Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FH202 AC-63/0.3 is a 2-pole Type AC FH200 residual current circuit breaker rated at 63 A with 300 mA residual-current sensitivity for compatible low-voltage electrical installations.
£84.92
The ABB FH202 AC-63/0.3 is a 2-pole residual current circuit breaker (RCCB) from the ABB FH200 family, designed to provide residual-current protection in compatible low-voltage electrical installations. Supplied under ABB order code 2CSF202006R3630, it combines a rated current of 63 A with a rated residual operating current of 300 mA.
As a Type AC RCCB, the FH202 AC-63/0.3 is designed to respond to sinusoidal alternating residual currents. Its 300 mA residual-current rating makes it suitable for appropriate earth-leakage and fault-protection applications where this sensitivity is specified by the circuit design and applicable installation requirements.
The two-pole configuration is intended for compatible single-phase circuits, while its modular construction enables straightforward DIN-rail installation in distribution boards and electrical panels. As an RCCB without integral overcurrent protection, the FH202 AC-63/0.3 must be coordinated with appropriately selected overload and short-circuit protection.
An RCCB monitors the current flowing through the live conductors of a circuit and operates when an imbalance indicates current leakage to earth. The ABB FH202 AC-63/0.3 combines a substantial 63 A rated current with a 300 mA rated residual operating current for compatible residual-current protection applications.
A 300 mA RCCB is generally selected for installation and earth-fault protection applications rather than the 30 mA additional personal protection commonly specified for certain final circuits. The FH202 AC-63/0.3 is an RCCB rather than an RCBO, so it does not provide integral overload or short-circuit protection; suitable overcurrent protection must therefore be provided separately.
| Product group | F200 / FH200 RCCB |
|---|---|
| Series | FH200 |
| Order code | 2CSF202006R3630 |
| Product type | Residual Current Circuit Breaker (RCCB) |
| Number of poles | 2 |
| Rated current (In) | 63 A |
| Rated residual current (IΔn) | 300 mA |
| Residual current type | Type AC |
| Rated operational voltage | 230 V AC |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Frequency | 50/60 Hz |
| Mounting | DIN rail |
| Overcurrent protection | Not incorporated; separate protection required |
The ABB FH202 AC-63/0.3 is a 2-pole Type AC residual current circuit breaker from the FH200 family, rated at 63 A with a 300 mA rated residual current.
The 300 mA figure is the RCCB's rated residual operating current. The device is designed to operate when qualifying residual current reaches its operating threshold, subject to the specified operating characteristics.
The FH202 AC-63/0.3 is a Type AC RCCB, designed to respond to sinusoidal alternating residual currents.
No. The FH202 AC-63/0.3 is an RCCB without integral overcurrent protection, so appropriate circuit-breaker or fuse protection must be provided separately.
The ABB order code for the FH202 AC-63/0.3 RCCB is 2CSF202006R3630.
ABB FH200 RCCBs provide residual-current protection for compatible low-voltage electrical installations, with variants covering different rated currents, residual-current sensitivities and residual-current characteristics.
We use cookies