2CCS862017R0605 ABB S802U-Z60 High Performance MCB 50kA 2P Z 60A UL489

2CCS862017R0605 ABB S802U-Z60 High Performance MCB 50kA 2P Z 60A UL489

ABB S802U-Z60 is a 60 A two-pole Z-characteristic high-performance miniature circuit breaker with a 50 kA interrupting rating at 240 V AC under UL 489 and a 50 kA ultimate short-circuit breaking capacity at 415 V AC under IEC/EN 60947-2.

SKU: 2CCS862017R0605Alt SKU: S802UZ60MPN: 2CCS862017R0605
Price
List Price £240.65 ex VAT
Your Price (ex VAT) Save 35%
£156.42 35% OFF
You save £84.23 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £156.42
Trade pricing is personalised to your account

Manufacturer Lead Time

£156.42

Why Choose the ABB S802U-Z60 High Performance MCB?

The ABB S802U-Z60 is a high-performance 2-pole miniature circuit breaker (MCB) designed for demanding commercial and industrial circuit protection. Part of the ABB S800U high-performance range, it combines a 60 A rated current, Z tripping characteristic and a high 50 kA interrupting rating for installations where substantial prospective fault currents may occur.

The S802U-Z60 protects cables, conductors and connected equipment against overload and short-circuit conditions. Its thermal release mechanism provides overload protection, while its electromechanical release mechanism responds rapidly to short circuits. The Z characteristic provides sensitive magnetic operation, making it suitable for circuits where a fast response to fault current is important.

With a rated current of 60 A, a Z tripping characteristic and a 50 kA interrupting rating at 240 V AC under UL 489, the S802U-Z60 delivers robust two-pole circuit protection. It also provides a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC under IEC/EN 60947-2 and is designed for demanding industrial installations.

Key Advantages

  • High-performance 2-pole miniature circuit breaker for demanding electrical applications.
  • 60 A rated current with sensitive Z tripping characteristic.
  • High 50 kA interrupting rating at 240 V AC according to UL 489.
  • 50 kA Icu at 415 V AC according to IEC/EN 60947-2.
  • Thermal release provides dependable overload protection.
  • Electromechanical release provides rapid short-circuit protection.
  • Interchangeable cage terminal design supports practical installation and servicing.
  • Designed to UL 489, CSA C22.2 No. 5 and IEC/EN 60947-2 requirements.

Key Features

  • ABB S800U / S802U high-performance MCB range.
  • 2-pole configuration.
  • 60 A rated current.
  • Z tripping characteristic.
  • 50 kA interrupting rating at 240 V AC under UL 489.
  • 50 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 5.8 W power loss.
  • IP20 degree of protection.
  • Interchangeable cage terminal system.
  • Operating ambient temperature range of -25 to +60 °C.
  • Compact dimensions of approximately 54 × 95 × 82.5 mm.
  • Complies with IEC/EN 60947-2, UL 489 and CSA C22.2 No. 5.

Sensitive High-Fault-Level Circuit Protection

The ABB S802U-Z60 combines the sensitive response of a Z-characteristic breaker with the high fault-clearing performance of ABB's S800U platform. Its thermal release protects against sustained overload conditions, while its electromechanical release provides rapid interruption of short-circuit currents and ABB's fast arc-extinguishing technology helps limit the effects of severe faults.

The combination of a 50 kA UL 489 interrupting rating at 240 V AC and a 50 kA Icu rating at 415 V AC under IEC/EN 60947-2 makes the S802U-Z60 suitable for demanding industrial distribution and equipment circuits. Its Z characteristic is particularly useful where sensitive overcurrent protection is required, including long cable runs and electrical or electronic loads requiring rapid magnetic fault response.

Typical Applications

  • Commercial and industrial electrical distribution systems.
  • Sensitive electrical and electronic equipment circuits.
  • Long cable runs requiring sensitive overcurrent protection.
  • Industrial switchboards and distribution boards.
  • Machinery and automation control panels.
  • Branch-circuit protection requiring UL 489 compliance.
  • Industrial equipment requiring high short-circuit protection performance.
  • Installations requiring a 50 kA interrupting rating.

Technical Specifications

Tick the specs you need, then view products that match.

Certification UL 489
Series S800U / S802U
ABB order code 2CCS862017R0605
Product type High-performance miniature circuit breaker (MCB)
Number of poles 2
Rated current 60 A
Tripping characteristic Z
Rated voltage 240 V AC
UL 489 interrupting rating 50 kA at 240 V AC
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 415 V AC
Protection function Overload and short-circuit protection
Overload release Thermal release mechanism
Short-circuit release Electromechanical release mechanism
Power loss 5.8 W
Degree of protection IP20
Operating ambient temperature -25 to +60 °C
Terminal type Interchangeable cage terminal
Width 54 mm
Height 95 mm
Depth 82.5 mm
Installation width 3 modules
Standards IEC/EN 60947-2, UL 489, CSA C22.2 No. 5
Weight approx. 0.49 kg
EAN / GTIN 7612271214777
Product group S800 / S800P / S750 MCB

Frequently Asked Questions

What is the ABB S802U-Z60 used for?

The ABB S802U-Z60 is a high-performance two-pole miniature circuit breaker designed to protect commercial and industrial circuits against overload and short-circuit conditions, particularly where sensitive Z-characteristic protection and high fault-breaking performance are required.

What is the rated current of the S802U-Z60?

The S802U-Z60 has a rated current of 60 A and uses a Z tripping characteristic.

What is the interrupting rating of the ABB S802U-Z60?

The ABB S802U-Z60 has a 50 kA interrupting rating at 240 V AC under UL 489 and a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC under IEC/EN 60947-2.

What is the Z characteristic suitable for?

The Z characteristic provides sensitive magnetic overcurrent protection and is particularly useful for circuits where rapid fault response is required, including sensitive electrical equipment and long cable circuits.

Is the ABB S802U-Z60 UL 489 certified?

Yes. The ABB S802U-Z60 is designed to UL 489 and CSA C22.2 No. 5 requirements and also complies with IEC/EN 60947-2, supporting use in applicable North American and international industrial installations.

Trusted Industrial Circuit Protection from ABB

ABB S800U high-performance miniature circuit breakers combine high interrupting capacity, fast fault interruption and dependable overload and short-circuit protection, providing robust solutions for demanding commercial and industrial applications requiring UL 489, CSA and IEC-compliant circuit protection.