Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS203NCC10A300 is a 3P+N Type A RCBO with 10 A rated current, C tripping characteristic, 300 mA residual-current sensitivity and 6 kA breaking capacity for three-phase circuit protection.
£164.87
The ABB DS203NCC10A300 is a compact and reliable 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents. As part of the ABB DS203NC series, it combines residual-current and overcurrent protection within a space-saving four-module device for modern electrical distribution systems.
This RCBO features a 10 A rated current, C tripping characteristic and Type A residual-current detection. Type A protection detects sinusoidal AC residual currents as well as pulsating DC residual currents, making the DS203NCC10A300 suitable for a wide range of commercial and industrial circuits containing modern electronic loads.
With a rated residual operating current of 300 mA, a rated voltage of 400–415 V AC and a rated short-circuit breaking capacity of 6 kA according to EN/IEC 61009, the DS203NCC10A300 provides coordinated circuit and earth-fault protection. Its compact 3P+N four-module construction incorporates three protected poles and a switched neutral for efficient installation in three-phase distribution boards.
RCBOs combine the functions of a miniature circuit breaker and residual-current device in a single protective unit. The ABB DS203NCC10A300 monitors the circuit for overload and short-circuit conditions while simultaneously detecting residual currents to earth, providing coordinated protection for conductors, connected equipment and electrical installations.
The ABB DS203NC range is engineered to provide this combined protection in only four DIN modules. The DS203NCC10A300 also incorporates earth-fault trip indication, helping operators distinguish residual-current operation during troubleshooting and reducing the time required to identify the cause of a circuit interruption.
| Series | DS203NC |
|---|---|
| SKU | DS203NCC10A300 |
| ABB order code | 2CSR256140R3104 |
| EAN | 8012542839729 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3P+N / 4 poles |
| Protected poles | 3 |
| Rated current | 10 A |
| Tripping characteristic | C |
| Residual-current type | Type A |
| Rated residual operating current | 300 mA |
| Rated voltage | 400–415 V AC |
| Frequency | 50/60 Hz |
| Rated short-circuit breaking capacity Icn | 6 kA |
| Rated ultimate short-circuit breaking capacity Icu | 10 kA |
| Rated service short-circuit breaking capacity Ics | 6 kA |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP2X |
| Operating temperature | -25 to +55 °C |
| Terminal capacity | Up to 25 mm² conductor |
| Busbar connection capacity | 10 mm² |
| Mounting type | DIN rail |
| Width | 4 modules / 71 mm |
| Built-in depth | 69 mm |
| Weight | approx. 0.48 kg |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS203NCC10A300 is a 3P+N RCBO designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents.
The RCBO has a rated current of 10 A and uses a C tripping characteristic.
The DS203NCC10A300 provides Type A residual-current protection with a rated residual operating current of 300 mA.
The device has a rated short-circuit breaking capacity Icn of 6 kA according to EN/IEC 61009 and an ultimate short-circuit breaking capacity of 10 kA according to IEC 60947-2.
The DS203NCC10A300 occupies four DIN modules with a width of 71 mm, providing 3P+N residual-current and overcurrent protection in a compact installation footprint.
ABB DS203NC RCBOs combine residual-current and overcurrent protection in a compact four-module format, providing dependable circuit protection for modern three-phase commercial and industrial electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.