2CCS861001R0065 ABB S801S-B6 MCB 50 kA 1P Type B 6 A

2CCS861001R0065 ABB S801S-B6 MCB 50 kA 1P Type B 6 A

ABB S801S-B6 is a single-pole 6 A Type B high-performance miniature circuit breaker with 50 kA ultimate short-circuit breaking capacity at 240/415 V AC for overload and short-circuit protection in demanding AC and DC applications.

SKU: 2CCS861001R0065Alt SKU: S801SB6MPN: 2CCS861001R0065
Price
List Price £100.53 ex VAT
Your Price (ex VAT) Save 35%
£65.34 35% OFF
You save £35.19 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £65.34
Trade pricing is personalised to your account

Manufacturer Lead Time

£65.34

Why Choose the ABB S801S-B6 High-Performance MCB?

The ABB S801S-B6 is a single-pole, 6 A high-performance miniature circuit breaker with a Type B tripping characteristic, designed to protect electrical installations against overloads and short circuits where a high breaking capacity is required. Part of ABB's S800S range, it combines compact DIN-rail construction with powerful current-limiting performance for demanding commercial and industrial applications.

The S801S-B6 provides an ultimate short-circuit breaking capacity of 50 kA at 240/415 V AC, with additional ratings of 30 kA at 254/440 V AC, 6 kA at 400/690 V AC and 30 kA at 125 V DC. Its Type B characteristic provides sensitive magnetic tripping suited to circuits with relatively low normal inrush currents.

Protection is provided through a thermal tripping mechanism for overload conditions and an electromechanical tripping mechanism for short circuits. Fast arc extinction and current-limiting operation help reduce fault energy, while the interchangeable cage terminal, robust S800S construction and broad accessory range support reliable installation in professional distribution systems.

Key Advantages

  • 50 kA ultimate short-circuit breaking capacity at 240/415 V AC.
  • 6 A rated current with a Type B tripping characteristic.
  • Single-pole configuration for compact circuit protection.
  • Thermal tripping mechanism provides dependable overload protection.
  • Electromechanical tripping mechanism provides rapid short-circuit protection.
  • Current-limiting design and fast arc extinction help minimise fault energy.
  • Suitable for AC and DC applications within the specified device ratings.
  • Interchangeable cage terminal supports flexible installation and servicing.

Key Features

  • ABB S800S high-performance MCB range.
  • 6 A rated current.
  • Type B tripping characteristic.
  • 1P / one protected pole.
  • 50 kA Icu at 240/415 V AC.
  • 30 kA Icu at 254/440 V AC.
  • 6 kA Icu at 400/690 V AC.
  • 30 kA Icu at 125 V DC.
  • Interchangeable cage terminal connection.
  • Complies with IEC/EN 60947-2 and is recognised to UL 1077.

High-Performance Type B Circuit Protection

The ABB S800S platform is engineered for electrical installations where high prospective fault currents demand greater breaking performance than conventional miniature circuit breakers can provide. The S801S-B6 combines rapid electromagnetic fault interruption with effective current limitation and fast arc extinction, helping reduce the electrical and thermal stresses generated during a short circuit.

Its Type B characteristic provides sensitive magnetic operation for circuits where normal starting currents are relatively low, making it well suited to appropriate resistive, control and distribution loads. With AC and DC capability, interchangeable terminals and compatibility with ABB's extensive S800 accessory system, the S801S-B6 provides a versatile solution for professional circuit protection.

Typical Applications

  • Industrial electrical distribution systems.
  • Commercial distribution boards and switchgear.
  • Control and auxiliary power circuits.
  • Resistive loads with relatively low normal inrush currents.
  • Machine and automation control panels.
  • Installations with high prospective short-circuit currents.
  • AC and DC circuit protection within the specified device ratings.

Technical Specifications

Tick the specs you need, then view products that match.

Certification UL 1077
Series S800S
Product group S800 / S800P / S750 MCB
ABB order code 2CCS861001R0065
EAN / GTIN 7612271408107
Product type High-performance miniature circuit breaker
Rated current 6 A
Number of poles 1P
Tripping characteristic Type B
Maximum operating voltage Up to 400/690 V AC
DC application Up to 125 V DC for single-pole configuration
Ultimate breaking capacity (Icu>) at 240/415 V AC 50 kA
Ultimate breaking capacity (Icu>) at 254/440 V AC 30 kA
Ultimate breaking capacity (Icu>) at 400/690 V AC 6 kA
Ultimate breaking capacity (Icu>) at 125 V DC 30 kA
UL 1077 interrupting rating at 240 V AC 30 kA
UL 1077 interrupting rating at 277 V AC 14 kA
UL 1077 interrupting rating at 347 V AC 6 kA
Overload protection Thermal tripping mechanism
Short-circuit protection Electromechanical tripping mechanism
Terminal type Interchangeable cage terminal
Terminal tightening torque 3.5 Nm
Power loss 1.8 W per pole
Mounting DIN rail
Protection rating IP20
Standards IEC/EN 60947-2, IEC/EN 60898-1, UL 1077
Dimensions (H × W × D) 95 × 27 × 82.5 mm
Product net weight approx. 0.24 kg
Pack quantity 1 piece

Frequently Asked Questions

What is the ABB S801S-B6 used for?

The ABB S801S-B6 is a single-pole high-performance miniature circuit breaker designed to protect electrical circuits against overload and short-circuit currents in demanding commercial and industrial installations.

What is the rated current and tripping characteristic of the S801S-B6?

The S801S-B6 has a rated current of 6 A and a Type B tripping characteristic, making it suitable for appropriate circuits with relatively low normal starting or inrush currents.

What is the breaking capacity of the ABB S801S-B6?

The S801S-B6 has an ultimate short-circuit breaking capacity of 50 kA at 240/415 V AC. Its available breaking capacity varies according to the applied operational voltage.

Can the ABB S801S-B6 be used on DC circuits?

Yes. The single-pole S801S-B6 can be used at up to 125 V DC, where ABB specifies an ultimate short-circuit breaking capacity of 30 kA.

How does the S801S-B6 protect against overloads and short circuits?

The S801S-B6 uses a thermal tripping mechanism for overload protection and an electromechanical tripping mechanism for short-circuit protection, while its current-limiting construction and fast arc extinction help reduce fault energy.

Trusted High-Performance Circuit Protection from ABB

ABB S800S high-performance miniature circuit breakers combine high short-circuit breaking capacity, effective current limitation and robust construction, with the S801S-B6 providing dependable 6 A Type B protection for demanding single-pole electrical circuits.