2CCS863001R0064 ABB S803S-C6 High Performance MCB 50kA 3P Type C 6A

2CCS863001R0064 ABB S803S-C6 High Performance MCB 50kA 3P Type C 6A

ABB S803S-C6 is a 6 A three-pole Type C high-performance miniature circuit breaker with a maximum 50 kA breaking capacity at 240/415 V AC, AC/DC capability and current-limiting protection for demanding industrial circuits.

SKU: 2CCS863001R0064Alt SKU: S803SC6MPN: 2CCS863001R0064
Price
List Price £299.69 ex VAT
Your Price (ex VAT) Save 35%
£194.80 35% OFF
You save £104.89 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £194.80
Trade pricing is personalised to your account

Manufacturer Lead Time

£194.80

Why Choose the ABB S803S-C6 High Performance MCB?

The ABB S803S-C6 is a high-performance 3-pole miniature circuit breaker (MCB) designed for demanding industrial circuit protection. Part of the ABB S800S high-performance range, it combines a 6 A rated current, Type C tripping characteristic and a maximum 50 kA breaking capacity at 240/415 V AC.

The S803S-C6 is a current-limiting circuit breaker with separate thermal and electromechanical tripping mechanisms. The thermal mechanism provides overload protection, while the electromechanical mechanism responds rapidly to short-circuit conditions. ABB's fast arc-extinction technology helps limit fault energy and protect connected equipment.

With 3 protected poles, a 6 A rated current and Type C characteristic, the S803S-C6 is suitable for industrial distribution and equipment circuits with moderate functional inrush currents. Its cage-terminal construction, AC/DC capability and compliance with IEC/EN 60947-2, IEC/EN 60898-1 and UL 1077 make it a versatile high-performance protection device.

Key Advantages

  • High-performance 3-pole miniature circuit breaker for demanding industrial applications.
  • 6 A rated current with Type C tripping characteristic.
  • Maximum 50 kA breaking capacity at 240/415 V AC.
  • Suitable for AC operating voltages up to 690 V AC and DC applications up to 375 V DC.
  • Current-limiting design with fast arc extinction helps reduce fault energy.
  • Separate thermal overload and electromechanical short-circuit tripping mechanisms.
  • Cage terminal construction for secure conductor connection.
  • Extensive ABB S800 accessory range supports flexible system integration.

Key Features

  • ABB S800S / S803S high-performance MCB range.
  • 3 poles with 3 protected poles.
  • 6 A rated current.
  • Type C tripping characteristic.
  • 50 kA Icu at 240/415 V AC.
  • 40 kA Ics at 415 V AC.
  • 25 kA Icn at 400 V AC.
  • 690 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • AC/DC circuit protection capability.
  • IP20 degree of protection.
  • DIN-rail mounting with 4.5-module installation width.

High-Performance Three-Phase Circuit Protection

The ABB S803S-C6 combines high short-circuit breaking performance with a Type C characteristic suited to general industrial loads and circuits with moderate starting currents. Its three protected poles allow simultaneous protection of three-phase circuits, while the thermal and electromechanical releases provide dedicated responses to overload and short-circuit conditions.

The current-limiting construction and fast arc-extinction system help reduce the energy passed downstream during severe faults. With ratings for AC and DC operation, multiple international standards and a broad ABB accessory platform, the S803S-C6 is suitable for industrial switchboards, machinery, control equipment and distribution systems requiring dependable high-fault-level protection.

Typical Applications

  • Three-phase industrial electrical distribution systems.
  • Industrial machinery and automation equipment.
  • Control panels and switchboards.
  • Commercial and industrial distribution boards.
  • Circuits with moderate functional starting or inrush currents.
  • AC and DC equipment protection.
  • Supplementary protection applications requiring UL 1077 recognition.
  • Installations requiring high short-circuit breaking capacity.

Technical Specifications

Tick the specs you need, then view products that match.

Certification UL 1077
Series S800S / S803S
ABB order code 2CCS863001R0064
Product type High-performance miniature circuit breaker (MCB)
Number of poles 3
Number of protected poles 3
Rated current 6 A
Tripping characteristic Type C
Rated operational voltage up to 690 V AC / 375 V DC according to IEC 60947-2
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 240/415 V AC
Icu at 254/440 V AC 30 kA
Icu at 400/690 V AC 6 kA
Icu at 125 V DC 30 kA
Rated service short-circuit breaking capacity (Ics) 40 kA at 415 V AC
Rated short-circuit capacity (Icn) 25 kA at 400 V AC
UL 1077 interrupting rating 30 kA at 240 V AC
Rated insulation voltage (Ui) 690 V
Rated impulse withstand voltage (Uimp) 8 kV
Voltage type AC/DC
Power loss 1.8 W per pole / 5.4 W total
Current limiting class 3
Overvoltage category IV
Pollution degree 3
Degree of protection IP20
Operating ambient temperature -25 to +60 °C
Terminal type Cage terminal
Mounting DIN rail
Installation width 4.5 modules / 81 mm
Height 95 mm
Depth 82.5 mm
Mechanical endurance 10,000 cycles
Standards IEC/EN 60947-2, IEC/EN 60898-1, UL 1077
Weight approx. 0.74 kg
EAN / GTIN 7612271408169
Product group S800 / S800P / S750 MCB

Frequently Asked Questions

What is the ABB S803S-C6 used for?

The ABB S803S-C6 is a high-performance three-pole miniature circuit breaker designed to protect industrial AC and DC circuits against overload and short-circuit conditions, including three-phase distribution, machinery and control applications.

What is the rated current and trip characteristic of the S803S-C6?

The S803S-C6 has a rated current of 6 A and a Type C tripping characteristic, making it suitable for general industrial circuits and loads that can experience moderate starting currents.

What is the breaking capacity of the ABB S803S-C6?

The S803S-C6 has a maximum rated ultimate short-circuit breaking capacity (Icu) of 50 kA at 240/415 V AC. Its Icu varies with operating voltage, including 30 kA at 254/440 V AC and 6 kA at 400/690 V AC.

Can the ABB S803S-C6 be used on DC circuits?

Yes. The S803S-C6 supports AC and DC applications and has a rated operational voltage of up to 375 V DC according to IEC 60947-2, subject to the appropriate circuit configuration and ABB application requirements.

Which standards does the ABB S803S-C6 comply with?

The ABB S803S-C6 is specified to IEC/EN 60947-2, IEC/EN 60898-1 and UL 1077, supporting use across a wide range of industrial and supplementary circuit protection applications.

Trusted Industrial Circuit Protection from ABB

ABB S800S high-performance miniature circuit breakers combine current-limiting technology, fast arc extinction and high short-circuit breaking capacity to provide dependable overload and fault protection for demanding industrial distribution, machinery and control applications.