2CCS893001R0161 ABB S803N-D16 MCB 36kA 3P Type D 16A

2CCS893001R0161 ABB S803N-D16 MCB 36kA 3P Type D 16A

ABB S803N-D16 is a 16 A Type D 3-pole high-performance miniature circuit breaker with a 36 kA ultimate short-circuit breaking capacity at 415 V AC for demanding industrial circuit protection and high-inrush loads.

SKU: 2CCS893001R0161Alt SKU: S803ND16MPN: 2CCS893001R0161
Price
List Price £242.82 ex VAT
Your Price (ex VAT) Save 35%
£157.83 35% OFF
You save £84.99 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £157.83
Trade pricing is personalised to your account

Manufacturer Lead Time

£157.83

Why Choose the ABB S803N-D16 High Performance MCB?

The ABB S803N-D16 is a high-performance 3-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits in demanding commercial and industrial installations. As part of the ABB S800N high-performance MCB range, it combines robust circuit protection with a compact DIN rail format and high short-circuit breaking capacity.

Featuring a 16 A rated current and Type D tripping characteristic, the S803N-D16 is particularly suited to circuits supplying equipment with high inrush currents. Its thermal and electromagnetic tripping mechanisms provide dependable overload and short-circuit protection while allowing the temporary starting currents associated with suitable motors, transformers and other inductive equipment.

The S803N-D16 provides a rated ultimate short-circuit breaking capacity of 36 kA at 415 V AC according to IEC/EN 60947-2. Its three-pole configuration, high breaking performance and robust construction make it suitable for industrial distribution boards, machinery and three-phase electrical systems where reliable protection against high prospective fault currents is required.

Key Advantages

  • High-performance 3-pole miniature circuit breaker for demanding electrical installations.
  • 16 A rated current with Type D tripping characteristic.
  • 36 kA Icu breaking capacity at 415 V AC for high prospective fault-current applications.
  • Type D characteristic is suitable for circuits with high inrush currents.
  • Protects electrical circuits against both overloads and short circuits.
  • Current-limiting design helps reduce fault energy during short-circuit conditions.
  • Three-pole configuration provides coordinated protection for three-phase circuits.
  • DIN rail mounting enables straightforward installation in electrical panels and distribution boards.

Key Features

  • ABB S800N / S803N high-performance MCB series.
  • 3-pole configuration with three protected poles.
  • 16 A rated current.
  • Type D tripping characteristic.
  • 36 kA rated ultimate short-circuit breaking capacity (Icu) at 415 V AC.
  • High breaking performance for demanding commercial and industrial installations.
  • Thermal tripping mechanism for overload protection.
  • Electromagnetic tripping mechanism for short-circuit protection.
  • Suitable for loads with substantial starting or energisation currents.
  • Current-limiting construction with rapid fault interruption.
  • DIN rail format for integration into electrical distribution equipment.
  • Designed in accordance with IEC/EN 60898-1 and IEC/EN 60947-2.

High-Performance Protection for High Inrush Loads

Miniature circuit breakers such as the ABB S803N-D16 automatically interrupt electrical circuits when excessive current occurs because of an overload or short circuit. Thermal protection responds to sustained overload conditions, while electromagnetic protection provides rapid interruption during high-current short-circuit faults, helping protect conductors, equipment and the wider electrical installation.

The Type D characteristic makes the S803N-D16 particularly suitable for circuits supplying equipment that can draw substantial current during starting or energisation. Combined with the high breaking capacity of the ABB S800N range, this makes the breaker suitable for demanding motor, transformer and industrial equipment circuits where reliable protection and tolerance of normal inrush currents are required.

Typical Applications

  • Industrial electrical distribution boards.
  • Three-phase motor circuits with high starting currents.
  • Transformer protection circuits.
  • Machinery and industrial control panels.
  • Commercial and industrial three-phase systems.
  • Electrical equipment with high switch-on or inrush currents.
  • High fault-level electrical installations.
  • Circuits requiring high-performance Type D protection.

Technical Specifications

Series S800N / S803N
Order code 2CCS893001R0161
Product type High-performance miniature circuit breaker (MCB)
Number of poles 3P
Number of protected poles 3
Rated current 16 A
Tripping characteristic Type D
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 36 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 20 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 10 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 4.5 kA
Ultimate short-circuit breaking capacity (Icu) at 375 V DC 20 kA
Rated short-circuit breaking capacity (Icn) at 400 V AC 20 kA
Rated insulation voltage (Ui) 690 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Terminal type Cage terminal
Tightening torque 3.5 N·m
Mounting type DIN rail
Standards IEC/EN 60898-1, IEC/EN 60947-2
Dimensions (H × W × D) 95 × 81 × 82.5 mm
Weight approx. 0.72 kg

Frequently Asked Questions

What is the ABB S803N-D16 used for?

The ABB S803N-D16 is a high-performance miniature circuit breaker used to protect three-pole electrical circuits against overloads and short circuits, particularly where equipment can produce high starting or inrush currents.

What is the current rating of the ABB S803N-D16?

The S803N-D16 has a rated current of 16 A and uses a Type D tripping characteristic.

What is the breaking capacity of the S803N-D16?

The S803N-D16 has a rated ultimate short-circuit breaking capacity (Icu) of 36 kA at 415 V AC, making it suitable for demanding installations with high prospective fault currents.

Why does the ABB S803N-D16 use a Type D characteristic?

The Type D characteristic is suited to circuits with high inrush currents, including suitable motor and transformer applications where temporary current peaks can occur during starting or energisation.

How many poles does the ABB S803N-D16 have?

The S803N-D16 is a 3-pole MCB with three protected poles, making it suitable for three-phase electrical circuit protection.

Trusted High-Performance Protection from ABB

ABB S800N high-performance miniature circuit breakers provide dependable overload and short-circuit protection for demanding commercial and industrial electrical installations, including circuits with high inrush currents and applications requiring high short-circuit breaking capacity.