2CCS862001R0321 ABB S802S-D32 32A 2-Pole Type D 50kA MCB

2CCS862001R0321 ABB S802S-D32 32A 2-Pole Type D 50kA MCB

ABB S802S-D32 is a 32 A 2-pole Type D high-performance miniature circuit breaker with up to 50 kA breaking capacity for overload and short-circuit protection in demanding electrical installations.

SKU: 2CCS862001R0321Alt SKU: S802SD32MPN: 2CCS862001R0321
Price
List Price £180.95 ex VAT
Your Price (ex VAT) Save 35%
£117.62 35% OFF
You save £63.33 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £117.62
Trade pricing is personalised to your account

Manufacturer Lead Time

£117.62

Why Choose the ABB S802S-D32 High Performance MCB?

The ABB S802S-D32 is a high-performance 2-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits in demanding residential, commercial and industrial installations. As part of the proven ABB S800S high-performance circuit breaker series, it combines compact modular construction with high short-circuit interruption capability.

This circuit breaker features a Type D tripping characteristic and a rated current of 32 A, making it particularly suitable for circuits supplying equipment with comparatively high starting or inrush currents. It incorporates a thermal tripping mechanism for overload protection and an electromechanical tripping mechanism for rapid short-circuit protection.

With a maximum breaking capacity of 50 kA at 240/415 V AC, the S802S-D32 is engineered for installations where high prospective fault currents demand greater interruption capability than conventional miniature circuit breakers. It can be used at voltages up to 400/690 V AC and is also suitable for specified DC applications.

Key Advantages

  • High-performance 2-pole miniature circuit breaker for demanding electrical installations.
  • 32 A rated current with Type D tripping characteristic.
  • Maximum breaking capacity of 50 kA at 240/415 V AC.
  • Thermal overload and electromechanical short-circuit tripping mechanisms.
  • Current-limiting design with fast arc extinction for dependable fault interruption.
  • Suitable for residential, commercial and industrial circuit protection applications.

Key Features

  • ABB S800S high-performance MCB series.
  • 2-pole configuration.
  • 32 A rated current.
  • Type D tripping characteristic.
  • 50 kA rated ultimate short-circuit breaking capacity at 240/415 V AC.
  • 25 kA rated short-circuit capacity at 230/400 V AC.
  • Suitable for voltages up to 400/690 V AC.
  • Cage terminal connection system.
  • Fast arc extinction for reliable interruption of fault currents.

Reliable High-Performance Circuit Protection

Miniature circuit breakers such as the ABB S802S-D32 automatically disconnect an electrical circuit when excessive current results from an overload or short circuit. Its thermal tripping mechanism provides overload protection, while the electromechanical tripping mechanism responds rapidly to short-circuit conditions.

The Type D characteristic is particularly suited to circuits where higher transient starting currents may occur. Combined with the S800S series' current-limiting design, high breaking capacity and rapid arc extinction, this makes the S802S-D32 a dependable protection solution for demanding electrical distribution and machinery applications.

Typical Applications

  • Industrial electrical distribution systems.
  • Machinery and automation control panels.
  • Circuits with high starting or inrush currents.
  • Commercial electrical installations.
  • Motor, transformer and inductive-load circuits.
  • High fault-level distribution and protection systems.

Technical Specifications

Series S800S
ABB order code 2CCS862001R0321
EAN / GTIN 7612271201135
Product type High-performance miniature circuit breaker (MCB)
Number of poles 2
Rated current 32 A
Tripping characteristic Type D
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 240/415 V AC
Rated short-circuit capacity (Icn) 25 kA at 230/400 V AC
Rated frequency 50/60 Hz
Terminal type Cage terminal
Power loss 3.7 W per pole at rated operating conditions
Protection rating IP20
Operating temperature -25 to +60 °C
Standards IEC/EN 60947-2, IEC/EN 60898-1, UL 1077
Dimensions (W × H × D) 54 × 95 × 82.5 mm
Weight approx. 0.49 kg

Frequently Asked Questions

What is the ABB S802S-D32 used for?

The S802S-D32 is a high-performance miniature circuit breaker used to protect electrical circuits against overloads and short circuits in residential, commercial and industrial installations.

What is the rated current of the ABB S802S-D32?

The circuit breaker has a rated current of 32 A.

What tripping characteristic does the S802S-D32 use?

The S802S-D32 has a Type D tripping characteristic, making it suitable for circuits where comparatively high starting or inrush currents can occur.

What is the breaking capacity of the ABB S802S-D32?

The S802S-D32 has a maximum breaking capacity of 50 kA at 240/415 V AC.

How many poles does the S802S-D32 have?

The S802S-D32 is a 2-pole high-performance circuit breaker designed for simultaneous protection across two poles.

Trusted High-Performance Protection from ABB

ABB S800S high-performance miniature circuit breakers provide dependable overload and short-circuit protection for demanding electrical systems, combining high breaking capacity, current-limiting performance and fast arc extinction.