2CSB202301R1400 ABB DDA202 AC-40/0.03 AP-R RCD Block 2P 40 A 30 mA Type AC

2CSB202301R1400 ABB DDA202 AC-40/0.03 AP-R RCD Block 2P 40 A 30 mA Type AC

ABB DDA202 AC-40/0.03 AP-R is a 2-pole Type AC residual current device block rated at 40 A with 30 mA sensitivity and an AP-R anti-nuisance tripping characteristic for enhanced immunity to transient disturbances.

SKU: 2CSB202301R1400Alt SKU: DDA202AC400.03APRMPN: 2CSB202301R1400
Price
List Price £143.36 ex VAT
Your Price (ex VAT) Save 35%
£93.18 35% OFF
You save £50.18 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £93.18
Trade pricing is personalised to your account

Manufacturer Lead Time

£93.18

Why Choose the ABB DDA202 AC-40/0.03 AP-R RCD Block?

The ABB DDA202 AC-40/0.03 AP-R is a 2-pole Type AC residual current device (RCD) block with ABB's AP-R anti-nuisance tripping characteristic. Part of the ABB DDA200 RCD series, it combines a 40 A rated current with sensitive 30 mA residual-current protection for electrical installations where improved immunity to transient disturbances is required.

Its Type AC characteristic is designed to detect sinusoidal alternating residual currents. The AP-R characteristic provides enhanced resistance to unwanted tripping caused by transient overvoltages and disturbance currents, helping improve continuity of service in circuits where conventional instantaneous residual-current devices may be susceptible to nuisance operation.

Designed for assembly with compatible ABB miniature circuit breakers, the DDA202 AC-40/0.03 AP-R enables residual-current protection to be combined with overload and short-circuit protection in a coordinated modular assembly. Its 30 mA sensitivity makes it suitable for applications requiring additional protection against electric shock.

Key Advantages

  • AP-R anti-nuisance tripping characteristic for enhanced immunity to transient disturbances.
  • 30 mA rated residual current for additional protection against electric shock.
  • Type AC protection for sinusoidal alternating residual currents.
  • 40 A rated current for compatible electrical distribution circuits.
  • 2-pole configuration for two-conductor circuit protection arrangements.
  • Designed for modular assembly with compatible ABB miniature circuit breakers.

Key Features

  • ABB DDA200 RCD series.
  • 2-pole Type AC RCD block.
  • AP-R anti-nuisance tripping characteristic.
  • 40 A rated current.
  • 30 mA rated residual current.
  • 230/400 V AC rated voltage.
  • 50/60 Hz rated frequency.
  • 500 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • Enhanced immunity to transient currents compared with standard instantaneous Type AC protection.

AP-R Residual-Current Protection with Enhanced Continuity

Electrical installations can experience short-duration transient currents caused by switching operations, capacitive loads and other disturbances. ABB AP-R residual-current devices are designed with enhanced resistance to unwanted operation under these conditions, helping reduce nuisance tripping while maintaining the required residual-current protection.

The DDA202 AC-40/0.03 AP-R combines this anti-nuisance tripping characteristic with 30 mA Type AC protection. When assembled with a compatible ABB miniature circuit breaker, the resulting protective arrangement combines earth leakage detection with overload and short-circuit protection for the associated circuit.

Typical Applications

  • Residential electrical distribution systems.
  • Commercial building electrical installations.
  • Industrial and infrastructure distribution boards.
  • Circuits requiring 30 mA residual-current protection.
  • Installations susceptible to transient currents and nuisance RCD tripping.
  • Electrical control panels and modular distribution equipment.
  • Circuits where improved continuity of service is required.
  • Combined RCD and MCB protection assemblies using compatible ABB devices.

Technical Specifications

Series DDA200
SKU DDA202AC400.03APR
Order code 2CSB202301R1400
Product type Residual current device (RCD) block
Residual-current type Type AC
Operating characteristic AP-R anti-nuisance tripping
Number of poles 2
Rated current 40 A
Rated residual current 30 mA
Rated voltage 230/400 V AC
Rated operational voltage 230 V AC
Rated frequency 50/60 Hz
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Residual-current waveform Sinusoidal AC
Standard IEC/EN 61009 Annex G
Operating ambient temperature -25 to +55 °C
Conductor connection capacity up to 25 mm²
Dimensions (H × W × D) 93 × 70 × 76 mm

Frequently Asked Questions

What is the ABB DDA202 AC-40/0.03 AP-R used for?

The DDA202 AC-40/0.03 AP-R is a 2-pole Type AC RCD block designed to provide 30 mA residual-current protection when assembled with a compatible ABB miniature circuit breaker, with enhanced resistance to nuisance tripping caused by transient disturbances.

What does AP-R mean on the DDA202 AC-40/0.03?

AP-R identifies ABB's anti-nuisance tripping residual-current characteristic. It provides enhanced immunity to transient currents and disturbances, helping improve continuity of service compared with conventional instantaneous residual-current protection.

What residual-current sensitivity does the DDA202 AC-40/0.03 AP-R provide?

The device has a rated residual current of 30 mA, providing sensitive earth leakage detection and additional protection against electric shock.

What type of residual current does this RCD block detect?

The DDA202 AC-40/0.03 AP-R is a Type AC device designed to respond to sinusoidal alternating residual currents.

Is the DDA202 AC-40/0.03 AP-R a complete RCBO on its own?

No. It is an RCD block designed to be assembled with a compatible ABB miniature circuit breaker. The associated circuit breaker provides overload and short-circuit protection, while the DDA202 block provides residual-current protection.

Trusted ABB Circuit Protection

ABB DDA200 AP-R residual current device blocks combine modular residual-current protection with enhanced resistance to nuisance tripping, supporting dependable circuit protection and improved continuity of service in residential, commercial and industrial electrical installations.