2CDS251103R0608 ABB S201-Z63NA Miniature Circuit Breaker 1P+N Type Z 63 A

2CDS251103R0608 ABB S201-Z63NA Miniature Circuit Breaker 1P+N Type Z 63 A

ABB S201-Z63NA miniature circuit breaker, a 63 A 1P+N Type Z MCB with switched neutral from the System pro M compact S200 series providing 6 kA and 10 kA breaking capacities for overload and short-circuit protection.

SKU: 2CDS251103R0608Alt SKU: S201Z63NAMPN: 2CDS251103R0608
Price
List Price £109.41 ex VAT
Your Price (ex VAT) Save 45%
£60.18 45% OFF
You save £49.23 per unit
Manufacturer Lead Time Estimated Delivery 14 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £60.18
Trade pricing is personalised to your account

Manufacturer Lead Time

£60.18

Why Choose the ABB S201-Z63NA Miniature Circuit Breaker?

The ABB S201-Z63NA is a compact and reliable 1P+N miniature circuit breaker (MCB) with switched neutral designed to protect electrical circuits against overloads and short circuits. As part of the established ABB System pro M compact S200 MCB series, it combines delayed thermal overload protection with electromagnetic short-circuit protection for dependable circuit protection in commercial and industrial electrical installations.

Featuring a Type Z tripping characteristic, the S201-Z63NA is particularly suited to applications requiring sensitive overcurrent protection, including electronic equipment, control systems and other circuits where relatively low fault currents require rapid disconnection. Its current-limiting construction helps reduce electrical and thermal stresses during fault conditions.

With a rated current of 63 A, a 1P+N configuration and breaking capacities of 6 kA to IEC/EN 60898-1 and 10 kA at 230 V AC to IEC/EN 60947-2, the S201-Z63NA provides robust protection while simultaneously switching the neutral conductor. ABB order code 2CDS251103R0608 identifies this specific 63 A Type Z model within the S200 range.

Key Advantages

  • Reliable miniature circuit breaker for overload and short-circuit protection.
  • 63 A rated current suitable for higher-current commercial and industrial circuits.
  • Type Z tripping characteristic suited to sensitive electrical and electronic loads.
  • 1P+N configuration with one protected phase pole and simultaneously switched neutral.
  • Breaking capacity of 6 kA to IEC/EN 60898-1 and 10 kA at 230 V AC to IEC/EN 60947-2.
  • Current-limiting design helps reduce electrical and thermal stresses during short-circuit conditions.

Key Features

  • ABB System pro M compact S200 series.
  • 63 A rated current.
  • 1P+N configuration with switched neutral.
  • 1 protected pole.
  • Type Z tripping characteristic.
  • Thermal tripping mechanism for overload protection.
  • Electromagnetic tripping mechanism for short-circuit protection.
  • 6 kA breaking capacity at 230 V AC according to IEC/EN 60898-1.
  • 10 kA ultimate breaking capacity at 230 V AC according to IEC/EN 60947-2.
  • Current limiting class 3 for effective limitation of fault energy.

Reliable Protection for Sensitive Electrical Circuits

Miniature circuit breakers such as the ABB S201-Z63NA automatically disconnect a circuit when excessive current occurs. The S200 design combines a delayed thermal tripping mechanism for overload protection with an electromagnetic mechanism for rapid response to short-circuit currents, helping protect conductors, equipment and connected loads.

The Type Z characteristic provides sensitive magnetic overcurrent protection and is particularly useful for electronic equipment and circuits where rapid response to comparatively low fault currents is required. The 1P+N arrangement also switches the neutral conductor together with the protected phase pole, providing convenient simultaneous isolation within a compact modular device.

Typical Applications

  • Electronic equipment and sensitive electrical loads.
  • Industrial control and automation panels.
  • Control and instrumentation systems.
  • Commercial electrical installations.
  • Distribution boards requiring switched-neutral isolation.
  • Industrial electrical distribution and switchgear assemblies.

Technical Specifications

Tick the specs you need, then view products that match.

Breaking Capacity 6 kA
Series System pro M compact S200
ABB order code 2CDS251103R0608
EAN 4016779552134
Product type Miniature circuit breaker (MCB)
Pole configuration 1P+N
Total number of poles 2
Number of protected poles 1
Neutral Simultaneously switched neutral
Rated current 63 A
Tripping characteristic Type Z
Rated voltage 230 V AC
Frequency 50–60 Hz
Rated insulation voltage 440 V
Breaking capacity (IEC/EN 60898-1) 6 kA at 230 V AC
Ultimate breaking capacity (IEC/EN 60947-2) 10 kA at 230 V AC
Rated impulse withstand voltage 4 kV
Current limiting class 3
Overvoltage category III
Pollution degree 3
Protection rating IP20
Mounting type DIN rail
Terminal type Screw terminal
Maximum solid conductor cross-section 35 mm²
Maximum stranded conductor cross-section 25 mm²
Width 2 modular spaces
Built-in depth 69 mm
Weight approx. 0.32 kg
Power loss 10.4 W
Operating temperature -25 to +55 °C
Standards IEC/EN 60898-1 and IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S201-Z63NA used for?

The ABB S201-Z63NA is a 1P+N miniature circuit breaker used to protect electrical circuits against overloads and short circuits, with its Type Z characteristic making it particularly suitable for sensitive electrical and electronic applications.

What is the current rating of the S201-Z63NA?

The S201-Z63NA has a rated current of 63 A.

What does the Type Z characteristic mean?

The Type Z tripping characteristic provides sensitive overcurrent protection and is particularly suited to electronic equipment and circuits requiring rapid magnetic tripping at comparatively low fault-current levels.

What is the breaking capacity of the ABB S201-Z63NA?

The S201-Z63NA provides a breaking capacity of 6 kA at 230 V AC according to IEC/EN 60898-1 and an ultimate breaking capacity of 10 kA at 230 V AC according to IEC/EN 60947-2.

What does 1P+N mean on the S201-Z63NA?

The 1P+N configuration means the breaker has one overcurrent-protected phase pole together with a simultaneously switched neutral pole, allowing both conductors to be disconnected together.

Trusted Circuit Protection from ABB