Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA204 B-63/0.03 AP-R is a four-pole 63 A Type B RCD block with 30 mA residual-current sensitivity and an AP-R high-immunity characteristic for circuits requiring sinusoidal AC, pulsating DC and smooth DC residual-current detection.
£955.93
The ABB DDA204 B-63/0.03 AP-R is a four-pole Type B residual current device (RCD) block with ABB's AP-R high-immunity characteristic, designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD block series, it provides residual-current protection for applications where a broad range of residual-current waveforms may occur.
Type B residual-current protection is designed to respond to sinusoidal AC, pulsating DC and smooth DC residual currents, making this device suitable for installations containing power-electronic equipment capable of producing residual currents beyond the detection scope of Type AC or Type A devices. Its 30 mA rated residual operating current provides high-sensitivity protection, while the AP-R characteristic provides enhanced immunity to transient disturbances.
With a 63 A rated current and four-pole configuration, the DDA204 B-63/0.03 AP-R is suited to multi-pole electrical circuits requiring Type B residual-current protection. When combined with a compatible ABB miniature circuit breaker, the resulting assembly provides residual-current protection alongside the MCB's overcurrent and short-circuit protection.
Electrical equipment incorporating rectifiers, inverters, converters and other power-electronic circuitry can produce residual-current waveforms containing pulsating or smooth DC components. Type B residual-current protection extends detection beyond conventional AC residual currents, making it appropriate for installations where these more complex residual-current forms can occur.
The DDA204 B-63/0.03 AP-R combines broad Type B detection capability with 30 mA sensitivity and ABB's AP-R high-immunity characteristic. This combination supports sensitive residual-current protection while providing enhanced resistance to transient disturbances that could otherwise cause unwanted operation.
| Series | DDA200 |
|---|---|
| ABB order code | 2CSB204592R1630 |
| Product type | Residual current device (RCD) block |
| Residual-current type | B |
| Characteristic | AP-R high immunity |
| Number of poles | 4 |
| Rated current | 63 A |
| Rated residual operating current | 30 mA |
| Residual-current detection | Sinusoidal AC, pulsating DC and smooth DC |
| Applicable standard | IEC/EN 61009 Annex G |
| Mounting | DIN rail as part of a compatible modular circuit protection assembly |
It is a four-pole Type B RCD block designed to provide 30 mA residual-current protection in circuits where sinusoidal AC, pulsating DC or smooth DC residual currents may occur when assembled with a compatible ABB miniature circuit breaker.
The ABB DDA204 B-63/0.03 AP-R has a rated current of 63 A.
It has a rated residual operating current of 30 mA.
Type B residual-current protection is designed to detect sinusoidal AC, pulsating DC and smooth DC residual currents, making it suitable for circuits where power-electronic equipment can produce complex residual-current waveforms.
The AP-R characteristic provides enhanced immunity to transient disturbances, helping reduce unwanted operation and improve continuity of service.
ABB DDA200 Type B RCD blocks provide broad residual-current detection for modern electrical installations, while AP-R variants add enhanced immunity to transient disturbances for dependable modular circuit protection.