ABB SH203M-D25 is a 25 A three-pole Type D miniature circuit breaker with 10 kA short-circuit breaking capacity for reliable overload and short-circuit protection of three-phase circuits with comparatively high inrush currents.
£73.86
The ABB SH203M-D25 is a compact and reliable three-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits. As part of the ABB SH200M MCB series, it provides dependable thermal-magnetic protection for three-phase electrical distribution, machinery and control applications.
Featuring a 25 A rated current, Type D tripping characteristic and 10 kA short-circuit breaking capacity, the SH203M-D25 is particularly suited to circuits containing equipment with comparatively high starting or inrush currents. The Type D characteristic helps accommodate normal start-up surges while maintaining effective overcurrent protection.
With a 400 V AC rated operational voltage and three-pole configuration, the SH203M-D25 enables coordinated switching and protection across three phases. Its compact modular construction and standard DIN-rail mounting make it suitable for integration into electrical distribution boards, machinery panels and industrial control systems.
Miniature circuit breakers such as the ABB SH203M-D25 automatically disconnect a circuit when excessive current results from an overload or short circuit. Thermal operation responds to sustained overload conditions, while magnetic operation provides rapid disconnection when severe short-circuit currents occur.
The Type D characteristic makes the SH203M-D25 suitable for appropriately designed circuits containing equipment that produces comparatively high inrush current during normal start-up. Combined with its three-pole construction, 25 A current rating and 10 kA breaking capacity, it provides dependable protection for suitable three-phase machinery, distribution and equipment circuits.
| Series | SH200M |
|---|---|
| ABB order code | 2CDS273011R0251 |
| Product type | Miniature circuit breaker (MCB) |
| Number of poles | 3 |
| Number of protected poles | 3 |
| Rated current | 25 A |
| Tripping characteristic | Type D |
| Rated short-circuit breaking capacity | 10 kA |
| Rated operational voltage | 400 V AC |
| Rated insulation voltage | 440 V |
| Rated impulse withstand voltage | 4 kV |
| Rated frequency | 50 / 60 Hz |
| Standard | IEC/EN 60898-1 |
| Protection principle | Thermal-magnetic |
| Mounting type | DIN rail |
| Number of modules | 3 |
| Width | 52.5 mm |
The ABB SH203M-D25 is a three-pole miniature circuit breaker used to protect electrical circuits against overloads and short circuits, particularly in suitable applications where equipment can produce comparatively high starting currents.
The SH203M-D25 has a rated current of 25 A.
The Type D tripping characteristic is suited to circuits with comparatively high starting or inrush currents, helping accommodate normal equipment start-up while maintaining effective overcurrent protection.
The SH203M-D25 has a 10 kA short-circuit breaking capacity.
The SH203M-D25 is a three-pole (3P) miniature circuit breaker, enabling coordinated switching and protection across three phases.
ABB SH200M miniature circuit breakers provide dependable thermal-magnetic protection in a compact DIN-rail format, helping protect electrical distribution and equipment circuits against overload and short-circuit conditions.