Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA803 A S-100/0.3 is a 100 A three-pole 300 mA Type A selective RCD block designed for coordinated residual current protection with compatible ABB S800 miniature circuit-breakers.
£583.45
The ABB DDA803 A S-100/0.3 is a high-performance Type A selective residual current device (RCD) block designed for assembly with compatible ABB S800 miniature circuit-breakers. As part of the ABB DDA800 series, it provides residual current protection for electrical installations while allowing the associated S800 MCB to provide overload and short-circuit protection.
The selective S characteristic incorporates a time delay that enables coordination with downstream residual current protective devices, helping ensure that a downstream fault is disconnected locally while upstream circuits remain energised where correct selectivity conditions are met. As a Type A device, the DDA803 detects sinusoidal alternating residual currents and pulsating DC residual currents, making it suitable for modern commercial and industrial electrical systems.
With a rated current of 100 A, a three-pole configuration and a rated residual operating current of 300 mA, the DDA803 A S-100/0.3 is well suited to three-phase distribution circuits requiring selective earth leakage and fault protection. Its modular design enables integration with compatible ABB S800 miniature circuit-breakers to create a coordinated protective assembly.
Residual current devices monitor current balance within a protected circuit and operate when leakage to earth exceeds the specified threshold. The 300 mA rated residual current of the ABB DDA803 A S-100/0.3 makes it suitable for appropriate earth fault and leakage protection applications in commercial and industrial distribution systems.
The selective S characteristic provides delayed operation to facilitate coordination with downstream RCDs. When correctly designed, this arrangement allows a downstream residual current device to clear a local fault before the upstream selective device operates, helping improve continuity of supply across unaffected circuits.
| Series | DDA800 |
|---|---|
| ABB order code | 2CSB803201R3000 |
| Product type | Selective RCD block |
| Residual current type | Type A |
| Operating characteristic | Selective S |
| Rated current | 100 A |
| Rated residual current | 300 mA |
| Number of poles | 3 |
| Application | Three-phase electrical distribution |
| Residual current detection | Sinusoidal AC and pulsating DC |
| Compatible product family | ABB S800 miniature circuit-breakers |
The DDA803 A S-100/0.3 is a Type A selective RCD block designed for assembly with compatible ABB S800 miniature circuit-breakers to provide residual current protection in suitable three-phase electrical distribution systems.
The ABB DDA803 A S-100/0.3 has a rated residual operating current of 300 mA.
The S characteristic indicates selective, time-delayed operation designed to support coordination with downstream residual current protective devices.
As a Type A device, it detects sinusoidal alternating residual currents and pulsating DC residual currents.
The ABB order code for the DDA803 A S-100/0.3 is 2CSB803201R3000.
ABB DDA800 RCD blocks are designed to combine with compatible S800 miniature circuit-breakers, providing dependable residual current protection and selective options for demanding commercial and industrial low-voltage distribution systems.