ABB DDA202 A S-63/1 is a 2-pole selective Type A residual current device block rated at 63 A with 1000 mA sensitivity and intentional tripping delay for coordinated residual-current protection.
£121.88
The ABB DDA202 A S-63/1 is a 2-pole Type A selective residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD series, it combines a 63 A rated current with a 1000 mA (1 A) rated residual current for commercial and industrial electrical distribution applications.
Its Type A characteristic provides protection against sinusoidal alternating and pulsating DC earth fault currents. The selective S-type operating characteristic introduces an intentional tripping delay, allowing selectivity with suitable downstream instantaneous residual-current devices and helping isolate faults at the appropriate level of a coordinated distribution system.
The DDA202 A S-63/1 also offers 5 kA surge-current resistance and additional terminals for remote tripping. Its modular design enables combination with compatible ABB circuit breakers, providing residual-current protection alongside the overload and short-circuit protection supplied by the associated protective device.
Selective residual-current protection is used where coordinated operation between upstream and downstream RCDs is required. The intentional tripping delay of the ABB DDA202 A S-63/1 allows an appropriate downstream instantaneous residual-current device to respond first to a local fault, helping maintain continuity on unaffected parts of the electrical installation.
As a Type A device, the DDA202 A S-63/1 responds to both sinusoidal alternating and pulsating DC earth fault currents. Its selective characteristic, 5 kA surge-current resistance and 1 A residual-current rating make it particularly suited to coordinated commercial and industrial distribution systems rather than additional personal protection applications requiring lower residual-current thresholds.
| Series | DDA200 |
|---|---|
| SKU | DDA202AS631 |
| Order code | 2CSB202201R5630 |
| EAN | 8012542799603 |
| Product type | Selective residual current device (RCD) block |
| Residual-current type | Type A |
| Selective characteristic | S type, intentional tripping delay |
| Number of poles | 2 |
| Rated current | 63 A |
| Rated residual current | 1000 mA (1 A) |
| Nominal voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Surge-current resistance | 5 kA (8/20 waveform) |
| Residual-current waveform | Sinusoidal AC and pulsating DC |
| Degree of protection | IP2X |
| Conductor connection capacity | up to 25 mm² |
| Standard | IEC/EN 61009 Annex G |
| Dimensions (W × H × D) | 70 × 93 × 76 mm |
| Weight | approx. 0.18 kg |
The DDA202 A S-63/1 is a 2-pole selective Type A RCD block designed for assembly with compatible ABB circuit breakers, providing 1000 mA residual-current protection for coordinated commercial and industrial electrical distribution systems.
The S designation indicates selective operation. The device has an intentional tripping delay that can provide selectivity with suitable downstream instantaneous residual-current devices, helping the downstream device clear a local fault before the upstream RCD operates.
The device has a rated residual current of 1000 mA (1 A). This makes it suitable for earth leakage and installation protection applications rather than the additional personal protection normally associated with lower residual-current ratings such as 30 mA.
Type A means the RCD block responds to sinusoidal alternating residual currents and pulsating direct residual currents, making it suitable for many circuits containing electronic equipment.
ABB DDA200 RCD blocks can be coupled with compatible S200 L, S200, S200 M and S200 P miniature circuit breakers. They can also be coupled with M200 magnetic-only circuit breakers when suitable additional thermal overload protection is provided.
ABB DDA200 A S residual current device blocks provide selective Type A residual-current protection for coordinated commercial and industrial distribution systems, combining intentional tripping delay, surge-current resistance and modular integration with compatible ABB circuit breakers.