Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA204 AC-40/0.03 AP-R is a four-pole 40 A Type AC RCD block with 30 mA residual-current sensitivity and an AP-R high-immunity characteristic for improved resistance to unwanted tripping.
£119.25
The ABB DDA204 AC-40/0.03 AP-R is a four-pole Type AC residual current device (RCD) block with ABB's AP-R high-immunity characteristic, designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD block series, it provides residual-current protection for electrical distribution systems while offering enhanced resistance to unwanted tripping.
This Type AC RCD block is designed to detect sinusoidal alternating residual currents. Its 30 mA rated residual operating current provides high-sensitivity residual-current protection, while the AP-R characteristic improves immunity to transient disturbances that can otherwise cause nuisance operation.
With a 40 A rated current and four-pole configuration, the DDA204 AC-40/0.03 AP-R is suited to multi-pole circuits where Type AC residual-current protection and enhanced continuity of service are required. When combined with a compatible ABB miniature circuit breaker, the assembly provides residual-current protection alongside the MCB's overcurrent and short-circuit protection.
Residual current devices monitor the balance of current flowing through the active conductors of an electrical circuit. If an insulation fault or leakage path causes current to flow to earth, the resulting imbalance can initiate disconnection when the RCD block is correctly combined with its compatible circuit breaker.
The AP-R characteristic is designed to provide increased immunity to transient disturbances compared with standard instantaneous residual-current protection, helping reduce unwanted tripping and improve continuity of service. Combined with 30 mA Type AC protection, the DDA204 AC-40/0.03 AP-R is intended for circuits where sinusoidal AC residual-current detection and enhanced immunity are required.
| Series | DDA200 |
|---|---|
| ABB order code | 2CSB204301R1400 |
| Product type | Residual current device (RCD) block |
| Residual-current type | AC |
| Characteristic | AP-R high immunity |
| Number of poles | 4 |
| Rated current | 40 A |
| Rated residual operating current | 30 mA |
| Rated frequency | 50–60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Applicable standard | IEC/EN 61009 Annex G |
| Mounting | DIN rail as part of a compatible modular circuit protection assembly |
It is a four-pole Type AC RCD block designed to provide 30 mA residual-current protection with enhanced AP-R immunity when assembled with a compatible ABB miniature circuit breaker.
The ABB DDA204 AC-40/0.03 AP-R has a rated current of 40 A.
It has a rated residual operating current of 30 mA.
The AP-R characteristic provides enhanced immunity to transient disturbances, helping reduce unwanted RCD operation and improve continuity of service compared with standard instantaneous protection.
Type AC residual-current protection is designed to detect sinusoidal alternating residual currents.
ABB DDA200 AP-R residual current device blocks combine modular circuit protection integration with enhanced immunity to transient disturbances, helping provide dependable residual-current protection and improved continuity of service.