ABB DDA202 A-63/0.03 AP-R is a 2-pole Type A residual current device block rated at 63 A with 30 mA sensitivity and an AP-R anti-nuisance tripping characteristic for enhanced immunity to transient disturbances.
£149.46
The ABB DDA202 A-63/0.03 AP-R is a 2-pole Type A residual current device (RCD) block featuring ABB's AP-R anti-nuisance tripping characteristic. Part of the ABB DDA200 RCD series, it combines a 63 A rated current with sensitive 30 mA residual-current protection for electrical installations where enhanced immunity to transient disturbances is required.
Its Type A characteristic enables detection of sinusoidal alternating residual currents and pulsating DC residual currents, making it suitable for circuits supplying modern electronic equipment. The AP-R characteristic provides increased resistance to unwanted tripping caused by transient currents and disturbances, helping maintain continuity of service without sacrificing residual-current protection.
Designed for assembly with compatible ABB miniature circuit breakers, the DDA202 A-63/0.03 AP-R allows residual-current protection to be combined with overload and short-circuit protection in a coordinated modular assembly. Its 30 mA sensitivity provides additional protection against electric shock, while the 63 A rating supports higher-current distribution circuits.
Modern electrical installations can experience pulsating DC leakage currents from electronic equipment as well as short-duration transient currents caused by switching operations and other disturbances. The ABB DDA202 A-63/0.03 AP-R combines Type A residual-current detection with ABB's AP-R characteristic to address both requirements while helping reduce unwanted tripping.
The device's 30 mA residual-current sensitivity provides additional protection against electric shock, while the AP-R characteristic improves resistance to transient disturbances. When assembled with a compatible ABB miniature circuit breaker, the resulting protective assembly combines residual-current detection with overload and short-circuit protection.
| Series | DDA200 |
|---|---|
| SKU | DDA202A630.03APR |
| Order code | 2CSB202401R1630 |
| Product type | Residual current device (RCD) block |
| Residual-current type | Type A |
| Operating characteristic | AP-R anti-nuisance tripping |
| Number of poles | 2 |
| Rated current | 63 A |
| Rated residual current | 30 mA |
| Rated voltage | 230/400 V AC |
| Rated operational voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Residual-current waveform | Sinusoidal AC and pulsating DC |
| Standard | IEC/EN 61009 Annex G |
| Operating ambient temperature | -25 to +55 °C |
| Conductor connection capacity | up to 25 mm² |
| Dimensions (H × W × D) | 93 × 70 × 76 mm |
The DDA202 A-63/0.03 AP-R is a 2-pole Type A RCD block designed to provide 30 mA residual-current protection when assembled with a compatible ABB miniature circuit breaker, with enhanced resistance to nuisance tripping caused by transient disturbances.
AP-R identifies ABB's anti-nuisance tripping characteristic. It provides enhanced immunity to transient currents and disturbances, helping improve continuity of service compared with conventional instantaneous residual-current protection.
The device has a rated residual current of 30 mA, providing sensitive earth leakage detection and additional protection against electric shock.
Type A means the RCD block responds to sinusoidal alternating residual currents and pulsating direct residual currents, making it suitable for many circuits supplying electronic equipment.
No. It is an RCD block designed to be assembled with a compatible ABB miniature circuit breaker. The associated circuit breaker provides overload and short-circuit protection, while the DDA202 block provides residual-current protection.
ABB DDA200 AP-R residual current device blocks combine modular Type A residual-current protection with enhanced resistance to nuisance tripping, supporting dependable circuit protection and improved continuity of service in residential, commercial and industrial electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.