ABB S752DR-K20 is a 20 A Type K 2-pole selective main circuit breaker with a 25 kA ultimate short-circuit breaking capacity at 400 V AC for coordinated low-voltage distribution protection.
£155.93
The ABB S752DR-K20 is a selective 2-pole main circuit breaker (SMCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems where selectivity and continuity of supply are important. Part of the ABB S750 DR series, it combines selective protection with voltage-independent operation and DIN rail mounting.
Featuring a 20 A rated current and Type K selective characteristic, the S752DR-K20 is designed for coordinated protection with suitable downstream miniature circuit breakers. The S750 DR operating principle provides total short-circuit selectivity to downstream MCBs and high selectivity to upstream protective devices, helping isolate faults at the appropriate protection level while maintaining supply to unaffected circuits.
The S752DR-K20 provides an ultimate short-circuit breaking capacity (Icu) of 25 kA at 400 V AC and a service short-circuit breaking capacity (Ics) of 12.5 kA at 400 V AC. Its two-pole construction, screw terminals and clear red ON / green OFF contact-position indication provide a robust solution for selective commercial, industrial and building distribution systems.
Selective main circuit breakers are designed to coordinate with downstream protective devices so that a fault can be disconnected as close as possible to its source without unnecessarily interrupting unaffected sections of the electrical installation. The ABB S750 DR series uses a current-limiting selective operating principle and voltage-independent operation, supporting dependable group protection and continuity of supply in appropriately coordinated distribution systems.
With its 20 A rating, Type K selective characteristic, 25 kA Icu at 400 V AC and two-pole construction, the S752DR-K20 provides robust selective protection for demanding low-voltage distribution systems. Its DIN rail format and screw-terminal connections make it suitable for commercial, industrial and building installations requiring coordinated main and downstream circuit protection.
| Product group | S800 / S800P / S750 MCB |
|---|---|
| Series | S750 DR / S752DR |
| Order code | 2CDH782010R0487 |
| GTIN / EAN | 4016779879477 |
| Product type | Selective main circuit breaker (SMCB) |
| Number of poles | 2P |
| Rated current | 20 A |
| Tripping characteristic | Type K selective |
| Rated operational voltage | 400 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 25 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 12.5 kA |
| Rated frequency | 50 / 60 Hz |
| Power loss at rated operating conditions per pole | 5.1 W |
| Protection rating | IP20 / IP40 |
| Pollution degree | 3 |
| Operating temperature | -25 to +55 °C |
| Terminal type | Screw terminals |
| Tightening torque | 2.5–3 N·m |
| Contact-position indication | Red ON / green OFF |
| Operating principle | Voltage-independent |
| Mounting type | DIN rail |
| Standard | IEC/EN 60947-2 |
| Dimensions (H × W × D) | 130 × 54 × 96 mm |
| Weight | approx. 0.70 kg |
The ABB S752DR-K20 is a 2-pole selective main circuit breaker used for overload and short-circuit protection in low-voltage distribution systems where selective coordination with downstream protective devices and continuity of supply are important.
The S752DR-K20 has a rated current of 20 A and uses a Type K selective characteristic.
The S752DR-K20 has an ultimate short-circuit breaking capacity (Icu) of 25 kA at 400 V AC and a service short-circuit breaking capacity (Ics) of 12.5 kA at 400 V AC.
Selective operation enables coordinated protective devices to isolate a downstream fault at the appropriate protection level. The ABB S750 DR series provides total short-circuit selectivity to suitable downstream MCBs, helping maintain supply to unaffected circuits.
The S752DR-K20 is a 2-pole selective main circuit breaker, providing coordinated switching and protection across two poles.
ABB S750 DR selective main circuit breakers combine voltage-independent operation, current-limiting selectivity and high short-circuit interruption capability for low-voltage distribution systems where coordinated protection and continuity of supply are important.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.