2CSR256140R2105 ABB DS203NCB10A100 DS203NC B10 A100 10 A 100 mA Type A RCBO 3P+N

2CSR256140R2105 ABB DS203NCB10A100 DS203NC B10 A100 10 A 100 mA Type A RCBO 3P+N

ABB DS203NCB10A100 is a 10 A B-curve 3P+N Type A RCBO with 100 mA residual-current sensitivity and 6 kA short-circuit capacity for three-phase circuit protection.

SKU: 2CSR256140R2105Alt SKU: DS203NCB10A100MPN: 2CSR256140R2105
Price
List Price £279.00 ex VAT
Your Price (ex VAT) Save 35%
£181.35 35% OFF
You save £97.65 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £181.35
Trade pricing is personalised to your account

Manufacturer Lead Time

£181.35

Why Choose the ABB DS203NCB10A100 RCBO?

The ABB DS203NCB10A100 (DS203NC B10 A100) is a compact and reliable residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and earth leakage faults. As part of the ABB System pro M compact DS203NC series, it combines residual-current and overcurrent protection in a single device for commercial and industrial electrical installations.

This Type A RCBO detects sinusoidal AC residual currents as well as pulsating DC residual currents, making it suitable for circuits supplying a wide range of modern electrical equipment. Its 100 mA rated residual operating current provides earth-leakage protection, while the integrated B tripping characteristic provides responsive overcurrent protection for circuits with relatively low starting and inrush currents.

With a rated current of 10 A and a 3P+N configuration, the DS203NCB10A100 is designed for three-phase circuits requiring combined overcurrent and residual-current protection. Its compact DIN-rail format helps conserve distribution-board space while providing coordinated circuit protection within a single device.

Key Advantages

  • Combined residual-current and overcurrent protection in one compact RCBO.
  • 10 A rated current with B tripping characteristic.
  • 100 mA rated residual current for earth-leakage protection.
  • Type A residual-current detection for sinusoidal AC and pulsating DC residual currents.
  • 3P+N configuration designed for three-phase circuits with neutral.
  • Compact DIN-rail design for space-efficient distribution-board installation.

Key Features

  • ABB System pro M compact DS203NC series.
  • 10 A rated current.
  • B tripping characteristic.
  • 100 mA rated residual current.
  • Type A residual-current protection.
  • 3P+N configuration for three-phase circuits with neutral.
  • 6 kA rated short-circuit capacity (Icn).
  • Protection against overload, short circuit and residual earth leakage currents.
  • DIN-rail mounting for straightforward integration into electrical distribution systems.

Reliable Protection for Three-Phase Electrical Circuits

RCBOs such as the ABB DS203NC combine the functions of a miniature circuit breaker and residual-current device in one unit. This enables a single protective device to respond to overloads, short circuits and earth leakage currents while simplifying distribution-board design and reducing the space required for separate protective devices.

The DS203NC Type A range is designed for commercial and industrial installations where protection against sinusoidal AC and pulsating DC residual currents is required. The B characteristic provides responsive protection for circuits with relatively low inrush currents, while its 100 mA residual-current sensitivity provides earth-leakage protection for appropriately designed circuits.

Typical Applications

  • Three-phase commercial electrical circuits.
  • Industrial distribution boards and control panels.
  • Three-phase circuits requiring 100 mA residual-current protection.
  • Control and auxiliary circuits.
  • Building services and electrical distribution systems.
  • Circuits with relatively low inrush currents requiring B-curve protection.

Technical Specifications

Series System pro M compact DS203NC
SKU DS203NCB10A100
ABB order code 2CSR256140R2105
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Pole configuration 3P+N
Rated current 10 A
Tripping characteristic B curve
Rated residual current 100 mA
Residual-current type Type A
Rated short-circuit capacity (Icn) 6 kA
Frequency 50 / 60 Hz
Mounting type DIN rail
Width 4 modules / approx. 71 mm
Dimensions (W × H × D) approx. 71 × 85 × 69 mm
Net weight approx. 0.48 kg
Standards IEC/EN 61009-1, IEC/EN 61009-2-1

Frequently Asked Questions

What is the ABB DS203NCB10A100 used for?

The ABB DS203NCB10A100 is used to protect three-phase circuits with neutral against overloads, short circuits and residual earth leakage currents.

What is the rated current of the DS203NCB10A100?

The RCBO has a rated current of 10 A and uses a B tripping characteristic.

What residual-current sensitivity does this RCBO provide?

The DS203NCB10A100 has a rated residual operating current of 100 mA for earth-leakage protection in appropriately designed electrical circuits.

What does Type A mean on this ABB RCBO?

Type A means the RCBO is designed to detect sinusoidal alternating residual currents as well as pulsating DC residual currents.

What is the breaking capacity of the ABB DS203NCB10A100?

The DS203NCB10A100 has a rated short-circuit capacity Icn of 6 kA, providing dependable short-circuit protection for suitable commercial and industrial circuits.

Trusted ABB Circuit Protection

ABB System pro M compact circuit protection devices are designed for dependable electrical distribution in commercial and industrial installations, combining compact construction with coordinated protection against electrical faults.