2CSR255180R2065 ABB DS201 B6 A100 RCBO 1P+N 6A Type A 100mA 6kA

2CSR255180R2065 ABB DS201 B6 A100 RCBO 1P+N 6A Type A 100mA 6kA

ABB DS201 B6 A100 is a 1P+N 6 A B-curve Type A RCBO with 100 mA residual current sensitivity and 6 kA short-circuit breaking capacity for combined residual current and overcurrent circuit protection.

SKU: 2CSR255180R2065Alt SKU: DS201B6A100MPN: 2CSR255180R2065
Price
List Price £263.67 ex VAT
Your Price (ex VAT) Save 35%
£171.39 35% OFF
You save £92.28 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £171.39
Trade pricing is personalised to your account

Manufacturer Lead Time

£171.39

Why Choose the ABB DS201 B6 A100 RCBO?

The ABB DS201 B6 A100 is a compact and reliable residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase circuits against overloads, short circuits and earth leakage faults. As part of the ABB DS200 / DS201 RCBO range, it combines residual current and overcurrent protection in a single modular device for residential, commercial and industrial electrical distribution.

This RCBO provides a 6 A rated current, B tripping characteristic and 100 mA Type A residual current sensitivity. Type A residual current protection detects sinusoidal AC and pulsating DC residual currents, while the B characteristic is suited to circuits with relatively low inrush currents.

With a 1P+N configuration, 230 V AC rated voltage and 6 kA rated short-circuit breaking capacity, the DS201 B6 A100 provides comprehensive protection in a compact two-module DIN-rail format. ABB order code 2CSR255180R2065 identifies this specific 6 A, B-curve, Type A, 100 mA version.

Key Advantages

  • Combines residual current, overload and short-circuit protection in one device.
  • 6 A rated current for lower-current single-phase circuits.
  • 100 mA rated residual operating current.
  • Type A residual current detection for sinusoidal AC and pulsating DC residual currents.
  • B tripping characteristic suitable for loads with relatively low inrush currents.
  • 6 kA rated short-circuit breaking capacity to IEC/EN 61009.
  • Compact 1P+N two-module design for DIN-rail distribution boards.

Key Features

  • ABB DS201 RCBO series.
  • 6 A nominal current.
  • B-curve tripping characteristic.
  • Type A residual current protection.
  • 100 mA rated residual operating current.
  • 1P+N configuration with one protected pole and two switched poles.
  • 230 V AC rated voltage.
  • 50–60 Hz rated frequency.
  • 6 kA rated short-circuit breaking capacity.
  • 10 kA ultimate short-circuit breaking capacity.
  • Compact two-module DIN-rail construction.

Combined Residual Current and Overcurrent Protection

RCBOs such as the ABB DS201 combine the functions of a miniature circuit breaker and residual current protective device. The DS201 B6 A100 therefore protects the connected single-phase circuit against overload and short-circuit currents while also disconnecting the supply when residual current to earth reaches the device's operating threshold.

The Type A residual current characteristic provides detection of sinusoidal alternating and pulsating direct residual currents. Combined with its 100 mA sensitivity, B tripping characteristic and compact 1P+N construction, the DS201 B6 A100 provides practical protection for suitable residential, commercial and industrial electrical circuits.

Typical Applications

  • Single-phase electrical distribution circuits.
  • Residential and commercial installations.
  • Lighting and building-services circuits.
  • Control and auxiliary circuits.
  • Circuits supplying electronic equipment.
  • Industrial control panels and distribution boards.

Technical Specifications

Series DS201 / DS200 RCBO
ABB order code 2CSR255180R2065
EAN 8012542779414
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Rated current 6 A
Tripping characteristic B
Residual current type Type A
Rated residual operating current 100 mA
Poles 1P+N
Protected poles 1
Rated voltage 230 V AC
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Rated frequency 50–60 Hz
Rated short-circuit breaking capacity (Icn) 6 kA
Ultimate short-circuit breaking capacity (Icu) 10 kA
Protection rating IP20
Width 2 modules
Installation depth 69 mm
Mounting type DIN rail
Operating temperature -25 to +55 °C
Standards IEC/EN 61009-1, IEC/EN 61009-2-1

Frequently Asked Questions

What is the ABB DS201 B6 A100 used for?

The ABB DS201 B6 A100 protects single-phase circuits against overloads, short circuits and residual earth fault currents in one compact RCBO.

What is the current rating of the DS201 B6 A100?

The RCBO has a rated current of 6 A with a B tripping characteristic.

What residual current protection does this RCBO provide?

It provides Type A, 100 mA residual current protection for sinusoidal AC and pulsating DC residual fault currents.

What is the breaking capacity of the DS201 B6 A100?

The DS201 B6 A100 has a rated short-circuit breaking capacity of 6 kA to IEC/EN 61009.

What is the ABB order code for the DS201 B6 A100?

The ABB order code is 2CSR255180R2065.

Trusted ABB Circuit Protection

ABB DS201 RCBOs combine residual current and overcurrent protection in a compact DIN-rail format, providing dependable circuit protection for residential, commercial and industrial electrical installations.