ABB F202 A-100/0.3 is an instantaneous 2-pole Type A F200 residual current circuit breaker rated at 100 A with 300 mA residual-current sensitivity for compatible residential, commercial and industrial low-voltage electrical installations.
£188.53
The ABB F202 A-100/0.3 is a 2-pole Type A residual current circuit breaker (RCCB) from the ABB F200 series, designed to protect people and electrical installations against fault currents to earth. Supplied under ABB order code 2CSF202101R3900, it combines a high rated current of 100 A with a rated residual operating current of 300 mA.
As a Type A RCCB, the F202 A-100/0.3 is designed to respond to sinusoidal alternating residual currents and pulsating direct residual currents. This makes it suitable for compatible residential, commercial and industrial circuits containing modern electrical and electronic loads capable of producing these residual-current waveforms.
The F202 A-100/0.3 provides instantaneous operation, a rated voltage of 230 V and a rated frequency of 50–60 Hz. Its two-pole modular construction is designed for DIN-rail installation, while its 100 A current rating makes it suitable for higher-current residual-current protection applications.
Type A RCCBs are designed to detect both sinusoidal alternating residual currents and pulsating direct residual currents. This broader residual-current response makes the ABB F202 A-100/0.3 suitable for compatible circuits containing electrical and electronic equipment that can produce pulsating DC components during fault conditions.
With its 100 A current rating and 300 mA residual-current sensitivity, the F202 A-100/0.3 is suited to appropriate higher-current earth-fault and installation-protection applications. It is an RCCB rather than an RCBO and therefore does not provide integral overload or short-circuit protection; suitable overcurrent protection must be provided separately according to the circuit design and applicable installation requirements.
| Product group | F200 / FH200 RCCB |
|---|---|
| Series | F200 |
| Order code | 2CSF202101R3900 |
| Product type | Residual Current Circuit Breaker (RCCB) |
| Number of poles | 2 |
| Rated current (In) | 100 A |
| Rated residual current (IΔn) | 300 mA |
| Residual current type | Type A |
| Residual-current detection | Sinusoidal AC and pulsating DC residual currents |
| Operating characteristic | Instantaneous |
| Rated voltage | 230 V |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated frequency | 50–60 Hz |
| Power loss | 6.5 W per pole at rated operating conditions |
| Terminal type | Screw terminals |
| Maximum solid conductor connection | 35 mm² |
| Mounting | DIN rail |
| Modular width | 2 modules |
| Width | 35 mm |
| Height | 85 mm |
| Built-in depth | 69 mm |
| Degree of protection | IP20 |
| Operating ambient temperature | -25 to +55 °C |
| Standards | IEC/EN 61008, UL 1053 |
| Product weight | approx. 0.225 kg |
| EAN / GTIN | 8012542915706 |
The ABB F202 A-100/0.3 is a 2-pole Type A residual current circuit breaker from the F200 series, rated at 100 A with a 300 mA rated residual current.
The 300 mA figure is the RCCB's rated residual operating current. This rating is suited to appropriate earth-fault and leakage-current protection applications rather than the 30 mA additional personal protection commonly specified for certain final circuits.
As a Type A RCCB, the F202 A-100/0.3 is designed to respond to sinusoidal alternating residual currents and pulsating direct residual currents.
No. The F202 A-100/0.3 is an RCCB without integral overcurrent protection, so appropriately selected overcurrent protection must be provided separately.
The ABB order code for the F202 A-100/0.3 is 2CSF202101R3900, with EAN / GTIN 8012542915706.
ABB F200 Type A RCCBs provide residual-current protection against sinusoidal alternating and pulsating direct fault currents, with configurations designed for residential, commercial and industrial low-voltage electrical installations.