Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S403M-D20NP is a 20 A 3P+NP Type D miniature circuit breaker with four protected poles, 10 kA Icn and 50 kA Icu breaking capacities, designed for the SMISSLINE TP plug-in system.
£127.97
The ABB S403M-D20NP is a high-performance 3P+NP miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in commercial and industrial electrical distribution systems. As part of the ABB SMISSLINE TP S400M series, it combines a Type D tripping characteristic with a protected neutral and ABB's flexible plug-in distribution architecture.
With a rated current of 20 A and a Type D tripping characteristic, the S403M-D20NP is particularly suitable for circuits supplying equipment with high starting or inrush currents. Its four-pole arrangement protects three phase conductors together with the neutral, with the neutral protected at 100% of the nominal value of the pole conductor.
The S403M-D20NP provides a rated short-circuit breaking capacity of 10 kA Icn according to EN 60898-1 and an ultimate short-circuit breaking capacity of 50 kA Icu at 230/400 V AC according to IEC 60947-2. Designed specifically for the ABB SMISSLINE TP plug-in system, its four-module format provides robust protection while supporting efficient installation and modular distribution-board design.
Miniature circuit breakers such as the ABB S403M-D20NP protect electrical wiring and connected equipment against excessive current caused by overloads and short circuits. Thermal overload protection responds to sustained overcurrent conditions, while rapid electromagnetic operation provides protection against short-circuit faults.
The Type D characteristic is particularly suited to circuits where substantial short-duration starting currents can occur during normal operation. Combined with four protected poles and ABB's SMISSLINE TP plug-in architecture, the S403M-D20NP provides a practical protection solution for demanding three-phase and neutral industrial distribution systems.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | S400M |
| ABB order code | 2CCS573103R8201 |
| EAN / GTIN | 7612270104024 |
| Product type | Miniature circuit breaker (MCB) |
| Rated current | 20 A |
| Pole configuration | 3P+NP |
| Total poles | 4 |
| Protected poles | 4 |
| Neutral protection | 100% of nominal pole-conductor current |
| Tripping characteristic | Type D |
| Rated voltage | 230/400 V AC |
| Rated short-circuit breaking capacity Icn | 10 kA at 230/400 V AC |
| Rated ultimate short-circuit breaking capacity Icu | 50 kA at 230/400 V AC |
| Rated insulation voltage | 440 V |
| Rated impulse withstand voltage | 4 kV |
| Frequency | 50–60 Hz |
| Protection rating | IP20 |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Pollution degree | 3 |
| Power loss | 8 W |
| Operating temperature | -25 to +60 °C |
| Solid conductor capacity | 0.75–35 mm² |
| Stranded conductor capacity | 0.75–25 mm² |
| Electrical endurance | 10,000 cycles |
| Width | 4 modules |
| Installation depth | 75 mm |
| Mounting system | SMISSLINE TP plug-in system |
| Standards | EN 60898-1, IEC/EN 60947-2 |
| Weight | approx. 428 g |
The S403M-D20NP is a 3P+NP miniature circuit breaker designed to protect three-phase and neutral electrical circuits against overload and short-circuit currents, particularly where connected equipment can produce high starting or inrush currents.
The ABB S403M-D20NP has a rated current of 20 A.
The Type D tripping characteristic is suited to circuits containing equipment with high starting or inrush currents, such as compatible motors, transformers and other inductive industrial loads.
Yes. The S403M-D20NP has four protected poles, with the neutral protected at 100% of the nominal value of the pole conductor.
The S403M-D20NP has a rated short-circuit breaking capacity of 10 kA Icn at 230/400 V AC and a rated ultimate short-circuit breaking capacity of 50 kA Icu at 230/400 V AC.
ABB SMISSLINE TP circuit protection devices provide modular and dependable protection for commercial and industrial electrical distribution systems, combining plug-in installation with proven circuit-breaker technology for automation, machinery and power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.