ABB DDA204 A S-63/0.3 is a four-pole 63 A Type A selective RCD block with 300 mA residual-current sensitivity for coordinated protection against sinusoidal AC and pulsating DC residual currents.
£147.26
The ABB DDA204 A S-63/0.3 is a four-pole Type A selective residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. As part of the ABB DDA200 RCD block series, it combines Type A residual-current detection with selective, time-delayed operation for coordinated protection in electrical distribution systems.
This RCD block detects sinusoidal alternating residual currents and pulsating DC residual currents. Its 300 mA rated residual operating current and selective S-type characteristic make it particularly suitable for upstream protection where coordination with downstream residual-current devices is required.
With a 63 A rated current, four-pole configuration and selective operating characteristic, the DDA204 A S-63/0.3 is well suited to commercial, industrial and building distribution systems. When combined with a compatible ABB miniature circuit breaker, the assembly provides residual-current protection alongside the MCB's overcurrent and short-circuit protection.
Residual current devices monitor the balance of current flowing through the active conductors of an electrical circuit. If an insulation fault or leakage path causes current to flow to earth, the resulting imbalance can initiate disconnection when the RCD block is correctly combined with its compatible circuit breaker.
The selective S-type characteristic introduces intentional time delay to support discrimination between upstream and downstream residual-current protection. Combined with Type A sensitivity to both sinusoidal AC and pulsating DC residual currents, this makes the DDA204 A S-63/0.3 particularly useful in coordinated distribution systems where an upstream RCD should allow an appropriate downstream device to clear a fault first.
| Series | DDA200 |
|---|---|
| ABB order code | 2CSB204201R3630 |
| Product type | Residual current device (RCD) block |
| Residual-current type | A |
| Operating characteristic | Selective, S type |
| Number of poles | 4 |
| Rated current | 63 A |
| Rated residual operating current | 300 mA |
| Rated frequency | 50–60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Applicable standard | IEC/EN 61009 Annex G |
| Mounting | DIN rail as part of a compatible modular circuit protection assembly |
It is a four-pole Type A selective RCD block designed for residual-current protection and coordination with downstream protective devices when combined with a compatible ABB miniature circuit breaker.
The ABB DDA204 A S-63/0.3 has a rated current of 63 A.
It has a rated residual operating current of 300 mA.
The S designation indicates selective, time-delayed operation, helping coordinate an upstream RCD with suitable downstream residual-current protective devices.
Type A protection is designed to detect sinusoidal alternating residual currents and pulsating DC residual currents.
ABB DDA200 residual current device blocks provide modular residual-current protection for coordinated commercial, industrial and building distribution systems, with selective variants designed to support discrimination between protective devices.