ABB DS202MAB500.03 is a 2-pole 50 A Type B Type A RCBO with 30 mA residual-current sensitivity and 10 kA short-circuit capacity for commercial and industrial circuit protection.
£228.64
The ABB DS202MAB500.03 is a high-performance 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to provide combined protection against overloads, short circuits and earth fault currents. Part of the proven ABB DS200 / DS202 M series, it combines residual-current and overcurrent protection within a factory-assembled DIN-rail device for demanding commercial and industrial electrical installations.
With a rated current of 50 A, 30 mA residual-current sensitivity and Type B tripping characteristic, the DS202 M A-B50/0.03 provides dependable protection for final circuits requiring sensitive overcurrent operation. Its Type A residual-current detection responds to sinusoidal alternating and pulsating DC earth fault currents, making it suitable for modern circuits containing electronic equipment.
The DS202MAB500.03 provides a rated short-circuit capacity of 10 kA and is intended for commercial and industrial applications. ABB supplies this model under order code 2CSR272101R1505, with a test pushbutton for functional verification and indication features that assist inspection and fault identification.
RCBOs combine overcurrent and residual-current protection within a single protective device. The ABB DS202 M A-B50/0.03 protects connected circuits against overload and short-circuit currents while also detecting sinusoidal alternating and pulsating DC earth fault currents that can occur in modern electrical installations.
The ABB DS200 range is designed for demanding commercial and industrial applications. Its factory-combined construction helps reduce installation time, while features including the test pushbutton, earth fault indication and contact-position indication support efficient testing, maintenance and fault identification.
| Series | DS200 / DS202 M |
|---|---|
| SKU | DS202MAB500.03 |
| ABB order code | 2CSR272101R1505 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 50 A |
| Tripping characteristic | B |
| Residual-current type | A |
| Rated residual current | 30 mA |
| Rated short-circuit capacity (Icn) | 10 kA |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Weight | 0.44 kg |
| Mounting | DIN rail |
The ABB DS202MAB500.03 provides combined protection against overloads, short circuits and Type A residual currents in commercial and industrial electrical installations.
The RCBO has a rated current of 50 A and uses a Type B tripping characteristic.
The DS202 M A-B50/0.03 has a rated residual operating current of 30 mA and uses Type A detection for sinusoidal alternating and pulsating DC residual currents.
The device has a rated nominal short-circuit breaking capacity of 10 kA, making it suitable for demanding commercial and industrial circuit-protection applications.
The ABB order code is 2CSR272101R1505.