 M A-C63/0.03, order code 2CSR272101R1634, is a high-performance 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect electrical circuits against overloads, short circuits and earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.
This DS200 M series RCBO uses Type A residual-current protection together with a C tripping characteristic. Type A protection detects both sinusoidal alternating and pulsating DC residual currents, making it suitable for circuits supplying modern electrical and electronic equipment. Its 30 mA rated residual operating current provides protection against indirect contact and additional protection against direct contact.
With a rated current of 63 A, 230 V AC rated operational voltage, 30 mA residual-current sensitivity and 10 kA rated short-circuit breaking capacity, the DS202 M A-C63/0.03 provides robust combined protection for demanding two-pole circuits. This 63 A version is also provided with additional terminals for remote tripping, extending its suitability for professional distribution and control applications.
An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS202 M A-C63/0.03 provides Type A residual-current detection, allowing it to respond to sinusoidal alternating as well as pulsating DC earth fault currents. This makes Type A protection particularly relevant to modern circuits containing electronic equipment capable of producing non-sinusoidal residual currents.
The DS202 M A-C63/0.03 combines its 63 A C-curve overcurrent characteristic with 30 mA residual-current protection and a 10 kA rated short-circuit breaking capacity. Its additional remote-tripping terminals further enhance integration into professional commercial and industrial distribution systems where remote operation or control functionality is required.
| Product group | DS200 / DSH200 RCBO |
|---|---|
| Series | DS200 M |
| ABB order code | 2CSR272101R1634 |
| EAN | 8012542849407 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 63 A |
| Tripping characteristic | C curve |
| Rated residual current (IΔn) | 30 mA |
| Residual current type | Type A |
| Operating characteristic | Instantaneous |
| Rated voltage | 230 V AC |
| Rated operational voltage | 230 V AC |
| Rated frequency | 50–60 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 15 kA at 400 V AC |
| Standards | IEC/EN 60947-2; IEC/EN 61009-1 |
| Additional provision | Additional terminals for remote tripping |
| Application | Commercial and industrial electrical installations |
| Mounting | DIN rail |
| Width | 70 mm |
| Height | 93 mm |
| Depth | 69 mm |
| Weight | approx. 0.44 kg |
The ABB DS202 M A-C63/0.03 is a 2-pole Type A RCBO used to protect commercial and industrial electrical circuits against overloads, short circuits and sinusoidal AC or pulsating DC earth fault currents.
The RCBO has a rated current of 63 A and uses a C-curve tripping characteristic.
The DS202 M A-C63/0.03 has a rated residual operating current of 30 mA, providing protection against indirect contact and additional protection against direct contact.
The DS202 M A-C63/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA and a rated ultimate short-circuit breaking capacity (Icu) of 15 kA at 400 V AC.
Type A means the RCBO is designed to detect both sinusoidal alternating and pulsating DC residual currents, making it suitable for circuits where electronic equipment may produce pulsating DC earth leakage components.
ABB DS200 M RCBOs combine residual-current and overcurrent protection in factory-assembled devices designed for reliable commercial and industrial electrical distribution, with high short-circuit breaking capacity and Type A options for circuits requiring detection of both sinusoidal AC and pulsating DC residual currents.