Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 2CDS271061R0377 S201M-K6UC single-pole AC/DC miniature circuit breaker with 6 A rated current, Type K tripping characteristic and 10 kA short-circuit breaking capacity.
£80.72
The ABB S201M-K6UC (2CDS271061R0377) is a single-pole miniature circuit breaker (MCB) from ABB’s S200M UC range, designed to provide dependable overload and short-circuit protection in AC and DC electrical circuits. This model combines a 6 A rated current, Type K tripping characteristic and 10 kA short-circuit breaking capacity.
As part of ABB’s universal-current MCB family, the S201M-K6UC is engineered for applications requiring protection on both AC and DC circuits. The UC design makes it particularly useful for industrial control systems, DC distribution, traction auxiliary circuits and other equipment where reliable direct-current fault interruption is required.
The Type K characteristic is intended for circuits with loads that can produce comparatively high starting or inrush currents, helping reduce unwanted magnetic tripping while retaining effective short-circuit protection. Combined with its thermal overload release and compact DIN-rail format, the S201M-K6UC is a practical choice for demanding industrial and automation applications.
The ABB S201M-K6UC uses thermal-magnetic protection to safeguard conductors and connected equipment against abnormal current. Its thermal release responds to sustained overloads, while its magnetic release provides rapid disconnection during short-circuit conditions. The Type K characteristic makes the device especially useful where normal operation can involve higher starting currents than would typically be expected on circuits protected by more sensitive tripping characteristics.
Direct-current fault interruption requires appropriate breaker construction because DC does not have the natural periodic current zero crossings present in AC systems. The ABB S200M UC range is specifically designed for universal-current applications. When the S201M-K6UC is used on a DC supply, ABB’s specified polarity and connection arrangement should be followed to achieve the intended interruption performance.
| Series | S200M UC |
|---|---|
| Order code | 2CDS271061R0377 |
| Product type | Miniature circuit breaker (MCB) |
| Product group | DC / Traction MCB |
| Number of poles | 1 |
| Rated current (In) | 6 A |
| Tripping characteristic | Type K |
| Short-circuit breaking capacity | 10 kA |
| Protection principle | Thermal-magnetic |
| Current type | AC/DC |
| Mounting | DIN rail |
| Product family | System pro M compact S200M UC |
The ABB S201M-K6UC has a rated current of 6 A and uses a single-pole configuration.
The S201M-K6UC uses a Type K tripping characteristic, which is suitable for industrial circuits where comparatively high starting or inrush currents can occur during normal operation.
The ABB S201M-K6UC has a 10 kA short-circuit breaking capacity.
Yes. The S201M-K6UC belongs to ABB’s S200M UC universal-current range for AC and DC circuit protection. ABB’s specified polarity and connection arrangement should be followed when the breaker is installed in a DC circuit.
A Type K MCB is suited to industrial circuits with loads that can produce relatively high starting or inrush currents, including appropriate inductive loads, while still providing overload and short-circuit protection.
ABB System pro M compact S200M UC miniature circuit breakers provide dependable AC and DC circuit protection, with the S201M-K6UC combining a 6 A rating, Type K characteristic and 10 kA short-circuit breaking capacity for demanding industrial applications.