ABB 2CSR256140R2324 DS203NC C32 A100 compact 3P+N RCBO with a 32 A rated current, C tripping characteristic, Type A residual current detection and 100 mA sensitivity.
£164.87
The ABB 2CSR256140R2324, also identified as the DS203NC C32 A100, is a compact residual current circuit breaker with overcurrent protection (RCBO) designed for three-phase electrical distribution systems. Combining residual current, overload and short-circuit protection in one device, it helps safeguard electrical equipment, installations and users while reducing the space required inside distribution boards.
As part of ABB's System pro M compact DS203NC series, this RCBO features a 3P+N configuration within a compact four-module housing. It provides protection for all three phase conductors while switching the neutral conductor, making it suitable for commercial, industrial and infrastructure applications where reliable protection and efficient panel design are essential.
The DS203NC C32 A100 has a rated current of 32 A, a C tripping characteristic and a rated residual operating current of 100 mA. Its Type A residual current detection responds to sinusoidal AC and pulsating DC residual currents, while its rated operating voltage of 400–415 V AC supports standard three-phase power distribution systems.
The ABB DS203NC C32 A100 monitors current flowing through the phase and neutral conductors while also protecting the circuit against excessive load and short-circuit currents. When a qualifying earth leakage, overload or short-circuit fault is detected, the device automatically disconnects the circuit to help reduce the risk of equipment damage, electric shock and electrical fires.
Its four-module design provides a space-efficient alternative to installing separate miniature circuit breakers and residual current devices. This makes the RCBO particularly valuable in compact switchboards, retrofit projects and distribution panels where available DIN rail space is limited.
Tick the specs you need, then view products that match.
| Poles | 3-pole + N | |
|---|---|---|
| Current | 32 A | |
| Phase | Three Phase | |
| Device Type | RCBO | |
| Trip Curve | C curve | |
| Breaking Capacity | 6 kA | |
| Residual Current | 100 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | DS203NC | |
| Model | DS203NC C32 A100 | |
| Product ID | 2CSR256140R2324 | |
| Product type | Residual current circuit breaker with overcurrent protection | |
| Device abbreviation | RCBO | |
| Number of poles | 4 | |
| Configuration | 3P+N | |
| Number of protected poles | 3 | |
| Rated current | 32 A | |
| Tripping characteristic | C | |
| Residual current type | Type A | |
| Rated residual current | 100 mA | |
| Rated voltage | 400–415 V AC | |
| Rated insulation voltage | 500 V | |
| Rated impulse withstand voltage | 4 kV | |
| Rated frequency | 50 / 60 Hz | |
| Rated short-circuit capacity | 6 kA at 230 / 400 V AC | |
| Ultimate short-circuit breaking capacity | 10 kA | |
| Conditional short-circuit current | 10 kA | |
| Service short-circuit breaking capacity | 6 kA | |
| Energy limiting class | 3 | |
| Overvoltage category | III | |
| Residual current operation | Undelayed | |
| Electrical endurance | 10,000 cycles | |
| Mechanical endurance | 20,000 cycles | |
| Power loss | 15.1 W | |
| Mounting type | DIN rail | |
| Module width | 4 modules | |
| Terminal capacity | Up to 25 mm² rigid or flexible conductor | |
| Standards | IEC/EN 61009-1 and IEC/EN 61009-2-1 | |
| EAN | 8012542831129 | |
| Weight | Approx. 0.47 kg | |
| HS Code | 85363030 | |
| Country of Manufacture | Italy |
It protects three-phase electrical circuits against earth leakage, overloads and short circuits in commercial, industrial and infrastructure installations.
The ABB DS203NC C32 A100 has a rated current of 32 A and a C-curve tripping characteristic.
The device has a rated residual operating current of 100 mA and uses Type A residual current detection.
It has a 3P+N configuration with four poles in total and overcurrent protection applied to the three phase conductors.
The DS203NC occupies four DIN modules, providing combined residual current and overcurrent protection in a compact format.
ABB DS203NC RCBOs provide compact and dependable protection for three-phase circuits, helping electrical engineers and panel builders create safe, space-efficient distribution systems.