ABB DS203NC C20 APR100 is a 20 A 3P+N Type A APR 100 mA high-immunity RCBO with C-curve overcurrent protection and 6 kA short-circuit breaking capacity for commercial and industrial three-phase circuits.
£214.25
The ABB DS203NC C20 APR100, order code 2CSR256440R2204, is a compact 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase circuits against overloads, short circuits and earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, this Type A APR device combines residual-current and overcurrent protection in a space-saving four-module format for commercial and industrial electrical installations.
The DS203NC C20 APR100 provides protection against sinusoidal alternating and pulsating DC residual currents while incorporating circuit-breaker protection against overload and short-circuit conditions. Its Type A APR high-immunity characteristic provides enhanced resistance to unwanted tripping, with increased surge-current withstand and short-time delayed operation helping to maintain continuity of service where transient disturbances are present.
With a rated current of 20 A, C tripping characteristic, 100 mA rated residual operating current and 6 kA rated short-circuit breaking capacity, the DS203NC C20 APR100 provides comprehensive protection for three-phase systems with neutral. Its compact 3P+N four-module design combines multiple protection functions in a single DIN rail device while helping minimise distribution-board space.
An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS203NC C20 APR100 therefore protects connected circuits against excessive current while detecting earth leakage currents that could create electrical hazards, damage equipment or contribute to electrically initiated fires.
ABB APR residual-current protection is designed to provide an effective balance between safety and continuity of service. Its increased immunity to transient disturbances, 3 kA surge-current withstand and 10 ms short-time delay reduce the risk of unwanted tripping, making the DS203NC C20 APR100 particularly suitable for commercial and industrial installations where dependable operation is important.
| Product group | DS200 / DSH200 RCBO |
|---|---|
| Series | DS203NC |
| ABB order code | 2CSR256440R2204 |
| EAN | 8012542179924 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3P+N |
| Total poles | 4 |
| Protected poles | 3 |
| Rated current | 20 A |
| Tripping characteristic | C curve |
| Rated residual current (IΔn) | 100 mA |
| Residual current type | Type A APR |
| Operating characteristic | High immunity / short-time delayed |
| Rated short-circuit breaking capacity (Icn) | 6 kA |
| Ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Surge-current withstand | 3 kA (8/20 µs) |
| APR short-time delay | 10 ms |
| Standards | IEC/EN 61009-1 |
| Application | Commercial, industrial and building electrical installations |
| Mounting | DIN rail |
| Width | 4 modules |
| Weight | approx. 0.48 kg |
The ABB DS203NC C20 APR100 is a 3P+N RCBO used to protect three-phase circuits against overloads, short circuits and residual earth fault currents in commercial and industrial electrical installations.
The RCBO has a rated current of 20 A and uses a C-curve tripping characteristic.
The DS203NC C20 APR100 has a rated residual operating current of 100 mA and uses Type A APR residual-current protection.
The device has a rated short-circuit breaking capacity (Icn) of 6 kA according to IEC/EN 61009-1 and an ultimate short-circuit breaking capacity (Icu) of 10 kA according to IEC/EN 60947-2.
APR identifies ABB's high-immunity residual-current characteristic, providing increased resistance to unwanted tripping with a 3 kA surge-current withstand and 10 ms short-time delay while maintaining Type A residual-current protection.
ABB DS203NC APR RCBOs provide compact combined residual-current and overcurrent protection with enhanced resistance to unwanted tripping, supporting reliable operation in modern commercial and industrial three-phase electrical installations.