Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202 AC-B50/0.03 is a two-pole 50 A B-curve Type AC RCBO with 30 mA residual-current sensitivity, 230 V AC rating and 6 kA short-circuit capacity.
£197.38
The ABB DS202 AC-B50/0.03 is a two-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect electrical circuits against overloads, short circuits and sinusoidal AC earth-fault currents. Part of the ABB DS200 series, it combines overcurrent and residual-current protection in a single DIN-rail device.
This RCBO combines a B-curve overcurrent characteristic with Type AC residual-current detection. It is rated at 50 A with 30 mA residual-current sensitivity, making it suitable for appropriate residential, commercial and industrial circuits where individual residual-current and overcurrent protection is required.
The DS202 AC-B50/0.03 provides a rated short-circuit capacity of 6 kA, operates at a rated voltage of 230 V AC and supports 50/60 Hz systems. Both poles are protected, and this 50 A version is provided with additional terminals for remote tripping.
An RCBO combines miniature circuit breaker and residual-current protection functions within one device. The ABB DS202 AC-B50/0.03 protects against overload and short-circuit currents while also detecting sinusoidal alternating earth-fault currents, providing protection against indirect contact and additional protection against direct contact.
Its 30 mA residual-current sensitivity and individual circuit protection make it suitable for applications where localised fault isolation is desirable. The B-curve characteristic is intended for appropriate circuits with relatively low starting currents, while the two-pole arrangement ensures both poles are protected.
| Series | DS200 |
|---|---|
| ABB order code | 2CSR252001R1505 |
| EAN | 8012542864301 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 50 A |
| Rated voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated residual operating current | 30 mA |
| Residual-current type | Type AC |
| Tripping characteristic | Type B |
| Number of poles | 2 |
| Protected poles | 2 |
| Rated short-circuit capacity | 6 kA |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1, IEC/EN 60947-2 |
| Mounting type | DIN rail |
| Weight | 0.44 kg |
It provides combined protection against overloads, short circuits and sinusoidal AC earth-fault currents in residential, commercial and industrial electrical installations.
The RCBO has a rated current of 50 A and uses a B-curve overcurrent characteristic.
The DS202 AC-B50/0.03 has a rated residual operating current of 30 mA.
The RCBO has a rated short-circuit capacity of 6 kA.
It is a Type AC RCBO, designed to respond to sinusoidal alternating residual currents.