ABB DDA202 A-63/1 AE is a 2-pole Type A residual current device block rated at 63 A with 1000 mA residual current sensitivity and additional terminals for emergency-stop remote opening in commercial and industrial installations.
£204.83
The ABB DDA202 A-63/1 AE, order code 2CSB202701R5630, is a 2-pole Type A residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. As part of the ABB DDA200 RCD series, the AE version incorporates two additional terminals for use in emergency circuits, enabling remote opening in positive safety.
This Type A RCD block has a 63 A rated current and a 1000 mA rated residual operating current. It provides protection against the effects of sinusoidal alternating and pulsating DC earth fault currents, making it suitable for commercial and industrial electrical installations requiring Type A residual current detection.
Rated at 230/400 V AC with a 50/60 Hz frequency rating, the DDA202 A-63/1 AE combines residual current protection with dedicated emergency-stop functionality. When assembled with a compatible ABB S200 series or S300P miniature circuit breaker, the RCD block provides residual current protection while the associated MCB provides overcurrent and short-circuit protection.
Type A residual current protection responds to both sinusoidal alternating and pulsating DC residual currents, making the ABB DDA202 A-63/1 AE suitable for commercial and industrial installations containing modern electrical and electronic equipment. Its 1000 mA residual current rating provides earth fault protection for circuits where this sensitivity is specified.
The AE variant adds dedicated emergency-stop functionality through two additional terminals that can be connected to an emergency control circuit using normally closed push buttons for remote opening in positive safety. ABB specifies top-side supply for the DDA200 AE range, and each DDA200 AE requires its own dedicated emergency-stop control circuit.
| Series | DDA200 |
|---|---|
| Order code | 2CSB202701R5630 |
| EAN | 8012542802006 |
| Product group | DDA200 RCD |
| Product type | Residual current device block |
| Residual current type | Type A |
| Application | Emergency stop |
| Rated current | 63 A |
| Rated residual current | 1000 mA (1 A) |
| Rated voltage | 230/400 V AC |
| Rated operational voltage | 230 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Number of poles | 2 |
| Frequency | 50/60 Hz |
| Protection rating | IP2X |
| Power loss | 5 W |
| Connecting capacity | up to 25 mm² rigid or flexible conductor |
| Operating ambient temperature | -25 to +55 °C |
| Standards | IEC/EN 61009-1 Annex G and IEC/EN 61009-2-1 |
| Compatible MCB families | ABB S200 series and S300P |
| Emergency control connection | Two additional terminals for remote opening in positive safety |
| Supply requirement | Top-side supply |
| Weight | approx. 0.18 kg |
The ABB DDA202 A-63/1 AE is a Type A RCD block designed for commercial and industrial electrical installations requiring 1000 mA residual current protection together with emergency-stop functionality for remote opening.
The DDA202 A-63/1 AE has a rated current of 63 A.
The device has a rated residual operating current of 1000 mA, equivalent to 1 A.
The AE version is intended for emergency-stop applications and incorporates two additional terminals that can be used in an emergency control circuit for remote opening in positive safety.
The DDA202 A-63/1 AE is designed for assembly with compatible ABB S200 series and S300P miniature circuit breakers, with the associated MCB providing overcurrent and short-circuit protection.
ABB DDA200 AE RCD blocks combine Type A residual current protection with dedicated emergency-stop functionality, providing a modular solution for commercial and industrial electrical installations requiring remote opening in positive-safety emergency circuits.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.