ABB S801S-D50 is a 50 A single-pole Type D high-performance miniature circuit breaker with an ultimate short-circuit breaking capacity of up to 50 kA at 240 V AC for demanding commercial and industrial circuit protection.
£64.12
The ABB S801S-D50 is a high-performance single-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits. As part of the ABB S800S high-performance circuit breaker series, it combines robust current-limiting technology with a high breaking capacity for dependable protection in demanding commercial and industrial electrical installations.
Featuring a Type D tripping characteristic and a rated current of 50 A, the S801S-D50 is particularly suitable for circuits with comparatively high starting or inrush currents. Its thermal trip mechanism provides overload protection, while electromagnetic tripping enables rapid interruption during short-circuit conditions.
With an ultimate short-circuit breaking capacity of up to 50 kA at 240 V AC, the S801S-D50 is engineered for installations where substantial prospective fault currents may occur. Its compact DIN-rail format and high-performance interruption technology make it suitable for industrial distribution systems, machinery and automation control panels.
The ABB S801S-D50 combines thermal overload protection with electromagnetic short-circuit protection. Its Type D tripping characteristic allows appropriately designed circuits to tolerate comparatively high transient currents while maintaining dependable protection against sustained overloads and fault currents.
The S800S platform is designed for rapid fault interruption and effective current limitation in demanding electrical systems. These characteristics make the S801S-D50 suitable for industrial distribution boards, machine control systems and circuits supplying equipment with significant starting or energisation currents.
| Series | S800S |
|---|---|
| ABB order code | 2CCS861001R0501 |
| Product type | High-performance miniature circuit breaker (MCB) |
| Number of poles | 1 |
| Protected poles | 1 |
| Rated current | 50 A |
| Tripping characteristic | Type D |
| Rated operational voltage | 230 V AC according to IEC/EN 60898-1; 400 V AC according to IEC/EN 60947-2 |
| Ultimate short-circuit breaking capacity (Icu) | 50 kA at 240 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Terminal type | Cage / screw terminal |
| Flexible conductor capacity | up to 50 mm² |
| Rigid conductor capacity | up to 70 mm² |
| Mounting type | DIN rail |
| Dimensions (H × W × D) | 95 × 27 × 82.5 mm |
| Standards | IEC/EN 60898-1, IEC/EN 60947-2 |
The ABB S801S-D50 protects electrical circuits against overloads and short circuits and is particularly suitable for applications where higher starting or inrush currents require a Type D tripping characteristic.
The S801S-D50 has a rated current of 50 A.
The S801S-D50 uses a Type D tripping characteristic, making it suitable for appropriately designed circuits with comparatively high starting or inrush currents.
The S801S-D50 has an ultimate short-circuit breaking capacity of up to 50 kA at 240 V AC.
The S801S-D50 is a single-pole (1P) high-performance miniature circuit breaker.
ABB S800S high-performance miniature circuit breakers provide dependable overload and short-circuit protection for demanding commercial and industrial electrical systems where high breaking capacity, current limitation and reliable operation are required.