Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS203NCK10A30 is a 10 A 3P+N Type K RCBO with 30 mA Type A residual-current protection, a 415 V AC rating and a 6 kA rated short-circuit breaking capacity.
£194.84
The ABB DS203NCK10A30 is a compact 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase end-user circuits against overloads, short circuits and residual earth-fault currents. Part of the ABB DS203NC series, it combines residual-current and overcurrent protection within a single four-module device for efficient commercial and industrial electrical distribution.
This RCBO has a rated current of 10 A, a Type K tripping characteristic and a rated residual operating current of 30 mA. Its Type A residual-current characteristic detects sinusoidal alternating and pulsating DC residual currents, providing protection for modern electrical circuits where these residual-current waveforms may occur.
With a rated voltage of 415 V AC and a rated short-circuit breaking capacity of 6 kA, the DS203NC K10 A30 provides integrated protection for three-phase plus neutral circuits. Its Type K characteristic is particularly suited to appropriate circuits with higher starting or inrush currents, while its compact four-module construction helps conserve valuable distribution-board space.
The ABB DS203NCK10A30 combines overcurrent and residual-current protection within one modular device. Its overcurrent function protects against overload and short-circuit currents, while its Type A residual-current function responds to sinusoidal alternating and pulsating DC earth-fault currents that can occur in modern electrical installations.
With a residual-current sensitivity of 30 mA, the DS203NCK10A30 provides protection against indirect contact and additional protection against direct contact where applicable. Its Type K characteristic makes it suitable for appropriate loads with comparatively high starting currents, while the four-module 3P+N format provides comprehensive protection without requiring separate overcurrent and residual-current devices.
| Series | DS203NC |
|---|---|
| SKU | DS203NCK10A30 |
| ABB order code | 2CSR256140R1107 |
| Product group | DS200 / DSH200 RCBO |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 10 A |
| Tripping characteristic | K |
| Rated residual operating current | 30 mA |
| Residual-current type | A |
| Number of poles | 4 (3P+N) |
| Number of protected poles | 3 |
| Rated voltage | 415 V AC |
| Rated frequency | 50/60 Hz |
| Rated short-circuit breaking capacity (Icn) | 6 kA |
| Short-circuit breaking capacity to IEC 60947-2 | 10 kA |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Current limiting class | 3 |
| Operating characteristic | Undelayed |
| Overvoltage category | III |
| Pollution degree | 2 |
| Degree of protection | IP2X |
| Neutral conductor | Simultaneously switched |
| Maximum conductor cross-section | 25 mm² |
| Power loss | 5.6 W |
| Operating temperature | -25 to +55 °C |
| Mounting type | DIN rail |
| Width | 4 modules |
| Installation depth | 69 mm |
| Weight | 480 g |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 |
| Application | Commercial and industrial |
| EAN | 8012542375920 |
The ABB DS203NCK10A30 is a 3P+N RCBO designed to protect three-phase end-user circuits against overloads, short circuits and residual earth-fault currents.
The DS203NCK10A30 has a rated current of 10 A and uses a Type K tripping characteristic, making it suitable for appropriate circuits where higher starting currents may occur.
The device has a rated residual operating current of 30 mA and uses Type A residual-current detection for sinusoidal alternating and pulsating DC residual currents.
The DS203NCK10A30 has a rated short-circuit breaking capacity of 6 kA according to IEC/EN 61009 and a short-circuit breaking capacity of 10 kA according to IEC 60947-2.
The ABB DS203NCK10A30 occupies four DIN-rail modules and has an installation depth of approximately 69 mm, integrating residual-current and overcurrent protection within a compact 3P+N device.
ABB DS203NC Type A residual current circuit breakers with overcurrent protection combine compact three-phase circuit protection with detection of sinusoidal AC and pulsating DC residual currents, providing integrated protection for modern commercial and industrial electrical systems.