ABB DS203NCC25AC300 is a 25 A 3P+N Type C RCBO with 300 mA Type AC residual-current protection, a 400–415 V AC rating and 6 kA rated short-circuit breaking capacity.
£137.36
The ABB DS203NCC25AC300 is a compact and reliable 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents. As part of the ABB DS203NC RCBO series, it combines residual-current and overcurrent protection within a single four-module device for efficient electrical distribution installations.
This RCBO has a rated current of 25 A, a Type C tripping characteristic and a rated residual operating current of 300 mA. Its Type AC residual-current characteristic detects sinusoidal alternating residual currents, making the device suitable for appropriate AC circuits where this form of residual-current protection is specified.
With a rated voltage of 400–415 V AC and a rated short-circuit breaking capacity of 6 kA, the DS203NC C25 AC300 provides coordinated protection for three-phase plus neutral circuits. Its compact four-module DIN-rail format integrates multiple protection functions into one device, helping conserve valuable space in distribution boards and electrical control panels.
RCBOs such as the ABB DS203NCC25AC300 combine the functions of an overcurrent protective device and a residual-current protective device in a single unit. This enables the device to respond to overload and short-circuit conditions while its residual-current function detects earth-fault currents, providing coordinated protection for suitable three-phase electrical circuits.
The DS203NC series is designed for compact three-phase distribution systems. Its 3P+N arrangement and four-module construction help conserve panel space compared with separate protective devices, while the Type C overcurrent characteristic is suitable for appropriate circuits where moderate inrush currents can occur during normal operation.
| Series | DS203NC |
|---|---|
| SKU | DS203NCC25AC300 |
| ABB order code | 2CSR256040R3254 |
| Product group | DS200 / DSH200 RCBO |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 25 A |
| Tripping characteristic | C |
| Rated residual operating current | 300 mA |
| Residual-current type | AC |
| Number of poles | 4 (3P+N) |
| Number of protected poles | 3 |
| Rated voltage | 400–415 V AC |
| Rated operational voltage | 415 V AC |
| Rated frequency | 50 / 60 Hz |
| Rated short-circuit breaking capacity (Icn) | 6 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Energy limiting class | 3 |
| Tripping | Undelayed |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP2X |
| Neutral conductor | Simultaneously switched |
| Connectable conductor cross-section | 1–25 mm² |
| Mounting type | DIN rail |
| Width | 4 modules |
| Dimensions (W × H × D) | 71 × 85 × 69 mm |
| Weight | 480 g |
| Standards | IEC 61009-1, IEC 61009-2-1, EN 61009-1, EN 61009-2-1 |
| EAN | 8012542517825 |
The ABB DS203NCC25AC300 is an RCBO designed to protect suitable three-phase plus neutral electrical circuits against overloads, short circuits and residual earth-fault currents.
The RCBO has a rated current of 25 A and uses a Type C tripping characteristic.
The DS203NCC25AC300 has a rated residual operating current of 300 mA and uses a Type AC residual-current characteristic.
The device has a rated short-circuit breaking capacity of 6 kA according to EN 61009-1.
The device has a 3P+N four-pole configuration with three protected phase poles and a simultaneously switched neutral conductor.