Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA202 A-63/0.5 AE is a 2-pole Type A residual current device block rated at 63 A with 500 mA residual current sensitivity and additional contacts for emergency-stop remote opening in commercial and industrial installations.
£204.83
The ABB DDA202 A-63/0.5 AE, order code 2CSB202701R4630, is a 2-pole Type A residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. As part of the ABB DDA200 RCD series, the AE version is specifically designed for emergency-stop applications and incorporates additional contacts for remote opening in positive-safety emergency circuits.
This Type A RCD block has a 63 A rated current and a 500 mA rated residual operating current. It responds to sinusoidal alternating and pulsating DC residual currents, making it suitable for commercial and industrial circuits where Type A residual current protection is required.
Rated at 230/400 V AC with a 50/60 Hz frequency rating, the DDA202 A-63/0.5 AE combines residual current protection with emergency-stop functionality. When assembled with a compatible ABB S200 series or S300P miniature circuit breaker, the RCD block provides earth fault protection while the associated MCB provides overcurrent and short-circuit protection.
Type A residual current protection responds to both sinusoidal alternating and pulsating DC residual currents, making the ABB DDA202 A-63/0.5 AE suitable for commercial and industrial installations containing modern electrical and electronic equipment. Its 500 mA residual current rating provides earth fault protection for circuits where this sensitivity is specified.
The AE variant adds dedicated emergency-stop functionality through two additional contacts that can be used in emergency circuits for remote opening in positive safety. When correctly assembled with a compatible ABB miniature circuit breaker, the DDA202 A-63/0.5 AE provides residual current protection while the associated MCB provides overcurrent and short-circuit protection.
| Series | DDA200 |
|---|---|
| Order code | 2CSB202701R4630 |
| EAN | 8012542801900 |
| Product group | DDA200 RCD |
| Product type | Residual current device block |
| Residual current type | Type A |
| Application | Emergency stop |
| Operating characteristic | Instantaneous (AE for emergency stop) |
| Rated current | 63 A |
| Rated residual current | 500 mA |
| Rated voltage | 230/400 V AC |
| Rated operational voltage | 230 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Number of poles | 2 |
| Frequency | 50/60 Hz |
| Protection rating | IP2X |
| Power loss | 5 W |
| Electrical endurance | 10,000 cycles |
| Connecting capacity | up to 25 mm² rigid or flexible conductor |
| Operating ambient temperature | -25 to +55 °C |
| Standards | IEC/EN 61009-1 Annex G and IEC/EN 61009-2-1 |
| Compatible MCB families | ABB S200 series and S300P |
| Supply requirement | Top-side supply |
| Dimensions (W × H × D) | 70 × 93 × 76 mm |
| Weight | approx. 0.18 kg |
The ABB DDA202 A-63/0.5 AE is a Type A RCD block designed for commercial and industrial electrical installations requiring 500 mA residual current protection together with emergency-stop functionality for remote opening.
The DDA202 A-63/0.5 AE has a rated current of 63 A.
The device has a rated residual operating current of 500 mA.
The AE version is intended for emergency-stop applications and includes two additional contacts that can be used in emergency circuits for remote opening in positive safety.
The DDA202 A-63/0.5 AE is designed for assembly with compatible ABB S200 series and S300P miniature circuit breakers, with the associated MCB providing overcurrent and short-circuit protection.
ABB DDA200 AE RCD blocks combine Type A residual current protection with dedicated emergency-stop functionality, providing a modular solution for commercial and industrial electrical installations requiring remote opening in positive-safety emergency circuits.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.