Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA204B630.3APR is a four-pole Type B AP-R DDA200 residual current device block rated at 63 A with 300 mA sensitivity, 10 ms short-time delay and 3 kA surge-current resistance for high-immunity protection in installations containing power electronic loads.
£916.04
The ABB DDA204B630.3APR is a four-pole Type B AP-R residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD series, it provides comprehensive residual-current protection for demanding commercial and industrial installations containing electronic equipment and power-conversion loads.
Rated at 63 A with a rated residual operating current of 300 mA, the DDA204B630.3APR provides Type B detection for sinusoidal AC, pulsating DC and smooth DC residual currents. ABB's AP-R high-immunity characteristic combines resistance to transient disturbances with a short 10 ms intentional delay, helping minimise unwanted tripping and improve continuity of service.
The DDA204B630.3APR has a four-pole configuration and a rated voltage of 230–400 V AC, making it suitable for three-phase systems with neutral. Its 3 kA surge-current resistance further enhances immunity to impulsive leakage currents, while assembly with a compatible ABB S200 series or S300P miniature circuit breaker adds overload and short-circuit protection.
The ABB DDA204B630.3APR provides comprehensive residual-current detection for installations where electronic equipment can generate complex earth-fault currents. Its Type B characteristic covers sinusoidal AC, pulsating DC and smooth DC residual currents, making it particularly appropriate for power electronic equipment, frequency converters and other electronically controlled loads.
ABB's AP-R high-immunity technology combines a short 10 ms delay with 3 kA surge-current resistance to help prevent unwanted operation caused by transient leakage-current peaks. Its 300 mA operating threshold is intended for appropriate higher-threshold residual-current protection applications and does not replace 30 mA additional protection where that sensitivity is required. Overload and short-circuit protection are provided by the compatible miniature circuit breaker assembled with the RCD block.
| Series | DDA200 |
|---|---|
| SKU | DDA204B630.3APR |
| ABB order code | 2CSB204592R3630 |
| EAN | 8012542732921 |
| Product type | Residual current device (RCD) block |
| Residual current type | Type B |
| Operating characteristic | AP-R high immunity |
| Rated current | 63 A |
| Rated residual current | 300 mA |
| Rated voltage | 230–400 V AC |
| Rated operational voltage | 230/400 V AC |
| Number of poles | 4 |
| Rated frequency | 50–60 Hz |
| AP-R short-time delay | 10 ms |
| Maximum surge current | 3 kA |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Power loss | 7.6 W |
| Protection rating | IP2X |
| Operating ambient temperature | -25 to +55 °C |
| Connectable conductor cross-section | up to 25 mm² |
| Dimensions (W × H × D) | 140 × 93 × 69 mm |
| Net weight | approx. 0.337 kg |
| Compatible MCB families | ABB S200 series and S300P |
| Reference standards | IEC/EN 61009 Annex G and IEC/EN 62423 |
The ABB DDA204B630.3APR is a four-pole Type B AP-R RCD block designed for residual-current protection in commercial and industrial installations containing electronic equipment, frequency converters and other loads capable of producing AC, pulsating DC or smooth DC residual currents.
The DDA204B630.3APR has a rated current of 63 A and a rated residual operating current of 300 mA.
Type B provides broad residual-current detection covering sinusoidal alternating, pulsating DC and smooth DC residual currents, making the device suitable for installations containing power electronic equipment capable of generating complex earth-leakage waveforms.
AP-R is ABB's high-immunity characteristic designed to improve resistance to unwanted tripping caused by transient disturbances. The DDA204B630.3APR combines approximately 10 ms short-time delay with 3 kA surge-current resistance.
The DDA204B630.3APR is designed for assembly with compatible ABB S200 series and S300P miniature circuit breakers, creating a combined arrangement in which the RCD block provides residual-current protection and the associated breaker provides overload and short-circuit protection.
ABB DDA200 Type B AP-R residual current blocks combine comprehensive residual-current detection with enhanced immunity to transient disturbances, supporting dependable protection and continuity of service in demanding commercial and industrial installations containing modern power electronic equipment.