ABB S754DR-E25 selective main circuit breaker, a 25 A four-pole Type E device with 25 kA ultimate short-circuit breaking capacity at 400 V AC for selective electrical distribution protection.

SKU: 2CDH784010R0252Alt SKU: S754DRE25MPN: 2CDH784010R0252
Price
List Price £503.03 ex VAT
Your Price (ex VAT) Save 35%
£326.97 35% OFF
You save £176.06 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £326.97
Trade pricing is personalised to your account

Manufacturer Lead Time

£326.97

Why Choose the ABB S754DR-E25 Selective Main Circuit Breaker?

The ABB S754DR-E25 is a high-performance selective main circuit breaker (SMCB) designed for reliable overcurrent and short-circuit protection in electrical distribution systems where continuity of supply and selective coordination are important. As part of the advanced ABB S750 DR series, it uses a voltage-independent operating principle and is engineered for energy distribution systems with demanding availability requirements.

This selective circuit breaker provides total selectivity towards downstream miniature circuit breakers and outstanding selectivity towards upstream protective devices through ABB's current-limiting selectivity principle. Its voltage-independent operation means that it does not rely on a control circuit to make or break the contacts, supporting dependable protection in modern electrical distribution installations.

With a rated current of 25 A, a four-pole configuration, Type E selective tripping characteristic and a rated ultimate short-circuit breaking capacity of 25 kA at 400 V AC, the S754DR-E25 provides robust protection for multi-pole distribution circuits. Its DIN-rail mounting format enables straightforward installation in compatible distribution boards, switchgear and electrical enclosures.

Key Advantages

  • Selective main circuit breaker designed for high-availability electrical distribution systems.
  • 25 A rated current with a four-pole configuration.
  • Type E selective tripping characteristic for coordinated circuit protection.
  • 25 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Voltage-independent operating principle requiring no control circuit for contact operation.
  • Total selectivity towards downstream MCBs and excellent selectivity towards upstream protective devices.

Key Features

  • ABB S750 DR selective main circuit breaker series.
  • 25 A rated current.
  • 4-pole configuration.
  • 400 V AC rated operational voltage.
  • 25 kA rated ultimate short-circuit breaking capacity.
  • 12.5 kA rated service short-circuit breaking capacity.
  • Type E selective tripping characteristic.
  • 690 V rated insulation voltage.
  • 50 / 60 Hz rated frequency.
  • DIN-rail mounting for integration into electrical distribution equipment.

Reliable Selective Protection for Electrical Distribution

Selective main circuit breakers such as the ABB S754DR-E25 are designed to coordinate with other protective devices so that an electrical fault can be disconnected as close as possible to its source while unaffected circuits remain operational. This helps improve continuity of supply and reduces unnecessary interruption across electrical distribution systems.

The S750 DR series combines high short-circuit breaking capability with current-limiting selectivity and voltage-independent operation. These characteristics make the S754DR-E25 particularly suitable for distribution systems requiring dependable protection, circuit isolation and coordinated operation with downstream miniature circuit breakers.

Typical Applications

  • Main circuit protection in electrical distribution systems.
  • Four-pole distribution and switching applications.
  • Commercial building electrical distribution.
  • Industrial power distribution installations.
  • Residential and multi-residential distribution systems.
  • Installations requiring selective coordination with downstream MCBs.

Technical Specifications

Series S750 DR
ABB order code 2CDH784010R0252
EAN 4016779879781
Product group S800 / S800P / S750 MCB
Product type Selective main circuit breaker (SMCB)
Rated current 25 A
Number of poles 4
Tripping characteristic E (Selective)
Rated operational voltage 400 V AC
Rated insulation voltage 690 V
Rated impulse withstand voltage 6 kV
Rated frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) 25 kA at 400 V AC
Rated service short-circuit breaking capacity (Ics) 12.5 kA at 400 V AC
Standard IEC/EN 60947-2
Protection rating IP20 / IP40
Pollution degree 3
Overvoltage category IV
Operating temperature -25 to +55 °C
Power loss 5.9 W per pole at rated operating conditions
Contact position indication Red ON / Green OFF
Mounting type DIN rail
Terminal type Screw terminals
Tightening torque 2.5–3 N·m
Dimensions (H × W × D) 130 × 108 × 96 mm
Weight approx. 1.4 kg

Frequently Asked Questions

What is the ABB S754DR-E25 used for?

The S754DR-E25 is a selective main circuit breaker used for overcurrent and short-circuit protection in electrical distribution systems where selective coordination and high continuity of supply are required.

What is the rated current of the S754DR-E25?

The ABB S754DR-E25 has a rated current of 25 A and uses a four-pole configuration.

What is the breaking capacity of the S754DR-E25?

The S754DR-E25 has a rated ultimate short-circuit breaking capacity of 25 kA at 400 V AC and a rated service short-circuit breaking capacity of 12.5 kA at 400 V AC.

What tripping characteristic does the S754DR-E25 use?

The S754DR-E25 uses a Type E selective tripping characteristic, designed for coordinated main circuit protection in electrical distribution systems.

How is the ABB S754DR-E25 installed?

The S754DR-E25 is designed for DIN-rail mounting in suitable distribution boards, switchgear assemblies and electrical enclosures.

Trusted Circuit Protection from ABB

ABB S750 DR selective main circuit breakers provide robust, voltage-independent circuit protection and selective coordination for residential, commercial and industrial electrical distribution systems where reliable continuity of supply is required.