Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S751DR-K80 is an 80 A Type K 1-pole selective main circuit breaker with a 25 kA ultimate short-circuit breaking capacity at 230 V AC for coordinated low-voltage distribution protection.
£71.78
The ABB S751DR-K80 is a selective 1-pole main circuit breaker (SMCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems where selectivity and continuity of supply are important. Part of the ABB S750 DR series, it uses a voltage-independent operating principle and is designed for DIN rail installation.
Featuring an 80 A rated current and Type K selective characteristic, the S751DR-K80 is designed to provide total selectivity with suitable downstream miniature circuit breakers and high selectivity with upstream protective devices. Its current-limiting selective operating principle helps isolate faults at the appropriate protection level, reducing unnecessary interruption to unaffected circuits.
The S751DR-K80 provides an ultimate short-circuit breaking capacity (Icu) of 25 kA at 230 V AC and a service short-circuit breaking capacity (Ics) of 12.5 kA at 230 V AC. With screw terminals, clear red ON / green OFF contact-position indication and a robust single-pole format, it provides high-performance main circuit protection for selective low-voltage distribution systems.
Selective main circuit breakers are designed to coordinate with other protective devices so that a downstream fault can be disconnected as close as possible to its source without unnecessarily interrupting unaffected sections of the electrical installation. The ABB S750 DR series uses a current-limiting selective operating principle and voltage-independent operation, making it particularly suitable for distribution systems with demanding continuity-of-service requirements.
With its 80 A rating, Type K selective characteristic and 25 kA Icu at 230 V AC, the S751DR-K80 combines selective protection with substantial short-circuit interruption capability. Its single-pole DIN rail construction makes it suitable for appropriately engineered low-voltage distribution systems where coordinated protection between main and downstream circuit breakers is required.
| Product group | S800 / S800P / S750 MCB |
|---|---|
| Series | S750 DR / S751DR |
| Order code | 2CDH781010R0627 |
| EAN | 4016779879149 |
| Product type | Selective main circuit breaker (SMCB) |
| Number of poles | 1P |
| Rated current | 80 A |
| Tripping characteristic | Type K selective |
| Rated operational voltage | 230 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Ultimate short-circuit breaking capacity (Icu) at 230 V AC | 25 kA |
| Service short-circuit breaking capacity (Ics) at 230 V AC | 12.5 kA |
| Rated frequency | 50 / 60 Hz |
| Power loss per pole | 10.5 W |
| Protection rating | IP20 / IP40 |
| Pollution degree | 3 |
| Operating temperature | -25 to +55 °C |
| Terminal type | Screw terminals |
| Tightening torque | 2.5–3 N·m |
| Contact-position indication | Red ON / green OFF |
| Operating principle | Voltage-independent |
| Mounting type | DIN rail |
| Standard | IEC/EN 60947-2 |
| Dimensions (H × W × D) | 130 × 35 × 92 mm |
| Weight | approx. 0.4 kg |
The ABB S751DR-K80 is a 1-pole selective main circuit breaker used for overload and short-circuit protection in low-voltage distribution systems where selective coordination with other protective devices and continuity of supply are important.
The S751DR-K80 has a rated current of 80 A and uses a Type K selective characteristic.
The S751DR-K80 has an ultimate short-circuit breaking capacity (Icu) of 25 kA at 230 V AC and a service short-circuit breaking capacity (Ics) of 12.5 kA at 230 V AC.
Selective operation helps coordinate the S751DR-K80 with other protective devices so that a fault can be disconnected by the appropriate downstream protection where applicable, helping minimise unnecessary interruption to unaffected parts of the electrical installation.
Yes. The S751DR-K80 uses a voltage-independent operating principle, so its protective operation does not depend on an auxiliary control circuit for making or breaking the main contacts.
ABB S750 DR selective main circuit breakers combine voltage-independent operation, current-limiting selectivity and high short-circuit interruption capability for low-voltage distribution systems where coordinated protection and continuity of supply are important.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.