ABB SH201-C40NA is a 40 A Type C 1P+N miniature circuit breaker with 6 kA breaking capacity for overload and short-circuit protection with neutral switching in electrical circuits.
£41.43
The ABB SH201-C40NA is a compact 1P+N miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits while also switching the neutral conductor. Part of the ABB SH200 series, it provides thermal-magnetic circuit protection in a modular DIN-rail format for residential, commercial and electrical distribution applications.
Featuring a 40 A rated current, Type C tripping characteristic and 6 kA rated short-circuit breaking capacity, the SH201-C40NA is suitable for appropriately designed circuits where moderate short-duration starting or inrush currents may occur. The Type C characteristic provides tolerance of these transient currents while maintaining dependable overload and short-circuit protection.
The SH201-C40NA combines a protected phase pole and switched neutral in a 1P+N configuration. This provides phase overcurrent protection together with neutral switching, making the breaker a practical solution for final and distribution circuits requiring simultaneous phase and neutral disconnection within a compact modular installation.
The ABB SH201-C40NA uses thermal-magnetic protection to respond to both overload and short-circuit conditions. Its thermal mechanism responds to sustained overcurrents, while the magnetic mechanism provides rapid operation when sufficiently high short-circuit fault currents occur.
The Type C characteristic provides tolerance of moderate short-duration inrush currents, making the SH201-C40NA suitable for appropriately designed circuits supplying inductive, lighting and general-purpose loads that can draw increased current during energisation. Its 1P+N configuration additionally switches the neutral conductor when the breaker is operated.
| Series | SH200 |
|---|---|
| ABB order code | 2CDS211103R0404 |
| Product type | Miniature circuit breaker (MCB) |
| Number of poles | 1P+N |
| Protected poles | 1 |
| Neutral switching | Yes |
| Rated current | 40 A |
| Tripping characteristic | Type C |
| Rated frequency | 50/60 Hz |
| Rated short-circuit capacity (Icn) | 6 kA |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Operating temperature | -25 to +55 °C |
| Mounting type | DIN-rail mounting |
| Standard | IEC/EN 60898-1 |
The ABB SH201-C40NA is used to protect 40 A electrical circuits against overloads and short circuits while also switching the neutral conductor.
The SH201-C40NA has a rated current of 40 A.
The Type C tripping characteristic provides tolerance of moderate short-duration starting and inrush currents, making it suitable for appropriately designed circuits containing loads with moderate energisation currents.
The SH201-C40NA has a rated short-circuit breaking capacity of 6 kA.
The 1P+N configuration provides overcurrent protection for the phase conductor together with switching of the neutral conductor, supporting simultaneous phase and neutral disconnection.
ABB SH200 miniature circuit breakers provide dependable thermal-magnetic protection in a compact modular format, supporting safe and space-efficient circuit protection across residential, commercial and electrical distribution applications.