ABB DS202 M AC-B6/0.03 is a 6 A 2-pole Type AC 30 mA RCBO with B-curve overcurrent protection and 10 kA short-circuit breaking capacity for commercial and industrial electrical circuits.
£153.32
The ABB DS202 M AC-B6/0.03, order code 2CSR272001R1065, is a high-performance 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.
This DS200 M series RCBO uses Type AC residual-current protection together with a B tripping characteristic. It provides protection against indirect contact and, with its 30 mA rated residual operating current, additional protection against direct contact. The B-curve characteristic is suited to circuits where lower magnetic trip thresholds are appropriate, including many resistive and low-inrush loads.
With a rated current of 6 A, 30 mA residual-current sensitivity and 10 kA rated short-circuit breaking capacity, the DS202 M AC-B6/0.03 provides robust combined protection for two-pole circuits. Its DIN rail construction makes it suitable for professional distribution-board and control-panel installations requiring dependable circuit and residual-current protection.
An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS202 M AC-B6/0.03 protects connected circuits against excessive current while also detecting sinusoidal alternating earth leakage currents, providing a coordinated protection solution for commercial and industrial electrical distribution.
The DS200 M series is designed for demanding applications and provides a 10 kA rated short-circuit breaking capacity. Its 30 mA Type AC protection provides additional protection against direct contact where Type AC residual-current detection is appropriate, while the B-curve characteristic provides overcurrent protection suited to circuits with relatively low inrush currents.
| Product group | DS200 / DSH200 RCBO |
|---|---|
| Series | DS200 M |
| ABB order code | 2CSR272001R1065 |
| EAN | 8012542932208 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Protected poles | 2 |
| Rated current | 6 A |
| Tripping characteristic | B curve |
| Rated residual current (IΔn) | 30 mA |
| Residual current type | Type AC |
| Rated voltage | 230 V AC |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 15 kA at 400 V AC |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Application | Commercial and industrial electrical installations |
| Mounting | DIN rail |
| Weight | approx. 0.44 kg |
The ABB DS202 M AC-B6/0.03 is a 2-pole RCBO used to protect electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial installations.
The RCBO has a rated current of 6 A and uses a B-curve tripping characteristic.
The DS202 M AC-B6/0.03 has a rated residual operating current of 30 mA and uses Type AC residual-current protection.
The DS202 M AC-B6/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA.
Type AC means the RCBO is designed to detect sinusoidal alternating residual currents, providing residual-current protection for applications where this type of earth leakage current is expected.
ABB DS200 M RCBOs combine residual-current and overcurrent protection in factory-assembled devices designed for reliable commercial and industrial electrical distribution, with high short-circuit breaking capacity and straightforward integration into modular installations.