Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S752DR-E20 is a 20 A two-pole E-characteristic selective main circuit breaker with 25 kA ultimate breaking capacity at 400 V AC for coordinated electrical distribution protection.
£155.93
The ABB S752DR-E20 is a high-performance two-pole selective main circuit breaker (SMCB) designed to provide dependable overload and short-circuit protection in electrical distribution systems where selective coordination and continuity of supply are important. Part of the ABB S750 DR series, it combines a 20 A rated current, E selective tripping characteristic and high short-circuit breaking capacity.
The S752DR-E20 operates according to a voltage-independent principle and does not require a control circuit to open or close its contacts. The S750 DR range is designed to provide total selectivity with downstream miniature circuit breakers and excellent selectivity with upstream protective devices through current-limiting selectivity, helping localise electrical faults and minimise unnecessary interruption to unaffected circuits.
With a two-pole configuration, 400 V AC rated operational voltage and a rated ultimate short-circuit breaking capacity of 25 kA at 400 V AC, the S752DR-E20 is suited to demanding energy-distribution applications. Its DIN-rail format supports straightforward installation in compatible distribution equipment, while ABB order code 2CDH782010R0202 identifies this specific 20 A E-characteristic model.
Selective main circuit breakers such as the ABB S752DR-E20 coordinate with other protective devices so that electrical faults can be disconnected as locally as possible. This selective operation helps reduce unnecessary interruption to unaffected circuits, supporting improved continuity and availability throughout the electrical distribution system.
The ABB S750 DR series combines voltage-independent operation with current-limiting selectivity. This makes the range particularly suitable for energy-distribution systems where dependable overload and short-circuit protection must be combined with effective coordination between upstream and downstream protective devices.
| Series | S750 DR |
|---|---|
| ABB order code | 2CDH782010R0202 |
| Product type | Selective main circuit breaker (SMCB) |
| Number of poles | 2 |
| Rated current | 20 A |
| Tripping characteristic | E selective |
| Rated operational voltage | 400 V AC |
| Rated frequency | 50/60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA at 400 V AC |
| Rated service short-circuit breaking capacity (Ics) | 12.5 kA at 400 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Operating temperature | −25 to +55 °C |
| Pollution degree | 3 |
| Protection degree | IP20 / IP40 |
| Contact-position indication | Red ON / green OFF |
| Terminal type | Screw terminals |
| Tightening torque | 2.5–3 N·m |
| Power loss | 5.4 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 130 × 54 × 96 mm |
| Weight | approx. 0.7 kg |
| Mounting type | DIN rail |
| Standard | IEC/EN 60947-2 |
The ABB S752DR-E20 is a selective main circuit breaker designed to provide overload and short-circuit protection while supporting coordinated operation with other protective devices in electrical distribution systems.
The S752DR-E20 has a rated current of 20 A and uses a two-pole configuration.
The breaker has a rated ultimate short-circuit breaking capacity of 25 kA at 400 V AC and a rated service short-circuit breaking capacity of 12.5 kA at 400 V AC.
The E selective characteristic defines the circuit breaker's tripping behaviour and supports coordinated selective protection with other protective devices in the electrical distribution system.
The S752DR-E20 is designed for DIN-rail mounting in compatible electrical distribution equipment and uses screw terminals for electrical connections.
ABB S750 DR selective main circuit breakers provide coordinated, voltage-independent protection for electrical distribution systems where dependable fault protection, selectivity and continuity of supply are essential.