2CCS573103R8537 ABB S403M-K32NP 32 A Type K 3P+NP Miniature Circuit Breaker

2CCS573103R8537 ABB S403M-K32NP 32 A Type K 3P+NP Miniature Circuit Breaker

ABB S403M-K32NP is a 32 A Type K 3P+NP SMISSLINE TP miniature circuit breaker rated at 415 V AC with 10 kA breaking capacity for overload and short-circuit protection.

SKU: 2CCS573103R8537Alt SKU: S403MK32NPMPN: 2CCS573103R8537
Price
List Price £191.25 ex VAT
Your Price (ex VAT) Save 35%
£124.31 35% OFF
You save £66.94 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £124.31
Trade pricing is personalised to your account

Manufacturer Lead Time

£124.31

Why Choose the ABB S403M-K32NP Miniature Circuit Breaker?

The ABB S403M-K32NP is a current-limiting SMISSLINE TP miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits. Part of the proven ABB S400M series, it combines a delayed thermal tripping mechanism for overload protection with an electromechanical tripping mechanism for short-circuit protection.

Designed specifically for the ABB SMISSLINE TP plug-in distribution system, the S403M-K32NP enables efficient integration into compatible commercial and industrial distribution assemblies. Its 3P+NP configuration provides three protected phase poles together with a protected neutral pole, with the neutral protected at 100% of the nominal value of the pole conductor.

With a rated current of 32 A, a Type K tripping characteristic, rated voltage of 415 V AC and a rated short-circuit breaking capacity of 10 kA, the S403M-K32NP is particularly suited to circuits supplying motors, transformers and other inductive equipment with elevated starting currents. Its plug-in construction provides a practical circuit-protection solution for professional SMISSLINE TP installations.

Key Advantages

  • Reliable overload and short-circuit protection for low-voltage electrical circuits.
  • 32 A rated current for commercial and industrial applications.
  • Type K tripping characteristic suited to loads with elevated starting and inrush currents.
  • 10 kA rated short-circuit breaking capacity.
  • 3P+NP configuration provides protection across three phases and neutral.
  • Neutral pole protected at 100% of the nominal pole-conductor rating.
  • Plug-in construction enables efficient integration with the ABB SMISSLINE TP system.

Key Features

  • ABB SMISSLINE TP S400M series miniature circuit breaker.
  • 32 A nominal current.
  • Type K tripping characteristic.
  • 10 kA rated short-circuit breaking capacity.
  • 3P+NP pole configuration with four protected poles.
  • 415 V AC rated voltage.
  • 4 kV rated impulse withstand voltage.
  • Thermal overload and electromechanical short-circuit tripping mechanisms.
  • IP20 degree of protection.
  • Four-module plug-in design for compatible SMISSLINE TP distribution systems.

Reliable Circuit Protection for High-Inrush Loads

Miniature circuit breakers such as the ABB S403M-K32NP automatically disconnect a circuit when excessive current occurs. The delayed thermal tripping mechanism responds to sustained overload conditions, while the electromechanical mechanism provides rapid short-circuit protection, helping protect conductors, cables and connected electrical equipment.

The Type K characteristic is particularly useful for circuits containing motors, transformers and other inductive loads where elevated starting currents can occur during normal operation. Combined with the SMISSLINE TP plug-in architecture, the S403M-K32NP provides dependable protection while supporting efficient installation and maintenance in professional electrical distribution systems.

Typical Applications

  • Industrial motor and machinery circuits.
  • Transformers and inductive electrical loads.
  • ABB SMISSLINE TP distribution boards.
  • Three-phase circuits requiring protected neutral functionality.
  • Industrial automation and control-panel power distribution.
  • Commercial and industrial low-voltage distribution systems.

Technical Specifications

Series S400M / SMISSLINE TP
ABB order code 2CCS573103R8537
Product type Miniature circuit breaker (MCB)
Rated current 32 A
Tripping characteristic Type K
Pole configuration 3P+NP
Number of protected poles 4
Rated voltage 415 V AC
Frequency 50–60 Hz
Rated short-circuit breaking capacity 10 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 15 kA
Rated insulation voltage (Ui) 440 V
Rated impulse withstand voltage (Uimp) 4 kV
Protection principle Thermal overload and electromechanical short-circuit tripping
Neutral protection 100% of nominal pole-conductor rating
Mounting system Plug-in SMISSLINE TP
Width 4 modules
Protection rating IP20
Solid conductor connection 0.75–35 mm²
Multi-wired conductor connection 0.75–25 mm²
Operating temperature −25 to +60 °C
Standard IEC/EN 60947-2
EAN 7612270104215

Frequently Asked Questions

What is the ABB S403M-K32NP used for?

The S403M-K32NP is a miniature circuit breaker used to protect electrical circuits against overloads and short circuits within ABB SMISSLINE TP distribution systems.

What is the current rating of the S403M-K32NP?

The ABB S403M-K32NP has a rated current of 32 A.

What does the Type K characteristic mean?

The Type K tripping characteristic is suited to circuits with elevated short-duration starting currents, including appropriate motor, transformer and other inductive-load applications.

What is the breaking capacity of the S403M-K32NP?

The S403M-K32NP has a rated short-circuit breaking capacity of 10 kA and a rated ultimate short-circuit breaking capacity of 15 kA at 415 V AC.

How is the ABB S403M-K32NP installed?

The S403M-K32NP is designed as a plug-in circuit breaker for the ABB SMISSLINE TP system, allowing efficient integration into compatible SMISSLINE TP distribution assemblies.

Trusted ABB Circuit Protection

ABB SMISSLINE TP S400M miniature circuit breakers provide dependable overload and short-circuit protection with a practical plug-in architecture for commercial and industrial low-voltage distribution systems.