ABB S803S-C6 is a 6 A three-pole Type C high-performance miniature circuit breaker with a maximum 50 kA breaking capacity at 240/415 V AC, AC/DC capability and current-limiting protection for demanding industrial circuits.
£194.80
The ABB S803S-C6 is a high-performance 3-pole miniature circuit breaker (MCB) designed for demanding industrial circuit protection. Part of the ABB S800S high-performance range, it combines a 6 A rated current, Type C tripping characteristic and a maximum 50 kA breaking capacity at 240/415 V AC.
The S803S-C6 is a current-limiting circuit breaker with separate thermal and electromechanical tripping mechanisms. The thermal mechanism provides overload protection, while the electromechanical mechanism responds rapidly to short-circuit conditions. ABB's fast arc-extinction technology helps limit fault energy and protect connected equipment.
With 3 protected poles, a 6 A rated current and Type C characteristic, the S803S-C6 is suitable for industrial distribution and equipment circuits with moderate functional inrush currents. Its cage-terminal construction, AC/DC capability and compliance with IEC/EN 60947-2, IEC/EN 60898-1 and UL 1077 make it a versatile high-performance protection device.
The ABB S803S-C6 combines high short-circuit breaking performance with a Type C characteristic suited to general industrial loads and circuits with moderate starting currents. Its three protected poles allow simultaneous protection of three-phase circuits, while the thermal and electromechanical releases provide dedicated responses to overload and short-circuit conditions.
The current-limiting construction and fast arc-extinction system help reduce the energy passed downstream during severe faults. With ratings for AC and DC operation, multiple international standards and a broad ABB accessory platform, the S803S-C6 is suitable for industrial switchboards, machinery, control equipment and distribution systems requiring dependable high-fault-level protection.
Tick the specs you need, then view products that match.
| Certification | UL 1077 | |
|---|---|---|
| Series | S800S / S803S | |
| ABB order code | 2CCS863001R0064 | |
| Product type | High-performance miniature circuit breaker (MCB) | |
| Number of poles | 3 | |
| Number of protected poles | 3 | |
| Rated current | 6 A | |
| Tripping characteristic | Type C | |
| Rated operational voltage | up to 690 V AC / 375 V DC according to IEC 60947-2 | |
| Rated ultimate short-circuit breaking capacity (Icu) | 50 kA at 240/415 V AC | |
| Icu at 254/440 V AC | 30 kA | |
| Icu at 400/690 V AC | 6 kA | |
| Icu at 125 V DC | 30 kA | |
| Rated service short-circuit breaking capacity (Ics) | 40 kA at 415 V AC | |
| Rated short-circuit capacity (Icn) | 25 kA at 400 V AC | |
| UL 1077 interrupting rating | 30 kA at 240 V AC | |
| Rated insulation voltage (Ui) | 690 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Voltage type | AC/DC | |
| Power loss | 1.8 W per pole / 5.4 W total | |
| Current limiting class | 3 | |
| Overvoltage category | IV | |
| Pollution degree | 3 | |
| Degree of protection | IP20 | |
| Operating ambient temperature | -25 to +60 °C | |
| Terminal type | Cage terminal | |
| Mounting | DIN rail | |
| Installation width | 4.5 modules / 81 mm | |
| Height | 95 mm | |
| Depth | 82.5 mm | |
| Mechanical endurance | 10,000 cycles | |
| Standards | IEC/EN 60947-2, IEC/EN 60898-1, UL 1077 | |
| Weight | approx. 0.74 kg | |
| EAN / GTIN | 7612271408169 | |
| Product group | S800 / S800P / S750 MCB |
The ABB S803S-C6 is a high-performance three-pole miniature circuit breaker designed to protect industrial AC and DC circuits against overload and short-circuit conditions, including three-phase distribution, machinery and control applications.
The S803S-C6 has a rated current of 6 A and a Type C tripping characteristic, making it suitable for general industrial circuits and loads that can experience moderate starting currents.
The S803S-C6 has a maximum rated ultimate short-circuit breaking capacity (Icu) of 50 kA at 240/415 V AC. Its Icu varies with operating voltage, including 30 kA at 254/440 V AC and 6 kA at 400/690 V AC.
Yes. The S803S-C6 supports AC and DC applications and has a rated operational voltage of up to 375 V DC according to IEC 60947-2, subject to the appropriate circuit configuration and ABB application requirements.
The ABB S803S-C6 is specified to IEC/EN 60947-2, IEC/EN 60898-1 and UL 1077, supporting use across a wide range of industrial and supplementary circuit protection applications.
ABB S800S high-performance miniature circuit breakers combine current-limiting technology, fast arc extinction and high short-circuit breaking capacity to provide dependable overload and fault protection for demanding industrial distribution, machinery and control applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.