2CSR252001R1165 ABB DS202 AC-B16/0.03 RCBO 2P Type AC 30mA B16 6kA

2CSR252001R1165 ABB DS202 AC-B16/0.03 RCBO 2P Type AC 30mA B16 6kA

ABB DS202 AC-B16/0.03 is a two-pole Type AC RCBO rated at 16 A and 30 mA with a B-curve characteristic and 6 kA short-circuit breaking capacity for combined residual-current, overload and short-circuit protection.

SKU: 2CSR252001R1165Alt SKU: DS202ACB160.03MPN: 2CSR252001R1165
Price
List Price £230.48 ex VAT
Your Price (ex VAT) Save 35%
£149.81 35% OFF
You save £80.67 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £149.81
Trade pricing is personalised to your account

Manufacturer Lead Time

£149.81

Why Choose the ABB DS202 AC-B16/0.03 RCBO?

The ABB DS202 AC-B16/0.03 is a two-pole Type AC residual current circuit breaker with overcurrent protection (RCBO) designed to provide residual-current, overload and short-circuit protection within a single modular device. Part of ABB’s DS200 series, it provides dedicated protection for individual circuits in residential, commercial and industrial electrical distribution systems.

With a rated current of 16 A, a B-curve tripping characteristic and a rated residual operating current of 30 mA, the DS202 AC-B16/0.03 protects against overcurrents while responding to sinusoidal alternating residual currents. Its 30 mA sensitivity provides additional protection against direct contact as well as protection against the effects of indirect contact.

The DS202 AC-B16/0.03 is rated at 230 V AC and provides a rated short-circuit breaking capacity of 6 kA. Its two-pole design protects both poles, while its combined MCB and residual-current functions provide a compact solution for circuits requiring individual fault isolation and comprehensive electrical protection.

Key Advantages

  • Combined RCBO protection against residual current, overload and short circuit in one device.
  • 30 mA residual-current sensitivity provides additional protection against electric shock.
  • 16 A rated current suitable for a wide range of final circuits.
  • B-curve characteristic is suited to circuits with relatively low normal starting and inrush currents.
  • Type AC residual-current detection responds to sinusoidal alternating earth-fault currents.
  • 6 kA rated short-circuit breaking capacity to IEC/EN 61009 requirements.
  • Two protected poles provide comprehensive protection for the connected circuit.

Key Features

  • ABB DS200 series RCBO.
  • 16 A rated current.
  • 30 mA rated residual operating current (IΔn).
  • B tripping characteristic.
  • Type AC residual-current characteristic.
  • Two-pole configuration with two protected poles.
  • 230 V AC rated voltage.
  • 50/60 Hz rated frequency.
  • 6 kA rated short-circuit breaking capacity (Icn).
  • 10 kA rated ultimate short-circuit breaking capacity (Icu) at 400 V AC.
  • Protection against overload and short-circuit currents.
  • Protection against sinusoidal alternating earth-fault currents.

Combined Residual-Current and Overcurrent Protection

An RCBO combines residual-current protection and miniature circuit breaker functions within a single protective device. The ABB DS202 AC-B16/0.03 protects its circuit against earth-fault currents as well as overload and short-circuit conditions, enabling individual circuit protection without requiring separate RCCB and MCB devices to perform these functions.

Its Type AC characteristic responds to sinusoidal alternating residual currents, while the B-curve 16 A characteristic is suited to circuits with relatively low normal inrush currents. Combined with 30 mA residual-current sensitivity and a 6 kA rated short-circuit breaking capacity, the DS202 AC-B16/0.03 provides dependable protection for suitable residential, commercial and industrial final circuits.

Typical Applications

  • Residential electrical distribution boards.
  • Commercial electrical distribution systems.
  • Industrial control and auxiliary circuits.
  • Final circuits requiring 16 A B-curve overcurrent protection.
  • Circuits requiring 30 mA additional residual-current protection.
  • Electrical installations requiring dedicated two-pole RCBO protection and individual fault isolation.

Technical Specifications

Series DS200
Product group DS200 / DSH200 RCBO
ABB order code 2CSR252001R1165
EAN 8012542863809
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 2P
Number of protected poles 2
Rated current (In) 16 A
Rated residual current (IΔn) 30 mA
Residual-current type Type AC
Tripping characteristic B curve
Rated voltage 230 V AC
Rated frequency 50/60 Hz
Rated short-circuit breaking capacity (Icn) 6 kA
Rated ultimate short-circuit breaking capacity (Icu) 10 kA at 400 V AC
Operating temperature -25 to +55 °C
Mechanical durability 20,000 cycles
Electrical life 10,000 cycles
Protection degree IP20
Mounting type DIN rail
Weight approx. 0.44 kg
Standards IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 60947-2

Frequently Asked Questions

What is the ABB DS202 AC-B16/0.03 used for?

The ABB DS202 AC-B16/0.03 is an RCBO that combines overload and short-circuit protection with 30 mA Type AC residual-current protection for residential, commercial and industrial electrical circuits.

What are the current and residual-current ratings?

The DS202 AC-B16/0.03 has a rated current of 16 A and a rated residual operating current of 30 mA.

What does the B characteristic mean?

The B-curve tripping characteristic defines the magnetic overcurrent response of the RCBO and is suited to circuits with relatively low normal starting or inrush currents.

What is the breaking capacity of the ABB DS202 AC-B16/0.03?

The DS202 AC-B16/0.03 has a rated short-circuit breaking capacity of 6 kA under the IEC/EN 61009 RCBO standard.

What is the ABB order code for the DS202 AC-B16/0.03?

The ABB order code for the DS202 AC-B16/0.03 is 2CSR252001R1165.

Trusted ABB Combined Circuit Protection

ABB DS200 RCBOs combine residual-current, overload and short-circuit protection within a single modular device, providing dedicated circuit protection and effective fault isolation for residential, commercial and industrial electrical distribution systems.