Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S801U-K80 is an 80 A single-pole K-characteristic high-performance miniature circuit breaker with a 30 kA interrupting rating at 240 V AC according to UL 489 for demanding commercial and industrial circuit protection.
£104.62
The ABB S801U-K80 is a high-performance single-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits where a high breaking capacity is required. As part of the ABB S800U high-performance MCB series, it combines a 80 A rated current, K tripping characteristic and a 30 kA interrupting rating at 240 V AC according to UL 489.
Designed for commercial and industrial electrical distribution, the S801U-K80 provides dependable circuit protection in demanding installations with high prospective short-circuit currents. The S800U range also provides strong selectivity properties against upstream moulded-case circuit breakers and back-up protection with downstream miniature circuit breakers, supporting continuity and coordination within electrical distribution systems.
The S801U-K80 is a 1-pole device with a 240 V AC rated operational voltage and 240/415 V AC rated voltage. Its K characteristic makes it particularly suitable for appropriately designed circuits where equipment can produce higher starting or inrush currents, while compliance with UL 489, CSA C22.2 No. 5 and IEC/EN 60947-2 supports professional industrial and commercial applications.
The ABB S800U range is designed for the protection and control of electrical circuits against overloads and short circuits when high breaking capacity is required. The S800 platform combines compact construction with high short-circuit performance and is intended for demanding commercial and industrial electrical distribution applications.
The K characteristic makes the S801U-K80 suitable for appropriately designed circuits where normal operation may involve elevated starting or inrush currents. Combined with an 80 A current rating and 30 kA UL 489 interrupting capability, it provides robust protection for higher-current branch circuits, machinery and industrial distribution systems.
Tick the specs you need, then view products that match.
| Certification | UL 489 | |
|---|---|---|
| Series | S800U | |
| ABB order code | 2CCS881017R0627 | |
| Product type | High-performance miniature circuit breaker (MCB) | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Rated current | 80 A | |
| Tripping characteristic | K | |
| Interrupting rating according to UL 489 | 30 kA at 240 V AC | |
| Rated ultimate short-circuit breaking capacity | 30 kA at 240 V AC | |
| Rated operational voltage | 240 V AC | |
| Rated voltage | 240/415 V AC | |
| Power loss | 6.4 W per pole at rated operating conditions | |
| Standards | IEC/EN 60947-2, UL 489, CSA C22.2 No. 5 | |
| Weight | approx. 0.25 kg | |
| EAN | 7612271214364 |
The S801U-K80 is a high-performance miniature circuit breaker designed to protect demanding commercial and industrial electrical circuits against overloads and short circuits.
The ABB S801U-K80 has a rated current of 80 A.
The single-pole S801U-K80 has a 30 kA interrupting rating at 240 V AC according to UL 489.
The S801U-K80 uses a K tripping characteristic, making it suitable for appropriately designed circuits where higher starting or inrush currents may occur during normal operation.
The breaker is specified to IEC/EN 60947-2, UL 489 and CSA C22.2 No. 5 standards.
ABB S800U high-performance miniature circuit breakers provide robust overload and short-circuit protection for demanding commercial and industrial electrical distribution applications where high breaking capacity, reliable operation and recognised international standards are required.