2CSR252101R1137 ABB DS202 A-K13/0.03 RCBO 2P Type A 30mA K13 6kA

2CSR252101R1137 ABB DS202 A-K13/0.03 RCBO 2P Type A 30mA K13 6kA

ABB DS202 A-K13/0.03 is a two-pole Type A RCBO rated at 13 A and 30 mA with a K tripping characteristic and 6 kA short-circuit breaking capacity for residual-current, overload and short-circuit protection in commercial and industrial circuits.

SKU: 2CSR252101R1137Alt SKU: DS202AK130.03MPN: 2CSR252101R1137
Price
List Price £420.98 ex VAT
Your Price (ex VAT) Save 35%
£273.64 35% OFF
You save £147.34 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £273.64
Trade pricing is personalised to your account

Manufacturer Lead Time

£273.64

Why Choose the ABB DS202 A-K13/0.03 RCBO?

The ABB DS202 A-K13/0.03 is a two-pole Type A residual current circuit breaker with overcurrent protection (RCBO) designed to combine residual-current, overload and short-circuit protection within a single modular device. Part of ABB’s DS200 series 6000, it is particularly suited to commercial and industrial circuits containing motors, transformers and auxiliary equipment.

With a rated current of 13 A, a K tripping characteristic and a rated residual operating current of 30 mA, the DS202 A-K13/0.03 provides overcurrent protection while detecting both sinusoidal AC residual currents and pulsating DC residual currents. The 30 mA sensitivity provides additional protection against electric shock, while the K characteristic is designed to tolerate current peaks associated with inductive loads without unnecessary tripping.

The DS202 A-K13/0.03 provides a rated short-circuit breaking capacity of 6 kA and uses a two-pole configuration. Its combination of Type A residual-current detection and K-curve overcurrent protection makes it particularly useful where motors, transformers or auxiliary circuits require dependable protection alongside improved resistance to normal current peaks.

Key Advantages

  • Combined RCBO protection against residual current, overload and short circuit within one device.
  • 30 mA residual-current sensitivity provides additional protection against electric shock.
  • 13 A rated current for suitable commercial and industrial circuits.
  • K tripping characteristic is designed for circuits containing motors, transformers and other loads with significant starting currents.
  • Type A residual-current detection responds to sinusoidal AC and pulsating DC residual currents.
  • 6 kA rated short-circuit breaking capacity.
  • K characteristic helps reduce unwanted operation during current peaks while maintaining sensitive overcurrent protection.

Key Features

  • ABB DS200 series 6000 RCBO.
  • 13 A rated current.
  • 30 mA rated residual operating current (IΔn).
  • K tripping characteristic.
  • Type A residual-current characteristic.
  • Two-pole configuration.
  • 230 V AC rated voltage.
  • 6 kA rated short-circuit breaking capacity (Icn).
  • 10 kA rated ultimate short-circuit breaking capacity (Icu) for industrial applications.
  • Designed to withstand current peaks associated with motors and transformers without unnecessary release.
  • Protection against sinusoidal AC and pulsating DC residual currents.
  • DIN-rail format for modular electrical distribution systems.

Type A Protection with K Characteristic

The ABB DS202 A-K13/0.03 combines Type A residual-current protection with ABB’s K overcurrent characteristic. Type A detection enables the RCBO to respond to sinusoidal alternating residual currents and pulsating DC residual currents, making it suitable for a broader range of electrical equipment than a Type AC device.

The K characteristic is intended particularly for circuits containing motors, transformers and auxiliary equipment. It provides increased tolerance of normal current peaks, helping avoid unwanted tripping during starting conditions, while its sensitive thermal protection supports effective protection of cables, lines and connected equipment against sustained overcurrents.

Typical Applications

  • Commercial electrical distribution systems.
  • Industrial electrical distribution systems.
  • Motor circuits requiring suitable starting-current tolerance.
  • Transformer and auxiliary circuits.
  • Circuits requiring 13 A K-characteristic overcurrent protection.
  • Circuits requiring 30 mA Type A residual-current protection.
  • Applications where normal current peaks could cause unwanted operation of more sensitive overcurrent characteristics.

Technical Specifications

Series DS200 series 6000
Product group DS200 / DSH200 RCBO
ABB order code 2CSR252101R1137
EAN 8012542930402
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 2P
Rated current (In) 13 A
Rated residual current (IΔn) 30 mA
Residual-current type Type A
Tripping characteristic K curve
Rated AC voltage 230 V AC
Rated short-circuit breaking capacity (Icn) 6 kA
Rated ultimate short-circuit breaking capacity (Icu) 10 kA
Tripping mechanism Thermal magnetic
Width 70 mm
Height 93 mm
Module width 4 modules
Mounting type DIN rail
Weight approx. 0.475 kg
Standards IEC/EN 61009-1 and IEC/EN 60947-2
Applications Commercial and industrial

Frequently Asked Questions

What is the ABB DS202 A-K13/0.03 used for?

The ABB DS202 A-K13/0.03 is a Type A RCBO designed to provide residual-current, overload and short-circuit protection, with its K characteristic making it particularly suitable for commercial and industrial circuits containing motors, transformers and auxiliary equipment.

What are the current and residual-current ratings?

The DS202 A-K13/0.03 has a rated current of 13 A and a rated residual operating current of 30 mA.

What does the K characteristic mean?

The K characteristic is designed for circuits where motors, transformers or similar equipment can produce substantial normal current peaks. It provides increased tolerance of these peaks while retaining sensitive thermal overcurrent protection.

What residual currents can the Type A DS202 A-K13/0.03 detect?

As a Type A RCBO, the DS202 A-K13/0.03 is designed to respond to sinusoidal alternating residual currents and pulsating DC residual currents, including residual currents with a smooth DC component of up to 6 mA.

What is the ABB order code for the DS202 A-K13/0.03?

The ABB order code for the DS202 A-K13/0.03 is 2CSR252101R1137.

Trusted ABB Combined Circuit Protection

ABB DS200 RCBOs combine residual-current, overload and short-circuit protection within a single modular device, while the Type A K-characteristic range provides protection tailored to commercial and industrial circuits containing motors, transformers and auxiliary equipment.