2CSR256440R3134 ABB DS203NC C13 APR300 RCBO 3P+N 13 A 300 mA

2CSR256440R3134 ABB DS203NC C13 APR300 RCBO 3P+N 13 A 300 mA

ABB DS203NC C13 APR300 is a 13 A 3P+N Type A APR 300 mA high-immunity RCBO with C-curve overcurrent protection and 6 kA short-circuit breaking capacity for commercial and industrial three-phase circuits.

SKU: 2CSR256440R3134Alt SKU: DS203NCC13APR300MPN: 2CSR256440R3134
Price
List Price £329.61 ex VAT
Your Price (ex VAT) Save 35%
£214.25 35% OFF
You save £115.36 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £214.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£214.25

Why Choose the ABB DS203NC C13 APR300 RCBO?

The ABB DS203NC C13 APR300, order code 2CSR256440R3134, is a compact 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase circuits against overloads, short circuits and earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, this Type A APR device combines residual-current and overcurrent protection in a space-saving four-module format for commercial and industrial electrical installations.

The DS203NC C13 APR300 provides protection against sinusoidal alternating and pulsating DC residual currents while incorporating circuit-breaker protection against overload and short-circuit conditions. Its Type A APR high-immunity characteristic provides enhanced resistance to unwanted tripping caused by transient disturbances, with a surge-current withstand of 3 kA and a 10 ms short-time delay helping to improve continuity of service.

With a rated current of 13 A, C tripping characteristic, 300 mA rated residual operating current and 6 kA rated short-circuit breaking capacity, the DS203NC C13 APR300 provides comprehensive protection for three-phase systems with or without a neutral conductor. Its compact 3P+N four-module design combines multiple protection functions in a single DIN rail device while helping minimise distribution-board space.

Key Advantages

  • Combined residual current, overload and short-circuit protection in one device.
  • 13 A rated current with C-curve overcurrent tripping characteristic.
  • 300 mA residual current sensitivity for earth fault protection.
  • Type A detection for sinusoidal AC and pulsating DC residual currents.
  • APR high-immunity design provides increased resistance to unwanted tripping.
  • 3P+N configuration with three protected poles and four-pole switching.
  • 6 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • Compact four-module construction reduces distribution-board space compared with separate RCD and MCB protection.

Key Features

  • ABB DS203NC RCBO series.
  • 13 A rated current.
  • C tripping characteristic.
  • 300 mA rated residual current (IΔn).
  • Type A APR residual current protection.
  • High immunity to unwanted tripping with short-time delayed operation.
  • 3P+N pole configuration with three protected poles and four-pole switching.
  • 6 kA rated short-circuit breaking capacity (Icn).
  • 10 kA ultimate short-circuit breaking capacity (Icu) according to IEC/EN 60947-2.
  • 3 kA surge-current withstand with an 8/20 µs impulse waveform.
  • 10 ms short-time delay for improved immunity to transient disturbances.
  • Test pushbutton for verification of correct residual-current protection operation.
  • Earth fault indicator and contact position indicator assist with fault identification and maintenance.
  • Compact four-module DIN rail format for space-efficient switchboard installation.

High-Immunity Protection for Three-Phase Circuits

An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS203NC C13 APR300 therefore protects connected circuits against excessive current while detecting earth leakage currents that could create electrical hazards, damage equipment or contribute to electrically initiated fires.

ABB APR residual-current protection is designed to provide an effective balance between safety and continuity of service. Its increased immunity to transient disturbances, 3 kA surge-current withstand and 10 ms short-time delay reduce the risk of unwanted tripping, making the DS203NC C13 APR300 particularly suitable for commercial and industrial installations where dependable operation is important.

Typical Applications

  • Three-phase commercial electrical distribution systems.
  • Industrial distribution boards and switchboards.
  • Circuits requiring combined overcurrent and 300 mA residual-current protection.
  • Installations requiring increased resistance to unwanted RCD tripping.
  • Three-phase equipment and machinery distribution circuits.
  • Commercial and industrial installations requiring compact combined circuit protection.

Technical Specifications

Product group DS200 / DSH200 RCBO
Series DS203NC
ABB order code 2CSR256440R3134
EAN 8012542518020
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 3P+N
Protected poles 3
Switching poles 4
Rated current 13 A
Tripping characteristic C curve
Rated residual current (IΔn) 300 mA
Residual current type Type A APR
Operating characteristic High immunity / short-time delayed
Rated short-circuit breaking capacity (Icn) 6 kA
Ultimate short-circuit breaking capacity (Icu) 10 kA
Surge-current withstand 3 kA (8/20 µs)
APR short-time delay 10 ms
Standard IEC/EN 61009-1
Application Commercial and industrial electrical installations
Mounting DIN rail
Width 4 modules
Weight approx. 0.48 kg

Frequently Asked Questions

What is the ABB DS203NC C13 APR300 used for?

The ABB DS203NC C13 APR300 is a 3P+N RCBO used to protect three-phase circuits against overloads, short circuits and residual earth fault currents in commercial and industrial electrical installations.

What is the current rating of the DS203NC C13 APR300?

The RCBO has a rated current of 13 A and uses a C-curve tripping characteristic.

What residual current sensitivity does this RCBO have?

The DS203NC C13 APR300 has a rated residual operating current of 300 mA and uses Type A APR residual-current protection.

What is the breaking capacity of the ABB DS203NC C13 APR300?

The device has a rated short-circuit breaking capacity (Icn) of 6 kA according to IEC/EN 61009-1 and an ultimate short-circuit breaking capacity (Icu) of 10 kA according to IEC/EN 60947-2.

What does APR mean on the ABB DS203NC C13 APR300?

APR identifies ABB's high-immunity residual-current characteristic, providing increased resistance to unwanted tripping with a 3 kA surge-current withstand and 10 ms short-time delay while maintaining Type A residual-current protection.

Trusted ABB Circuit Protection

ABB DS203NC APR RCBOs provide compact combined residual-current and overcurrent protection with enhanced resistance to unwanted tripping, supporting reliable operation in modern commercial and industrial three-phase electrical installations.