Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA204B250.3APR is a four-pole Type B AP-R DDA200 residual current device block rated at 25 A with 300 mA sensitivity for high-immunity protection in installations containing power electronic loads.
£704.66
The ABB DDA204B250.3APR is a four-pole Type B AP-R residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD series, it provides comprehensive residual-current detection for electrical installations containing power electronics, where AC, pulsating DC and smooth DC earth-leakage currents may occur.
Rated at 25 A with a rated residual operating current of 300 mA, the DDA204B250.3APR combines Type B residual-current detection with ABB's AP-R high-immunity characteristic. The AP-R design incorporates a short intentional delay and enhanced resistance to transient disturbances, helping reduce unwanted tripping and improve continuity of service in demanding electrical installations.
The four-pole configuration makes the DDA204B250.3APR suitable for three-phase systems with neutral, particularly where variable-speed drives, frequency converters, UPS systems and other electronic equipment can generate complex residual-current waveforms. When assembled with a compatible ABB miniature circuit breaker, it provides residual-current protection alongside the overload and short-circuit protection supplied by the associated breaker.
The ABB DDA204B250.3APR provides broader residual-current detection than Type AC or Type A devices. Its Type B characteristic enables detection of sinusoidal AC, pulsating DC and smooth DC residual currents, making it suitable for installations containing electronic converters and other equipment capable of producing DC components in earth-leakage currents.
ABB's AP-R high-immunity characteristic incorporates a short intentional delay of approximately 10 ms and enhanced surge-current resistance of up to 3 kA, helping prevent unwanted operation caused by transient leakage-current peaks. Its 300 mA sensitivity is intended for appropriate higher-threshold residual-current protection applications and does not replace 30 mA additional protection where that sensitivity is required.
| Series | DDA200 |
|---|---|
| SKU | DDA204B250.3APR |
| ABB order code | 2CSB204592R3250 |
| Product type | Residual current device (RCD) block |
| Residual current type | Type B |
| Characteristic | AP-R high immunity |
| Rated current | 25 A |
| Rated residual current | 300 mA |
| Number of poles | 4 |
| AP-R delay | 10 ms |
| Maximum surge-current resistance | 3 kA |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Electrical endurance | 10,000 cycles |
| Protection rating | IP2X |
| Operating ambient temperature | -25 to +55 °C |
| Maximum conductor cross-section | 25 mm² |
| Reference standards | IEC/EN 61009 Annex G and IEC/EN 62423 |
| Mounting arrangement | Assembly with compatible ABB miniature circuit breaker |
The ABB DDA204B250.3APR is a four-pole Type B AP-R RCD block intended for residual-current protection in installations containing power electronics, frequency converters and other equipment capable of producing AC, pulsating DC or smooth DC residual currents.
The DDA204B250.3APR has a rated current of 25 A and a rated residual operating current of 300 mA.
Type B provides broad residual-current detection including sinusoidal AC, pulsating DC and smooth DC residual currents, making the device suitable for installations containing power electronic equipment that can generate complex earth-leakage waveforms.
AP-R is ABB's high-immunity characteristic designed to improve resistance to unwanted tripping caused by transient disturbances. This model incorporates a short intentional delay of approximately 10 ms and surge-current resistance of up to 3 kA.
No. The DDA204B250.3APR has a rated residual operating current of 300 mA and is intended for suitable higher-threshold residual-current protection applications. It does not replace a 30 mA RCD where additional protection against electric shock at that sensitivity is required.
ABB DDA200 Type B AP-R residual current blocks provide comprehensive residual-current detection and enhanced immunity to transient disturbances, supporting dependable protection for demanding commercial and industrial installations containing modern power electronic equipment.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.