Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F202AC250.01 F202 AC-25/0.01 is a 2-pole Type AC residual current circuit breaker rated at 25 A with 10 mA residual-current sensitivity for compatible single-phase electrical installations.
£88.69
The ABB F202AC250.01, type F202 AC-25/0.01, is a 2-pole Type AC residual current circuit breaker (RCCB) designed to provide residual-current protection in compatible single-phase electrical installations. Part of ABB’s established F200 RCCB family, it combines a rated current of 25 A with a highly sensitive rated residual operating current of 10 mA.
As a Type AC RCCB, the F202 AC-25/0.01 is designed to respond to sinusoidal alternating residual currents. Its 10 mA sensitivity makes it suitable for applications requiring a lower residual-current trip threshold than conventional 30 mA RCCBs, subject to the requirements of the electrical installation and applicable standards.
The device uses ABB’s compact modular format for DIN-rail installation and incorporates a test facility for periodic functional verification. With two poles switching the protected circuit, the F202 AC-25/0.01 provides a purpose-designed residual-current protection solution for residential, commercial and similar electrical distribution applications.
An RCCB monitors the current flowing through the live conductors of a circuit and disconnects the supply when an imbalance exceeds its rated residual operating current. This helps provide protection against residual-current hazards, while separate overcurrent protection is required because an RCCB does not itself provide overload or short-circuit protection.
The ABB F202 AC-25/0.01 has a 10 mA residual operating threshold and a Type AC characteristic for sinusoidal alternating residual currents. Its two-pole configuration and 25 A current rating make it suitable for appropriately designed single-phase circuits where this level and type of residual-current protection is specified.
| Series | F200 |
|---|---|
| SKU | F202AC250.01 |
| ABB order code | 2CSF202001R0250 |
| Product type | Residual current circuit breaker (RCCB) |
| Number of poles | 2 |
| Rated current | 25 A |
| Rated residual operating current | 10 mA |
| Residual-current type | AC |
| Rated voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated conditional short-circuit current | 10 kA |
| Rated impulse withstand voltage | 4 kV |
| Mounting | DIN rail |
| Standard | IEC/EN 61008-1 |
The ABB F202 AC-25/0.01 is a 2-pole Type AC RCCB rated at 25 A with a rated residual operating current of 10 mA.
The 10 mA figure is the RCCB’s rated residual operating current, indicating its high-sensitivity residual-current protection threshold.
Type AC means the RCCB is designed to respond to sinusoidal alternating residual currents. The residual-current type should always be selected to suit the connected loads and installation requirements.
No. The F202 AC-25/0.01 is an RCCB for residual-current protection and does not itself provide overload or short-circuit protection, so suitable overcurrent protection must be provided separately.
The ABB manufacturer order code is 2CSF202001R0250.
ABB F200 residual current circuit breakers provide modular residual-current protection for residential, commercial and industrial electrical distribution systems, with configurations and sensitivities suited to a wide range of installation requirements.