ABB FH202 AC-40/0.3 is a 2-pole Type AC residual current circuit breaker rated at 40 A with 300 mA residual current sensitivity for residential and commercial low-voltage electrical installations.
£76.77
The ABB FH202 AC-40/0.3 is a 2-pole Type AC residual current circuit breaker (RCCB) designed to provide residual current protection in residential and commercial low-voltage electrical installations. Identified by ABB order code 2CSF202006R3400, it forms part of ABB's FH200 range of modular residual current protection devices.
Rated at 40 A with a rated residual operating current of 300 mA, the FH202 AC-40/0.3 responds to sinusoidal alternating earth fault currents. Its 2-pole configuration provides simultaneous switching of both live conductors, making it suitable for appropriately designed single-phase electrical circuits.
The FH202 AC-40/0.3 occupies 2 × 17.5 mm modules and is designed for compact integration into modular distribution equipment. It provides residual current protection and isolation functions in accordance with the requirements of the FH200 range, while overload and short-circuit protection must be provided separately.
An RCCB monitors the current flowing through the live conductors and detects an imbalance caused by current leaking to earth. When the residual current reaches the device's operating threshold, the RCCB disconnects the circuit. The ABB FH202 AC-40/0.3 combines a 40 A rated current with a 300 mA residual operating current for installations requiring this level of earth-fault protection.
As a Type AC RCCB, the FH202 AC-40/0.3 is intended for applications where sinusoidal alternating residual currents are expected. Its 300 mA sensitivity differs from the 30 mA devices used for additional protection against direct contact, so the RCCB must be selected according to the required protective function and applicable installation rules. Suitable overcurrent protection must also be provided separately.
| Series | FH200 |
|---|---|
| ABB order code | 2CSF202006R3400 |
| Product group | F200 / FH200 RCCB |
| Product type | Residual current circuit breaker (RCCB) |
| Number of poles | 2 |
| Rated current | 40 A |
| Rated residual operating current | 300 mA |
| Residual current type | Type AC |
| Module width | 2 × 17.5 mm |
| Weight | 0.225 kg |
| EAN | 8012542894902 |
| Pack unit | 1/6 pieces |
| Standard | IEC/EN 61008 |
| Application | Residential and commercial buildings |
The ABB FH202 AC-40/0.3 is a 2-pole RCCB designed to detect sinusoidal alternating residual currents and disconnect the protected circuit when earth leakage reaches its 300 mA operating threshold.
The ABB FH202 AC-40/0.3 has a rated current of 40 A.
The FH202 AC-40/0.3 has a rated residual operating current of 300 mA.
Type AC means the RCCB is designed to respond to sinusoidal alternating residual currents. The appropriate residual current device type should be selected according to the connected loads and applicable installation requirements.
No. The FH202 AC-40/0.3 provides residual current protection and does not incorporate overcurrent protection, so suitable protection against overload and short-circuit currents must be provided separately.
ABB FH200 residual current circuit breakers provide dedicated earth-leakage protection for modular low-voltage installations, combining dependable residual current detection with a compact format for residential and commercial electrical distribution systems.