2CSF202568R3160 ABB F202 B-16/0.3 RCCB 2P Type B 300 mA 16 A

2CSF202568R3160 ABB F202 B-16/0.3 RCCB 2P Type B 300 mA 16 A

ABB F202 B-16/0.3 is a 2-pole Type B residual current circuit breaker rated at 16 A with 300 mA residual current sensitivity for electrical installations requiring detection of AC, pulsating DC and smooth DC residual currents.

SKU: 2CSF202568R3160Alt SKU: F202B160.3MPN: 2CSF202568R3160
Price
List Price £588.22 ex VAT
Your Price (ex VAT) Save 35%
£382.34 35% OFF
You save £205.88 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £382.34
Trade pricing is personalised to your account

Manufacturer Lead Time

£382.34

Why Choose the ABB F202 B-16/0.3 RCCB?

The ABB F202 B-16/0.3 is a high-performance 2-pole Type B residual current circuit breaker (RCCB) designed to provide dependable residual current protection in electrical installations containing modern power-electronic equipment. As part of the established ABB F200 RCCB series, it is suited to applications where residual currents may include AC, pulsating DC and smooth DC components.

The Type B characteristic extends residual current detection beyond conventional Type A protection, making the F202 B-16/0.3 suitable for circuits containing equipment capable of producing smooth DC residual currents. Its 300 mA rated residual operating current makes it suitable for earth leakage and installation protection applications where Type B detection is required.

With a 16 A rated current and 2-pole configuration, the F202 B-16/0.3 provides residual current protection for specialised single-phase electrical circuits. Its modular DIN-rail construction supports straightforward integration into commercial and industrial electrical distribution boards.

Key Advantages

  • Type B residual current protection for a broad range of AC and DC residual current waveforms.
  • Detects smooth DC residual currents in addition to residual currents covered by Type A devices.
  • 300 mA rated residual current for earth leakage and installation protection applications.
  • 16 A rated current for electrical circuits and equipment.
  • 2-pole configuration suitable for single-phase applications.
  • Compact DIN-rail mounting for modular distribution boards.

Key Features

  • ABB F200 RCCB series.
  • Type B residual current characteristic.
  • Detection of sinusoidal AC, pulsating DC and smooth DC residual currents.
  • 16 A rated current.
  • 300 mA rated residual current.
  • 2-pole design.
  • Suitable for installations containing power-electronic equipment.
  • Residual current protection without integral overcurrent protection.
  • DIN-rail mounting for modular electrical distribution equipment.

Type B Residual Current Protection

RCCBs monitor the balance of current flowing through the active conductors of an electrical circuit and disconnect the supply when residual current to earth exceeds the device operating threshold. Type B RCCBs provide extended detection capabilities for installations where power-electronic equipment can produce residual current waveforms that conventional Type AC or Type A devices are not designed to detect.

The ABB F202 B-16/0.3 can respond to sinusoidal AC, pulsating DC and smooth DC residual currents, making it suitable for specialised applications incorporating electronic converters and other equipment capable of generating DC earth leakage. Its 300 mA sensitivity is intended for earth leakage and installation protection rather than the 30 mA additional protection commonly used for protection against electric shock.

Typical Applications

  • Commercial and industrial electrical distribution systems.
  • Circuits containing power-electronic equipment.
  • Variable-speed drive and frequency-converter applications where Type B protection is required.
  • Equipment capable of producing smooth DC residual currents.
  • Circuits requiring 300 mA Type B residual current protection.
  • Specialised single-phase electrical installations requiring AC and DC residual current detection.

Technical Specifications

Series F200
Order code 2CSF202568R3160
Product type Residual current circuit breaker (RCCB)
Residual current type Type B
Number of poles 2
Rated current 16 A
Rated residual current 300 mA
Mounting type DIN rail

Frequently Asked Questions

What is the ABB F202 B-16/0.3 used for?

It is a 2-pole Type B RCCB designed for residual current protection in applications where AC, pulsating DC and smooth DC residual currents may occur.

What is the rated current of the F202 B-16/0.3?

The ABB F202 B-16/0.3 has a rated current of 16 A.

What residual current sensitivity does this RCCB provide?

It has a rated residual operating current of 300 mA, making it suitable for earth leakage and installation protection applications requiring Type B residual current detection.

What does Type B mean on this ABB RCCB?

Type B indicates extended residual current detection that includes smooth DC residual currents as well as sinusoidal AC and pulsating DC residual currents.

Why would a Type B RCCB be used instead of a Type A RCCB?

A Type B RCCB is used where connected equipment can produce smooth DC or other residual current waveforms beyond the detection capability required of a Type A device, such as certain power-electronic and converter-based applications.

Trusted Residual Current Protection from ABB

ABB F200 residual current circuit breakers provide modular residual current protection for a wide range of electrical installations, with Type B variants extending protection to applications where AC and DC residual current components can occur.