Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S751DR-K50 is a 50 A single-pole K-characteristic selective main circuit breaker with 25 kA ultimate breaking capacity at 230 V AC for coordinated electrical distribution protection.
£67.33
The ABB S751DR-K50 is a high-performance single-pole selective main circuit breaker (SMCB) designed to provide dependable overload and short-circuit protection in electrical distribution systems where continuity of supply and coordinated protection are important. Part of the ABB S750 DR series, this model combines a 50 A rated current, K selective tripping characteristic and high short-circuit breaking capacity.
The S751DR-K50 operates using a voltage-independent principle, meaning it does not rely on a separate control circuit to make or break its contacts. The S750 DR range is designed to provide total selectivity with downstream miniature circuit breakers and excellent selectivity with upstream protective devices through ABB's current-limiting selectivity principle, helping isolate faults while maintaining supply to unaffected circuits.
With a single-pole configuration, 50 A rated current and rated ultimate short-circuit breaking capacity of 25 kA at 230 V AC, the S751DR-K50 is suitable for demanding energy-distribution installations. Its DIN-rail format allows straightforward installation in compatible distribution equipment, while ABB order code 2CDH781010R0577 identifies this specific K-characteristic model.
Selective main circuit breakers such as the ABB S751DR-K50 coordinate with other protective devices so that a fault can be disconnected as locally as possible. This selective operation helps prevent unnecessary interruption to unaffected circuits, supporting improved continuity and availability throughout an electrical distribution system.
The ABB S750 DR series uses a voltage-independent operating principle and current-limiting selectivity. These characteristics make the range particularly suitable for energy-distribution systems where dependable overload and short-circuit protection must be combined with effective coordination between upstream and downstream protective devices.
| Series | S750 DR |
|---|---|
| ABB order code | 2CDH781010R0577 |
| Product type | Selective main circuit breaker (SMCB) |
| Number of poles | 1 |
| Rated current | 50 A |
| Tripping characteristic | K selective |
| Rated operational voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA at 230 V AC |
| Rated service short-circuit breaking capacity (Ics) | 12.5 kA at 230 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Operating temperature | −25 to +55 °C |
| Pollution degree | 3 |
| Protection degree | IP20 / IP40 |
| Contact-position indication | Red ON / green OFF |
| Terminal type | Screw terminals |
| Tightening torque | 2.5–3 N·m |
| Power loss | 7.2 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 130 × 27 × 92 mm |
| Weight | approx. 0.35 kg |
| Mounting type | DIN rail |
| Standard | IEC/EN 60947-2 |
The ABB S751DR-K50 is a selective main circuit breaker designed to provide overload and short-circuit protection while coordinating with other protective devices in electrical distribution systems.
The S751DR-K50 has a rated current of 50 A and uses a single-pole configuration.
The breaker has a rated ultimate short-circuit breaking capacity of 25 kA at 230 V AC and a rated service short-circuit breaking capacity of 12.5 kA at 230 V AC.
The K selective characteristic is designed for coordinated circuit protection, allowing the S750 DR to provide selective operation with other protective devices in the electrical distribution system.
The S751DR-K50 is designed for DIN-rail mounting in compatible electrical distribution equipment and uses screw terminals for electrical connections.
ABB S750 DR selective main circuit breakers provide coordinated, voltage-independent protection for electrical distribution systems where high availability, dependable fault protection and selectivity between protective devices are essential.