ABB DDA202 A-63/0.03 AE is a 2-pole Type A residual current device block rated at 63 A with 30 mA sensitivity and an AE remote emergency-stop tripping function.
£197.16
The ABB DDA202 A-63/0.03 AE is a 2-pole Type A residual current device (RCD) block specifically designed for applications requiring an emergency-stop function. Part of the ABB DDA200 RCD series, it combines a 63 A rated current with sensitive 30 mA residual-current protection for commercial and industrial electrical installations.
Its Type A characteristic provides protection against sinusoidal alternating and pulsating DC earth fault currents. The AE emergency-stop version incorporates additional terminals that allow remote tripping through an external control circuit, making it suitable for installations where emergency disconnection must be initiated from a separate push-button or control point.
Designed for assembly with compatible ABB miniature circuit breakers, the DDA202 A-63/0.03 AE combines residual-current protection with the overload and short-circuit protection supplied by the associated circuit breaker. Its 30 mA sensitivity provides additional protection against direct contact, while the 63 A current rating supports demanding commercial and industrial distribution circuits.
The ABB DDA202 A-63/0.03 AE combines conventional Type A residual-current protection with an emergency-stop facility. Type A protection responds to sinusoidal alternating earth fault currents and pulsating DC residual currents, making it suitable for many commercial and industrial circuits containing electronic equipment.
The AE version includes two additional terminals for remote emergency tripping. This enables the protective device to be operated from an external emergency-stop circuit, allowing rapid electrical isolation when required. Multiple normally closed control buttons may be used to control one DDA200 AE device, making the arrangement suitable for machinery, industrial panels and other installations requiring accessible emergency disconnection points.
| Series | DDA200 |
|---|---|
| SKU | DDA202A630.03AE |
| Order code | 2CSB202701R1630 |
| EAN | 8012542801702 |
| Product type | Residual current device (RCD) block |
| Residual-current type | Type A |
| Operating characteristic | Instantaneous, AE for emergency stop |
| Number of poles | 2 |
| Rated current | 63 A |
| Rated residual current | 30 mA |
| Nominal voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Residual-current waveform | Sinusoidal AC and pulsating DC |
| Degree of protection | IP2X |
| Power loss | 5 W |
| Electrical endurance | 10,000 cycles |
| Standard | IEC/EN 61009 Annex G |
| Operating ambient temperature | -25 to +55 °C |
| Conductor connection capacity | 25 mm² |
| Dimensions (W × H × D) | 70 × 93 × 76 mm |
| Weight | approx. 0.18 kg |
| Additional function | Remote emergency tripping |
The DDA202 A-63/0.03 AE is a 2-pole Type A RCD block providing 30 mA residual-current protection together with an AE emergency-stop function for remote tripping. It is primarily intended for commercial and industrial electrical installations.
AE identifies the emergency-stop version of the DDA200 RCD block. It includes additional terminals that enable safe remote tripping through an external emergency-stop control circuit.
The device has a rated residual current of 30 mA, providing earth leakage protection and additional protection against direct contact.
Type A means the RCD block responds to sinusoidal alternating residual currents and pulsating direct residual currents, making it suitable for many circuits containing modern electronic equipment.
ABB DDA200 RCD blocks are designed for coupling with compatible S200 L, S200, S200 M and S200 P miniature circuit breakers. They can also be coupled with compatible M200 magnetic-only circuit breakers when suitable additional thermal overload protection is provided.